Heating, Ventilation, and Air Conditioning System: Service Manual For Recreational Vehicles
Heating, Ventilation, and Air Conditioning System: Service Manual For Recreational Vehicles
This manual was developed to assist certified technicians in servicing the air conditioning system on
class A motorhomes built on Ford, GM, Spartan, or Freightliner chassis, equipped with a DENSO air
conditioning system.
Since the dash A/C system utilizes chassis components (compressor, condenser, receiver/drier and
discharge hose), it is advised that the appropriate chassis repair manual for Ford, GM, or Freightliner be
consulted when required or necessary.
i
ii
TABLE OF CONTENTS
iii
TABLE OF CONTENTS
iv
GENERAL INFORMATION
2) Specific Heat
Specific heat is the quantity of heat
required to CHANGE THE TEMPERA-
TURE of an object by one degree.
The unit of specific heat is Kcal/kg°C
or BTU/lb°F.
2. Technical Terms
A. Heat
1) Heat Quantity
Heat is a form of energy. There are two
units to measure heat quantity, Kcal or Fig. 3: Specific Heat
BTU (British Thermal Unit). 3) Heat Transfer
• One Kcal heat quantity changes As heat travels over a distance, it
the temperature of one Kg of liquid tends to lose energy. Heat can be
water by one degree centigrade. transmitted through CONDUCTION,
• One BTU of heat changes the CONVECTION or RADIATION. It can
temperature of one pound of liquid also be transmitted by a combination
water by one degree Fahrenheit. of any or all of these methods.
1
GENERAL INFORMATION
2
GENERAL INFORMATION
C. Humidity
1) Humidity
When you pour water and ice into a
glass, you notice that drops of water
are generated on the glass. Do you
sometimes wonder where these drops
of water come from?
Drops of water come from the sur-
rounding air, so humidity is water Fig. 8: Relative Humidity
vapor contained in the air. 3) Absolute Humidity
Absolute humidity is the amount of
water the air contains, compared with
the dry air.
D. Pressure
1) What Is Pressure?
Pressure is defined as the vertical
force exerted on a unit area by a solid,
liquid, or gas. The unit generally used
to indicate the pressure is “kg/cm”.
3
GENERAL INFORMATION
4
GENERAL INFORMATION
Sensible Heat can change the temperature When a solid melts into a liquid, heat
of water but cannot change the state of is absorbed from its surroundings.
water. Therefore, the sensible heat raises 2) Solidification
or lowers the temperature of water. In the
case of water, 1 kg of water at 0°C must In the opposite situation, when liquid
absorb 100 Kcal of sensible heat to changes into a solid, heat is released
change to 1 kg of water at 100°C. to its surroundings.
Latent Heat can change the state of water, 3) Evaporation
but cannot change the temperature of
water. Ice melts into water by adding When liquid evaporates into gas, heat
latent heat and water evaporates into is absorbed from its surroundings.
steam by adding latent heat. In the case of
water, 1 kg of ice at 0°C must absorb 80
5
GENERAL INFORMATION
4) Condensation
In the opposite situation, heat is
released to the surrounding matter.
In the case of water, when 1 kg of
water evaporated into 1 kg of steam,
539 Kcal of heat is absorbed from its
surroundings.
In the opposite situation, 539 Kcal of
heat is released to the surrounding
matter.
5) Sublimation
In a rare case such as dry ice (solid
carbon dioxide) and napthaline,
heating causes the solid to directly
turn into gas.
6) Adhesion
The reverse of the sublimation process
is called adhesion.
So far we have been discussing the state of B. If the pressure exerted on water increases
change that occurs in water under atmo- by 0.09 kg/cm2 from atmospheric pres-
spheric pressure. The boiling point of water or sure, the water does not boil until water
any liquid changes depending on the pressure temperature reaches 118°C.
working on the liquid.
C. The water under pressure which is lower
Rule 1. When the pressure is high, the boiling than normal atmosphere by 0.4 kg/cm2
point of liquid also becomes high. begins to boil as soon as the water
temperature passes 84°C.
Rule 2. Conversely, under a low pressure,
liquid begins to boil at a lower temperature. The above rules between pressure and boiling
point can be applied to all liquids. HFC-134a,
The illustration below shows how the boiling the refrigerant used in automobile air condi-
point is influenced by pressure change. tioner is no exception.
