System No. C-AJ-2346: F Rating - 3 HR T Rating - 0 HR

This document provides a 3 hour fire-rated penetration seal for through penetrants in concrete floors or walls. It allows for up to 4 inch diameter pipes of various non-metallic materials, including PVC, CPVC, and ABS. The seal consists of intumescent wrap strips applied around the penetrant in two layers with butted seams offset, recessed half an inch from the surface. Additionally, caulk is applied within the annular space flush with the bottom surface to a depth of half an inch. Specific products rated for this assembly are identified.

Uploaded by

Arul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views

System No. C-AJ-2346: F Rating - 3 HR T Rating - 0 HR

This document provides a 3 hour fire-rated penetration seal for through penetrants in concrete floors or walls. It allows for up to 4 inch diameter pipes of various non-metallic materials, including PVC, CPVC, and ABS. The seal consists of intumescent wrap strips applied around the penetrant in two layers with butted seams offset, recessed half an inch from the surface. Additionally, caulk is applied within the annular space flush with the bottom surface to a depth of half an inch. Specific products rated for this assembly are identified.

Uploaded by

Arul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

System No.

C-AJ-2346
December 20, 2001

F Rating — 3 Hr

T Rating — 0 Hr

1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete floor or
min 5 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete wall. Wall may also be constructed of any UL
Classified Concrete Blocks*. Max diam of opening shall be 6 in.

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of
manufacturers.

2. Through Penetrants — One nonmetallic penetrant centered within the firestop system. The annular space between
pipe and periphery of opening shall be nom 3/4 in. Pipe to be rigidly supported on both sides of the floor assembly. The
following types and sizes of non-metallic pipe may be used:

A. Polyvinyl Chloride (PVC) Pipe — Nom 4 in. diam (or smaller) Schedule 40 solid core or
cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent)
piping systems.

B. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 4 in. diam (or smaller) SDR 13.5
CPVC pipe for use in closed (process or supply) piping systems.

C. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 4 in. diam (or smaller) Schedule 40
solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste
or vent) piping systems.

3. Firestop System — The details of the firestop system shall be as follows:

A. Fill, Void or Cavity Materials* - Wrap Strip — Nom 1/4 in. thick intumescent elastomeric
material faced on one side with plastic film, supplied in 2 in. wide strips. Two layers are
individually wrapped around the through penetrant with plastic film exposed and and ends
butted and held in place with tape or tie wire. Butted ends in successive layers shall be offset.
Wrap strip recessed ½ in. from bottom of floor or from the surface of each wall.
RECTORSEAL — Metacaulk Wrap Strip

B. Fill, Void or Cavity Materials* - Caulk — Nom ½ in. thickness of fill material applied within
the annulus, flush with bottom surface of floor or both surfaces of wall.

RECTORSEAL — Metacaulk 1000

*Bearing the UL Classification Mark