The document provides calculations for lateral load (F1, F2, F3), earthquake load analysis, and moment capacity of a 1m wall strip. It also includes designs for steel reinforcement of a footing, considering wide beam shear and two-way punching shear. Key parameters calculated include lateral loads, base shear, seismic coefficients, period of vibration, moment capacity, footing dimensions, steel reinforcement diameter and area.

Uploaded by

Frederick Quinto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
335 views

Swimming Pool Structural Calcs

The document provides calculations for lateral load (F1, F2, F3), earthquake load analysis, and moment capacity of a 1m wall strip. It also includes designs for steel reinforcement of a footing, considering wide beam shear and two-way punching shear. Key parameters calculated include lateral loads, base shear, seismic coefficients, period of vibration, moment capacity, footing dimensions, steel reinforcement diameter and area.

Uploaded by

Frederick Quinto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

LATERAL LOAD CALCULATIONS

F1 Calculation

γsat1 = 20.00 kN/cu.m


φ1 = 30.00 degrees
H1 = 1.39 m

k1 = 0.33
P1 = γsat1 *k1*H1
= 9.27 kN
F1 = P1*H1
= 12.88 kN

F2 Calculation

γ= 10.00 kN/cu.m
φ2 = 0.00 degrees
H2 = 1.39 m

k2 = 1.00
P2 = γsat2 *k2*H2
= 13.90 kN
F2 = 0.5*P2*H2
= 9.66 kN

F3 Calculation

γsat3 = 10.00 kN/cu.m


φ3 = 0.00 degrees
H3 = 0.71 m

k3 = 1.00
P3 = γsat3*k3*H3
= 7.10 kN
F3= 0.5*P3*H3
= 2.52 kN
Earthquake Load Analysis

Computation of Total Weight of Structural Frame


Volume kN/sq.m/kN/cu.m Weight (kN)
Walls 46.19 24 1108.56
Slabs 54.01 24 1296.24

1m Strip 2404.80
160.32

Soil Profile Type SD


Seismic zone gactor Z = 0.4 (Table 208-3)
Near Source factor Na = 1.05 (Table 208-5) Na Table 208-5 Nv Table 208-6
Near Source factor Nv = 1.3 (Table 208-6) 5 1.2 5 1.6
Seismic coefficient Ca = 0.462 (Table 208-7) 8.7 1.05 8.7 1.3
Seismic coefficient Cv = 0.832 (Table 208-8) 10 1 10 1.2
Importance factor I = 1.25 (Table 208-1)
Numerical coefficient R = 4.5 (Table 208-11)

Numerical coefficient for frame Ct = 0.0731


Total height Hn = 3.6 m

0.75
Period of vibration T = Ct Hn 0.19 sec

Total Seismic Dead Load W = 160.32 kN


Base shear V = Cv I W / (RT) 193.94 kN
V should not be less than V1 = 0.11 Ca I W 10.18 kN < 193.94 kN OK
V should not be less thanV2 = 0.80 Z Nv IW / R (for Zone 4) 18.53 kN < 193.94 kN OK
V need not exceed V3 = 2.50 Ca I W / R 51.44 kN < 193.94 kN OK
Use V = 51.44 kN

Additional lateral force concentrated at top of the structure Ft:


If T > 0.7 sec, Ft = 0.07V T but not exceeding 0.25V 0.25V = 48.48 kN
If T < 0.7 sec, Ft = 0
Ft = 0

Lateral Forces acting on the structure


Earthquake Loads (Input as Joint Loads to STAAD)
Level Wx (kN) hx (m) Wx hx (kN-m) Fx = Wx hx (V-Ft)/∑Wx hx) Z - Direction - Z - Direction X - Direction -X - Direction EL +X EL -X EL +Z EL -Z
Pool Top 160.32 3.60 577.15 51.44 3 3 3 3 17.15 17.15 17.15 17.15
Moment Capacity of 1m Wall strip

Given:
Wall Width, B= 1000.0 mm
Wall Thickness,H= 200.0 mm
Number of Tension Reinforcement= 5.0 pcs
or 212.50 mm
Diameter of Tension Reinforcement= 12.0 mm
Number of Compression Reinforcement= 5.0 pcs
Diameter of Compression Reinforcement= 12.0 mm
or 212.50 mm
Concrete Cover= 75.0 mm
fc'= 17.24 MPa
fy= 270.0 MPa

Solution:
Effective Depth, D= 119.0 mm
Steel Area, As= 565.49 sq.mm
Steel Area, As'=As2= 565.49 sq.mm
Concrete Area, Ac= 23,800.0 sq.mm

As1= .0 sq.mm

a= .0 mm

β1= 0.85
c= .0 mm

d'= 81.0
fs'= -108131641329.25 MPa

If fs' > fy, Mu is:

Mu= 5.22 kN-m

If fs'< fy, Mu is:

c= 49.93 mm
a= 42.44 mm

fs'= -373.28 MPa


Mu= 47.51 kN-m

since fs' < fy, Mu = 47.51 kN-m

Use:

200mm THK. WITH


Ø12-200 EACH FACE, EACH WAY
FOR TYPICAL SLAB ON GRADE AND WALLS
Designing Steel Reinforcement for Footing

Given:
P= 83.33 kN
Pu= 125.0 kN
Depth from Top of Soil To Footing Base= 800.0 mm
Soil Bearing Capacity, qa= 100.0 kPa
Assumed Depth of Footing= 400.0 mm
Unit Weigth of Soil, γsoil= 16.0 kN/cu.m
Unit Weigth of Concrete, γconcrete= 23.50 kN/cu.m
Preferred Length of Footing, L= 1.0 m
Diameter of Reinforcement= 12.0 mm
Concrete Cover From the base= 75.0 mm
Wall Width, c= 200.0 mm
fc'= 20.700 MPa
fy= 275.00 MPa
Solution:
Effective Soil Bearing Capacity, qe= qa-sum(γh)
= 84.20 kPa
Area of Footing= P / qe
= .99 sq.m
Computed Footing Dimension, W= .99 m

Ultimate Soil Bearing Capacity, qu= 0.126 MPa

Considering Wide Beam Shear


Vu= qu x (L/2-c/2-d) x W
Vc= 1/6 sqrt(fc') b d
Vu= ф Vc

Along Length, D= 65.54 mm


Along Width, D= 64.70 mm

Considering Wide Two-Way Punching Shear


Vu= qu (L W - (c + d)^2
Vc= 1/3 sqrt(fc') 4(c + d) d

a= 5.28
b= 1,081.79
c= (119,948.00)
depth, D= 80.0 mm

Use the biggest size of computed d.


D= 150.0 mm
Overall Depth, H= 231.0 mm
Design of Reinforcement

Mw= 10.0 kN-m

ML= 9.85 kN-m


Ruw= .498963
RuL= .486206

ρW = .001841
ρL= .001793
ρmin= 1.4/fy
= .005091
β1= 0.85
ρb= .037292
ρmax= .027969

Since ρw<ρmin, use ρmin


Use ρW= .005091
Since ρL<ρmin, use ρmin
Use ρL= .005091
Asw= 755.78 sq.mm
AsL= 763.64 sq.mm

Number of Bars Along Width= 7.0 pcs


Number of Bars Along Length= 7.0 pcs

USE:

300Dx1000W STRIP FOOTING


7-Ø12 ALONG
Ø12-200 ACROSS