6
GENERAL INFORMATION
A. Properties of Refrigerants
Among the refrigerants there are toxic
gases, inflammable gases, those that have
strong properties of oxidizing or corroding
metals, as well as those that are expen-
sive. The important properties demanded
in the refrigerant are as follows:
1) Since refrigeration is attained by
evaporation of liquid, the refrigerant
must evaporate or vaporize easily.
Fig. 15: Evaporating Heat 2) The larger the latent heat at vaporiza-
tion, the smaller the amount of the
Next, we conduct an experiment in latent heat. refrigerant will be required for circula-
As the liquid placed in a heat insulating box tion, and the smaller will be the
begins to evaporate, it takes heat out of the air refrigerator.
from around the receptacle in the box and
becomes gas when the valve is turned. The 3) The equipment must be safe to
temperature of the air goes down before operate so that refrigerant will not be
opening the valve. flammable or explosive.
This is the way we will create coolness. 4) The refrigerant must not be hazardous
However, since we are forced to constantly and preferably a substance in which
add liquid to this receptacle, this is an ineffi- leakage can be detected easily.
cient method. The best way to achieve this
coolness is to change the gas to liquid and 5) The stability must be high to allow
then evaporate it again. repeated use without decomposing or
changing in property.
6) There should be no injurious effect on
parts or packings used in the com-
pressor and other units.
7) The critical temperature should be far
higher than the condensation
temperature.
8) If the evaporation pressure is lower
than atmospheric, there will be a
chance of air entering in the refrigera-
tion cycle so that evaporation pressure
should be higher than atmospheric
Fig. 16: Cooling Experiment
pressure.
7
GENERAL INFORMATION
8
GENERAL INFORMATION
Conversely
Example-3
The liquid refrigerant can be converted
into gas by decreasing the pressure
without changing the temperature . Fig. 18: Heat Precautions
9
GENERAL INFORMATION
10
GENERAL INFORMATION
C. Condensing the Gaseous HFC-134a 5) This cold and foggy refrigerant flows
into the evaporator. Vaporizing the
In the car air conditioning, the high pres- liquid in the evaporator, the heat from
sure, high temperature gaseous refrigerant the warm air stream passing through
is transformed into a liquid by cooling it the evaporator core is transferred to
down at the condenser. the refrigerant.
By flowing through the condenser, the All the liquid will change into the
compressed gaseous refrigerant releases gaseous refrigerant in the evaporator
heat to the surrounding air and is con- and only the heat-laden gaseous
densed back into a liquid. At this time, the refrigerant is in the compressor. Then,
refrigerant temperature becomes lower the cycle begins once again.
than the boiling point (around 57°C). The
liquid refrigerant then returns to the
receiver.
11
GENERAL INFORMATION
Condenser: The condenser mounted at 3) The sight glass is installed on the top
the front of the coach acts as a radiator, of the receiver. The refrigerant charge
drawing off some of the heat of compres- amount is very important for the
sion, and changes the high temperature efficiency of the air conditioner. The
gas into a liquid under high pressure. sight glass is used to check the
When operating normally, the inlet of the amount of refrigerant. Also the sight
condenser is full of hot gas and the outlet glass is installed on the high pressure
is full of hot liquid. There are some models pipe between the receiver and the
which are equipped with a fan exclusively expansion valve.
for the condenser
Expansion Valve: This small valve controls
the flow of refrigerant into the evaporator.
It is controlled by a temperature sensor at
the evaporator outlet. If the outlet tem-
perature is too high, it means not enough
refrigerant is flowing into the evaporator
and the result will be poor cooling.
Fig. 26 Receiver/Drier
12
GENERAL INFORMATION
13
SAFETY PRECAUTIONS
14
SAFETY PRECAUTIONS
b) Splash large quantities of cool water 2) Parts mounted on the engine must be
to the eye or skin to raise the tempera- tightened to specified torque. (See vehicle
ture. service manual).
15
TOOLS AND EQUIPMENT
Service Tool and Testers 1) When low pressure side valve (“LO”) is
opened and high pressure side valve
1. Service Tool Kit (“HI”) is closed.
A. Recovery/Recycling/Recharging Machine
B. Refrigerant Charging Hoses low pressure gauge
1 2
16
TOOLS AND EQUIPMENT
2) How to Remove
a) Turn the hand valve completely
counter- clockwise.
b) Remove the service stop valve
from the discharge service valve.
c) Turn the hand valve clockwise
slightly to remove the residual
pressure in the charging hose.
