Ragagep Update: Douglas Reindl, Director, IRC 2016 IRC R&T Forum
Ragagep Update: Douglas Reindl, Director, IRC 2016 IRC R&T Forum
• Mechanical integrity
• (j)(4)(ii) Inspection and testing procedures shall follow recognized
and generally accepted good engineering practices.
• (j)(4)(iii) The frequency of inspections and tests of process
equipment shall be consistent with applicable manufacturers’
recommendations and good engineering practices, and more
frequently if determined to be necessary by prior operating
experience.
Relevant standards - big picture
Section VIII
B31.5 –
Div. 1 –
ASME Pressure
Refrigerant
Piping
Vessels
Standard 15 –
Safety Standard
ASHRAE for Refrigeration
Systems
Standard 2 - Standard
Standard 1 - Standard
IIAR Definitions
Equip, Design,
& Installation
3 - Valves 4-
Installation
Standard 5 - Standard 7 –
Standard 8 -
IIAR (cont) Start-up and
Commissioning
Operating
procedures
Decommissioning
3
Principal Codes & Standards for Ammonia
Refrigeration
• ASME
• B&PV Code (Pressure vessels)
• B31.5 (Refrigeration Piping)
• IIAR
• IIAR 1, IIAR 2, IIAR 3, IIAR 4,
IIAR 5, IIAR 7, IIAR 8
• ASHRAE
• Standard 15, Standard 34
• Codes
• International Mechanical Code or
• Uniform Mechanical Code
• Other State & Local Codes
RAGAGEP
4
IIAR 2
Purpose:
to specify minimum requirements for the safe design of
closed-circuit ammonia refrigeration systems
Scope:
Applies to closed-circuit refrigeration systems using ammonia
as a refrigerant.
• Contents:
• Part 1 – General
• Part 2 – Design and installation
considerations affecting construction
• Part 3 – Equipment
• Part 4 - Appendices
6
IIAR 2
Table of Contents
1. Purpose, scope, applicability
Part 1
2. Definitions
3. Reference standards
4. Location of ammonia refrigeration machinery
5. General system design requirements
6. Machinery rooms Part 2
7
IIAR 2
Table of Contents
8. Compressors
9. Refrigerant pumps
10. Condensers
11. Evaporators
12. Pressure vessels Part 3
13. Piping
14. Packaged systems & equipment
15. Overpressure protection devices
16. Instrumentation & controls
17. Ammonia detection and alarms
8
Select definitions
• Machinery room
“An enclosed space that, where required by this standard to contain
equipment, must comply with the requirements set forth in Chapter 6.”
• Equipment
“An assembly, subassembly, accessory, or
component of a refrigeration system.”
• Principal machinery room door
“A door leading to the exterior of the machinery room designated by the
owner or designee as the primary emergency egress door from the
machinery room, which has required placarding.”
9
Select definitions
• Monitored
“A means of continuous oversight, such as notification of staff, a third-
party alarm service, or a responsible party.”
• Restricted
“Describes a premises or piece of equipment that is permitted to be
accessed by authorized personnel and specifically excludes public
access.”
• Authorized personnel
“Persons who, by virtue of their training and job description, have been
specifically granted permission to enter a restricted area, specifically
granted permission to perform restricted tasks or both.”
10
Egress & Doors NOT COMPLIANT
• IIAR 2 (2014)
• For machinery rooms greater than 1000 sq ft, requires at least two
exit doors
• Doors shall be separated by a horizontal distance equal to or greater
than half the maximum horizontal dimension of the room
• All portions of the machinery room shall be within 150 ft of an exit
door
• §6.10.2 – Door Features
• Self-closing and tight-fitting with panic hardware and door hinged to
swing in the direction of egress for occupants leaving the machinery
room
Machinery rooms
• Room access
• IIAR 2 - §6.3.4
• Access…shall be restricted to authorized
personnel. Signage on door shall comply with §6.15
12
Machinery Room Ventilation
Emergency ventilation
• Exhaust requirements
• Machinery room exhaust shall
• vent to the outdoors not closer than 20 ft from a property line [6.14.3.4]
• discharge vertically upward with a minimum discharge velocity of 2,500
ft/min at the required emergency ventilation rate [6.14.3.5]
• Power
• Emergency ventilation shall be powered independently of
equipment within the machinery room [6.14.7.3]
• A monitored location shall be notified upon a loss of power to
the emergency ventilation system [6.14.7.4]
14
Temperature control
• Room temperature limit
• Air flow required to limit room temperature dry bulb to 104°F
based on 1% design dry bulb [6.14.6.1]
• A reduced temperature control ventilation is permitted where
a means of cooling is provided or room electrical equipment
is designed to operate at an elevated temperature [6.14.6.1]
15
Machinery room ventilation
• Inlet air
• Make-up air provided to
• maintain machinery room under negative pressure not greater than 0.25
in H2O, relative to adjacent areas [6.14.5.1]
• prevent short-circuiting of make-up air directly to exhaust [6.14.5.2]
• positioned to draw in uncontaminated outdoor air [6.14.5.4]
• motorized dampers, if used, shall fail open on a loss of power [6.14.5.6]
Ventilation testing
• Testing
– A schedule for testing the mechanical ventilation system
shall be established based on manufacturers’
recommendations, unless modified based on documented
experience. Testing shall include operation of the
ventilation system based on ammonia detection at and by
manual control switch [6.14.8.1]
– … the mechanical ventilation system shall be tested at
least twice per year [6.14.8.2]
Ammonia detection
IIAR 2-2014
• 6.13.1 Ammonia detection and alarm
Machinery room shall be provided with ammonia detection and alarm in
accordance with Sections 17.2-17.6 and provide the following:
1. At least one detector shall be provided in room or area
2. Detector shall activate an alarm that reports to a monitored location
so that corrective action can be taken at a concentration of 25 ppm
or higher
3. Audible and visual alarms shall be provided inside the room to warn
that access to the room is restricted to authorized and emergency
personnel. Additional audible and visual alarms shall be located
outside of each entrance to the machinery room.
Ammonia detection
IIAR 2-2014
• 6.13.2 Alarm response
6.13.2.1 Below 25 ppm – no alarm
Drip pocket
QUESTIONS?