17
TOOLS AND EQUIPMENT
Figure 35: Gas Leak Detector Figure 36: Charging Station (HFC-134a)
C. Replacement Parts
34430 Quick Change Recycling Filter
34750-50 Pound Refillable Tank
For additional information contact Robinair
at 1-800-368-6787.
18
TORQUE AND BOLT SPECIFICATIONS
M6 X 1.0 ––––––––––––––––
M8 X 1.25 29.4 (300, 21.7)
8T
M10 X 1.25 60.8 (620, 44.9)
M12 X 1.25 107.8 (1100, 79.6)
19
COMPONENT LOCATIONS AND POSITIONS
20
COMPONENT LOCATIONS AND POSITIONS
21
COMPONENT LOCATIONS AND POSITIONS
22
COMPONENT LOCATIONS AND POSITIONS
B. Rear Engine
23
This table shows the
priority in which each
problem should be
inspected. After
indentifying the problem,
use the area of
inspection in number
TROUBLESHOOTING
AREA OF INSPECTION
PROBLEM
Refrigerant volume
manifold gauge set
Inspect refrigeration system with
Inspect drive belt tension
A/C control lever adjustment
Engine coolant volume
A/C fuses
Blower speed control switch
A/C switch
Pressure switch
Blower relay
Blower motor
Blower resistor
A/C thermistor
Compressor
Condenser
Receiver
A/C evaporator
A/C expansion valve
Heater radiator
Wiring or wiring connection
Blocked air inlet
hose kinked
Air leak from heater unit or air duct
No blower operation 1 3 2 5 4 6
No blower control 2 1 3 4
24
No air flow mode control 1
First, have the manifold gauge high and low The gauge indications shown in the following
pressure side valves tightly closed, and connect diagrams are taken under the same conditions
the charging hoses (red and blue) to the respective (ambient air 86° - 95°F, engine speed 1500 rpm,
compressor service valves. strongest cooling setting, maximum blower speed),
so it should be noted that the gauge readings will
In this case, if the service valves are the valve differ somewhat with the ambient conditions.
plunger type, always make sure to set the plungers
to the intermediate seat position (slightly toward NOTE: Gauge should indicate static pressures
back seat if the pointer vibrates) so as to enable before A/C operation both high and low pressure
taking measurements with the gauges. sides between 71~114 psi.
NOTE: Be sure to purge the air in the charging
hoses at the manifold gauge connection end by
utilizing the refrigerant pressure in the refrigerating
cycle.
If the refrigeration cycle is operating normally, the
reading at the low pressure side should generally
be around 21 ˜ 35 psi and at the high pressure side
around 199 ˜ 227 psi when ambient air temperature
is about 86° - 95°F, engine speed 1500 rpm,
strongest cooling setting, and blower operating at
top speed.
25
TROUBLESHOOTING
Condition Diagnosis
1. Periodic cooling and no cooling at the evaporator. 1. Receiver/drier in oversaturated condition.
Symptoms seen in refrigeration cycle 2. Moisture in refrigeration cycle freezes expan-
sion valve orifice and obstructs refrigerant
1. During operation, low side pressure alternately circulation.
becomes vacuum and normal.
When Abnormal: Remedy
Low Pressure Side: Vacuum
High Pressure Side: 99 ~ 142 psi 1. Replace receiver/drier.
When Normal: 2. Remove moisture in cycle by means of re-
Low Pressure Side: 21 ~ 35 psi peated evacuation.
High Pressure Side: 199 ~ 227 psi
3. Check expansion valve.
Cause
4. Recharge new refrigerant to the proper quantity.
1. The moisture in the refrigeration cycle freezes
in the expansion valve orifice and causes
temporary blocking.
After a time, the ice melts and condition
returns to normal.
26
TROUBLESHOOTING
Condition Diagnosis
1. Would desire more cooling. 1. Refrigerant in cycle insufficient.
Symptoms seen in refrigeration cycle 2. Refrigerant leaking.
1. High and low side pressures both low. Remedy
Low Pressure Side: 7 ~14 psi
High Pressure Side: 99 ~ 142 psi 1. Check for leakage with leak detector and
correct.
2. Bubbles seen in sight glass.
2. Evacuate and recharge refrigerant to proper
3. Air discharged from air conditioner slightly amount.
cold.
Cause
1. Gas leaking someplace in refrigeration cycle.
27
TROUBLESHOOTING
1. High and low side pressures both high. 3. Condenser fins clogged or fan belt loose.
Low Pressure Side: 35 ~ 50 psi 4. Radiator fan fluid coupling slipping or electric
High Pressure Side: 284 ~ 355 psi fan inoperative.
2. Bubbles cannot be seen in the sight glass. Remedy
Cause 1. Clean condenser.
1. Due to overcharging refrigerant into cycle, 2. Adjust fan belt to proper tension.
proper performance cannot be shown. 3. If 1 and 2 are in normal condition, check
2. Condenser cooling faulty. refrigerant quantity.
NOTE: If excessive refrigerant is to be discharged,
You must use a refrigerant recovery station.
28
TROUBLESHOOTING
Condition Remedy
1. Air conditioner fails to cool sufficiently. 1. Replace receiver.
Symptoms seen in refrigeration cycles 2. Check compressor oil contamination and
quantity.
1. High and low side pressures high.
Low Pressure Side: 35 ~ 43 psi 3. Recover refrigerant, evacuate and recharge
High Pressure Side: 284 ~ 355 psi. new refrigerant.
2. Low pressure side piping not cold when NOTE: The above cycle can be seen when after the
touched. cycle is opened, the refrigerant is charged without
evacuation.
Cause
1. Air entered in refrigeration cycle.
Diagnosis
1. Air in refrigeration cycle.
2. Evacuating insufficient.
29
TROUBLESHOOTING
Figure 49: Expansion Valve Trouble or Improper Installation of Heat Sensitizing Tube
30
TROUBLESHOOTING
Condition Remedy
1. Intermittent cooling 1. Allow to stand for some time and then resume
Symptoms seen in refrigeration cycle operation to decide whether the plugging is
due to moisture or dirt.
1. Vacuum shown at low side and very low
pressure shown at high side. a. If caused by moisture – Correct by refer-
Low Pressure Side: 27 in. Hg ring to instructions in condition B.
High Pressure Side: 71 ~ 85 psi b. If caused by dirt – Remove the expansion
2. Frost or dew formed on piping at inlet and valve and blow out the dirt with com-
outlet of expansion valve or receiver. pressed air. If unable to remove the dirt,
replace the expansion valve. Replace the
Cause receiver. Evacuate and recharge proper
1. Refrigerant flow obstructed by moisture or dirt amount of new refrigerant.
in the refrigerating cycle freezing or sticking on c. If caused by gas leakage in heat sensitiz-
the expansion valve orifice. ing tube Replace the expansion valve.
Diagnosis
1. Expansion valve orifice plugged.
2. Refrigerant does not circulate.
31
TROUBLESHOOTING
32
TROUBLESHOOTING
33
TROUBLESHOOTING
4. Troubleshooting Chart
CAUTION: When repairs are required on the compressor, condenser, discharge hose, receiver/
drier, or the condenser fan motor, please refer to the appropriate chassis manufacturer repair
manual.
Blower and motor Blower motor related parts Blower mounting loose
defective Blower relations Blower hitting heater case
Blower deformed
34
TROUBLESHOOTING
5. Insufficient Cooling
A. Compressor
Disc harg e pre ssu re Low-pre ssu re sid e Heat se nsitiz in g tu be Re pla ce
abnorma lly lo w. pre ssu re to o lo w. gas le aka ge.
Low-pre ssu re pip in g Exp ansio n va lve fro zen
not cold . or defe ctive
Larg e passa ge of Not enough re frig era nt Charg e to pro per
bubble s th ro ugh sig ht amo unt
gla ss.
If comp re sso r is Comp re sso r disc harg e Re pair or re pla ce
sto pped, hig h- and of su ctio n va lve bro ke n.
lo w-pre ssu re sid e Fore ig n obje ct stu ck in Disa sse mb le and
pre ssu re s imme dia te ly comp re sso r disc harg e re mo ve
equaliz e. va lve
35
TROUBLESHOOTING
Compressor (cont’d)
Discharge and suction Heavy covering of dirt Condenser cooling Wash off dirt and dust to
pressure both high. and dust on condenser insufficient improve air passage.
fins.
Gas leakage. Shaft seal becomes Gas leaking from shaft Replace shaft seal.
noticeably dirty and seal.
gaskets leaking.
Bolts get stained with Gas leaking from bolted Retighten bolts.
oil. parts.
Gasket joints get stained Gas leaking from joints. Replace gasket.
with oil.
Leakage from cracked Gas leaking from part. Replace cracked part.
part.
36
TROUBLESHOOTING
B. Magnetic Clutch
C. Expansion Valve
Valve outlet not cold. Temperature difference Heat sensitizing tube Replace expansion
at outlet and inlet cannot gas leakage. valve.
be sensed.
Amount of refrigerant in Repair gas leakage point
cycle very small. and charge refrigerant.
37
TROUBLESHOOTING
6. Abnormal Noise
Bearing worn or damaged
Compressor
Defective cylinder and/or shaft
Bearing worn or damaged
Magnetic clutch Stator and rotor contacting
Stator mounting bolts loose
Blower assembled upside down
Blower motor
Blower improperly tightened
Noise from
Crank Pulley Improperly tightened
Improperly installed
Idler pulley
Bearing worn or damaged
Bracket, clamp, etc., improperly tightened or installed
Piping parts
Safety gap not suitable
Magnetic clutch noisy. Rattling noise when Bearing w orn or Replace bearing.
magnetic clutch is not damaged
engaged.
Noise from piping. Piping not secured. Piping vibrating. Secure piping.
Pulsating noise
resonates into body.
38
COMPONENT TESTING
1. Blower/Cooling Unit
A. On Vehicle Inspection of Expan-
Figure 53: HVAC Cover
sion Valve
Inspect A/C system visually and audibly .
Next, inspect the system with a ROBINAIR
(manifold gauge) or equivalent equipment.
1) While tur ning A/C switch “ON” and
BLOWER switch “HI”, run engine at
1,500 RPM for at least five (5) minutes
and check A/C performance in
RECIRC mode.
2) If expansion valve is clogged, the low
pressur e reading will dr op. If nor mal,
the pr essur e will r emain the same. Figure 54: Fresh/Recirc Air Box
3) If the low pr essur e reading is nor mal 4) Remove fresh/recirculate air box. (Fig. 54)
and A/C is not cooling, check for
malfunction of expansion valve. 5) Disconnect wir e har ness at: (Fig. 55)
• Three (3) r elays
B. Blower/Cooling Unit Removal
• Blower
1) Disconnect negative cable fr om • Servo motor
batter y.
• Two (2) connectors from thermostat
• Blower r esistor
• Fresh/r ecir culate connector
• Pressur e switch
• Main har ness connector
39
COMPONENT TESTING
6) Remove suction and liquid lines fr om 12) Carefully slide blower/cooling unit
cooling unit. (Fig. 56) assembly r ear war d.
NOTE: Seal lines to pr event moistur e C. Blower/Cooling Unit Disassembly
from entering into the A/C system. (Fig. 58)
9) Remove passenger far -right air vent 7) Remove upper and lower case halves
grille assembly . from evaporator cor e.
10) Remove scr ew securing the heater 8) Remove packing fr om expansion valve
unit by r eaching thr ough the vent hole sensing tube located on the evapora-
in the upper right cor ner of the dash. tor suction tube.
11) Loosen the two (2) scr ews securing 9) Remove “C” clip fr om sensing tube.
the heater unit to the engine compart- 10) Disconnect liquid tube fr om the inlet
ment cover (or wood support - diesel fitting of the expansion valve.
models).
11) Remove expansion valve.
NOTE: These two screws may be removed
by lifting the instrument panel and reach-
ing under the dashboard (or HVAC cover
on diesel models).
40
COMPONENT TESTING
1) Inspect evaporator cor e fins for 9) Install blower motor and vent tube.
blockage. 10) Reconnect wir e har ness. (Fig. 60)
• If fins ar e clogged, clean with
compr essed air .
• Do not use water to clean evapo-
rator cor e.
2) Inspect fittings for cracks or
scratches. Repair or r eplace as
requir ed.
Figure 59: Blower/Cooling Unit (disassembled) 9) Evacuate and char ge using ROBINAIR
or equivalent equipment.
2) Install expansion valve sensing bulb to
evaporator suction tube with “C” clip
and insulate with packing.
3) Connect the liquid tube to the evapo-
rator cor e and tor que to 13 N•m (135
kgf•cm, 10 lbf•ft).
4) Install lower case.
5) Install thermostat.
6) Install upper case.
7) Install nine (9) scr ews.
41
COMPONENT TESTING
B. Replacement
1) Recover r efrigerant fr om system.
2) Replace failed par t and tor que to 32
N•m (325 kgf•cm, 24 lbf•ft).
SUCTION HOSE
3. Refrigerant Hoses/Tubes Figure 63: GM Chassis (L29) Hose Routing (from mid-1996)
B. Replacement
1) Recover r efrigerant fr om system.
LIQUID HOSE #1
2) Replace failed par t and tor que to (CONNECTION TO
CONDENSER)
proper spec.
SUCTION HOSE LIQUID HOSE #1 RECEIVER/DRIER
• Suction Hose 32 N•m (325 Figure 64: GM Chassis (P12) Hose Routing (from mid-1998)
kgf•cm, 24 lbf•ft)
• Liquid Hose 13 N•m (135 kgf•cm,
10 lbf•ft)
3) Evacuate and char ge using Robinair
char ging station or equivalent.
42
COMPONENT TESTING
HEATER
HOSES
5. Heater
A. On Vehicle Inspection and Ad-
justment
1) Inspect HV AC contr ol panel. Move the
temperatur e contr ol lever to see if
cable moves fr eely without binding
and has full range of travel.
Figure 69: Cable Adjustment at Control Panel
43
COMPONENT TESTING
2) On the bottom of the HV AC unit, 5) While holding the cam lever in the
locate the spring clip and car efully proper position, r echeck that the
remove the contr ol cable insulation. temperatur e contr ol lever on the
(Fig. 70) contr ol panel is in the maximum cool
position. (Fig. 71)
6) While holding the cam lever in the
maximum cool position, snap the
contr ol cable insulation into the spring
clip by pushing upwar d. (Fig. 73)
44
COMPONENT TESTING
6. Thermostat
A. Thermostat Operation
The ther mostat is wir ed in series with the
high-low side of the pr essur e switch and
prevents the evaporator fr om fr eezing over
by contr olling the gr ound to the coil of the
magnetic clutch r elay.
Figure 75: Heater Hose Location
When the thermostat is set to the max cold
4) Remove temperatur e contr ol damper position (full clockwise), the thermostat
door cam which is secur ed by one (1) contacts will be closed at evaporator
screw with a plastic washer . temperatures above 4.5°C (40.1°F) and open
between 1°C and 25°C (32.9°F and 36.5°F).
CAUTION: Do not attempt to remove heater
core without removing damper door cam. When the thermostat is set to the max
war m position (full counter clockwise), the
5) Remove plastic lever which is
contacts will be closed at evaporator
mounted over heater cor e.
temperatur es above 7.5 °C (45.5°F).
If the thermostat does not perform as
specified, r eplace the ther mostat.
NOTE: The ther mostat is pr eset at the
factory and should not be adjusted. This
information is supplied for diagnostic
purposes only .
B. Thermostat Removal
1) Remove and disassemble blower/
cooling unit.
2) Remove ther mostat fr om unit.
Figure 76: Bottom View of Heater Core
45
COMPONENT TESTING
7. A/C Control System: On Vehicle B. Open instr ument contr ol panel (if equipped).
Inspection
A. Inspect A/C Switch for continuity.
B. Inspect A/C Blower Speed Contr ol Switch
for continuity .
C. A/C Contr ol Levers Inspection
1) Inspect the contr ol lever at contr ol
panel for smooth operation.
2) Inspect the contr ol lever at HV AC for
smooth operation.
Figure 79: Control Panel Location
Blower speed control switch
C. Remove four (4) scr ews on contr ol panel
Terminal
bezel plate (if equipped). (Fig. 80)
No.
1 2 3 4 5
Switch
Position
Low
Medium
Low
Medium
Hi
Hi
Indicates there is continuity between these terminals Figure 80: Removal of Control Panel Bezel
Blower speed control switch connector D. Remove contr ol panel fr om r ear of dash
panel.
E. Remove contr ol cable fr om contr ol panel.
5 6 3 (Fig. 81)
1 2 7 8 4
Figure 78: Blower Speed Control Switch
46
COMPONENT TESTING
9. Pressure Switch
A. Pressure Switch Operation
The pressure switch is a triple pressure
switch with a high and low pressure set of
contacts and a medium pressure set of
contacts. The high-low side is wired in series
with the thermostat and controls the ground
Figure 82: Removal of Subwire Harness
to the coil of the magnetic clutch relay. On
vehicles equipped with a condenser fan, the
medium side is wired in parallel with the
G. Remove and save metal support bracket water temperature switch and controls the
from contr ol panel (if equipped). ground to the coil of the condenser fan relay.
B. On Vehicle Inspection
1) Disconnect negative cable fr om
batter y.
2) Remove HV AC cover on passenger
side.
3) Confir m refrigerant char ge status with
ROBINAIR or equivalent equipment.
4) Disconnect the pr essur e switch
har ness connector fr om the cooling
Figure 83: Metal Support Bracket unit har ness.
High & Low Pressure
ON
A. Inspection
OFF OFF
Inspect contr ol panel for continuity .
29 34 298 384
Terminal
Medium Pressure
ON
No. 1 2 3 4 6 7 8 9 10 11
(-)
Mode Ground
OFF
A/C
(on) 177 220
Vent
(face) Units: PSI
B/L
Floor Switch
Off On On Off
DEF kg/cm2 (psi) kg/cm2 (psi)
Item
Recirc
(Button Depressed)
Fresh
Low Pressure
2.4 (34.1) 2.1 (29.9)
(Recirc Button Out)
Side
Indicates there is continuity between these terminals
1 2 3 4 5 6 Medium Pressure
15.5 (220.4) 12.5 (177.8)
Side
Figure 84: Control Panel Circuit Figure 85: Pressure Switch Operation
47
COMPONENT TESTING
D. Installation
Follow r eversal of steps for r emoval.
2
3 4
1 2 3 4
1
10. Blower
41A 42A 43A 44A
A. On Vehicle Inspection
0.5GR
0.5WR
0.5Br
0.5Y
42A
44A 43A
41A
41A 42A 43A 44A 43A 41A Connect positive (+) lead fr om batter y
13A 14A 15A 16A
to terminal #2 and negative (-) lead to
0.5WR
0.5GL
0.5Br
0.5GR
1
Figure 86: Pressure Switch Connector 18A
2
6) With the A/C system at normal operat- 4B
ing pr essur es, check for continuity
between terminals 41A and 42A for
the high-low side and terminals 43A
and 44A for the medium side. M 1 4B 3LW
3L
7) If ther e is no continuity , replace the 2 18A
switch.
Figure 88: Blower and Fan Circuit
C. Pressure Switch Removal 2) Blower Resistor Inspection.
1) Remove and disassemble blower/ Inspect the r esistor for specification.
cooling unit. (Fig. 87)
Checking for proper resistance of the blower motor resistor
Pins 1 2 4 5
Resistance
Value
.5Ω
.8Ω
1.68Ω
5 2
48
COMPONENT TESTING
B. Blower HI Relay
Inspect 4-pin Blower HI Relay for continu-
ity and r eplace the r elay as r equir ed.
Terminal
No. 21A 2B 50 18B
Battery
Voltage
Not
Supplied
Supplied +
Figure 90: HVAC Component Location
2) Remove HVAC cover on passenger side. Indicates there is continuity between these
terminals
Indicates terminals to which battery voltage
is supplied
3) Disconnect 4-pin connector fr om
Blower High Relay connector
blower r esistor .
3L
4 18B
0.5YG
4) Remove two (2) scr ews fr om blower 2 2B
1 21A 0.5Br
resistor . 3 5O 3WB
D. Installation 1 3
2B 18B
2 4
Follow r eversal of steps for r emoval. 21A 5O
49
COMPONENT TESTING
3 12A 0.5BW
Fresh
(recirc out)
Indicates terminals to which battery voltage is supplied
1 3
4I 4E
Air Intake Servo connector
2 4
13A 12A
M
Fig. 93: Magnetic Clutch Relay 4 3 2 1
0.5YW
0.5YG
50
COMPONENT TESTING
Figure 95: HVAC Wire Harness Connectors Figure 96: Vent Servo Positions
51
REFRIGERANT LINE REPLACEMENT
52
REFRIGERANT LINE REPLACEMENT
4. CHASSIS
A. GM Chassis: Liquid, Suction, and Heater Hoses (thru mid-1996)
Fig. 97: GM Chassis: Liquid, Suction, and Heater Hoses (thru mid-1996)
SUCTION HOSE
Fig. 98: GM Chassis (L29): Liquid, Suction, and Heater Hoses (from mid-1998)
53
REFRIGERANT LINE REPLACEMENT
C. GM P12 Chassis
Liquid, Suction, and Heater Hoses
LIQUID HOSE #1
(CONNECTION TO
CONDENSER)
Fig. 100 : Ford Chassis (thru mid-1998) Liquid, Suction, and Heater Hoses
54
REFRIGERANT LINE REPLACEMENT
HEATER
HOSES
LIQUID HOSE
LIQUID HOSE
SUCTION HOSE
Fig. 101: Ford Chassis (from mid-1998) Liquid, Suction, and Heater Hoses
LIQUID HOSE
RECEIVER DRIER
55
REFRIGERANT LINE REPLACEMENT
2) Suction Tube
SUCTION TUBE
INSULATION
CHASSIS RAIL
CHASSIS CROSS
MEMBER
56
REFRIGERANT LINE REPLACEMENT
57
REFRIGERANT LINE REPLACEMENT
58
REFRIGERANT LINE REPLACEMENT
59
REFRIGERANT LINE REPLACEMENT
Fan Bracket
Washer (4) Washer
Bolt (M6 x 25) (2)
Condenser Fan
60
REFRIGERANT LINE REPLACEMENT
(11)Condenser Removal
(a) Recover refrigerant from air
conditioning system.
(b) Disconnect hoses from condenser.
CAUTION: Cap ends of hoses IMMEDIATELY
after disconnecting from condenser to prevent
moisture or other contaminants from entering
the system.
(c) Disconnect 2-Pin connector from
condenser fan.
(d) Remove fan and fan bracket
together by removing two (2) nuts
and two (2) bolts securing fan
bracket to condenser bracket.
61
REFRIGERANT LINE REPLACEMENT
(14)Receiver/Drier Removal
(a) Recover refrigerant from A/C
system.
(b) Disconnect hoses from receiver/ Bolt (M6 x l 25)
drier.
CAUTION: Cap ends of hoses IMMEDIATELY
after disconnecting from condenser to prevent
moisture or other contaminants from entering
the system. Receiver Drier
Liquid Hose #2
62
REFRIGERANT CHARGING
63
REFRIGERANT CHARGING
Certification
(1) . . . each person performing service on
motor vehicle air conditioners for consid-
eration shall certify to the Administrator–
that such person has acquired, and is
properly using, approved refrigerant
recycling equipment in service on motor
vehicle air conditioners involving refriger-
ant and that each individual authorized by
Fig. 117: Automotive Service Excellence Certificate
such person to perform such service is
properly trained and certified;
(2) Effective January 1, 1993 each person . . .
Shall submit a certification under para-
graph (1) (A).
(3) Each certification under this subsection
shall contain the name and address of the
person certifying under this subsection
and the serial number of each unit of
approved recycling equipment acquired by
such person and shall be signed and
attested by the owner or another respon-
sible officer. Certifications under para-
graph (1)(A) may be made by submitting
the required information to the Administra-
tor on a standard form provided by the
manufacturer or certified refrigerant
recycling equipment. Fig. 118: California Air Quality Management Certificate
64
REFRIGERANT CHARGING
65
REFRIGERANT CHARGING
66
REFRIGERANT CHARGING
67
REFRIGERANT CHARGING
Remedy = Recover excess refrig- 5. Insert a dry bulb thermometer in the cool
erant to proper volume. Refer to air outlet, and place the psychrometer (dry
step (f). and wet bulb thermometer) close to the
inlet of cooling unit.
f. Sight Glass Foams and Becomes
Clear When A/C Is Turned Off
Refrigerant = Normal
B. Refrigerant Volume
1) Gas Front Engine Models:
Ford = 2.8 lbs.
GM = 2.0 lbs.
2) Diesel Models:
Freightliner = 3.8 lbs.
Spartan (thru mid-1998) = 4.2 lbs.
Spartan (from mid-1998) using com-
plete DENSO system= 3.0 lbs.
Fig. 127:Performance Testing
5. Performance Test
6. The high pressure gauge reading should
After completing repairs, make sure to carry
be within the specified pressure range,
out the performance test of the air condition-
14.0 - 16.0 kg/cm2 (199-227 psi)..
ing system as follows:
NOTE: If the gauge indicates too high, pour water
A. Procedure on the condenser, or if it is too low, cover the front
1. Connect the high and low side charging surface of condenser.
hose of manifold gauge set to the hose 7. The dry bulb thermometer at the air inlet
fittings of compressor. should be within 25-35°C (77-95°F).
2. Run the engine, and keep the compressor With the above conditions, operate air
speed at 1,500 RPM. conditioning system until a stabilized
3. Operate the air conditioner, and set the condition on high and low pressure
blower switch at “HI,” the temperature gauges and the thermometers have been
lever at “COOL” and in “recirc” mode. established.
4. Keep all windows and doors open.
68
REFRIGERANT CHARGING
8. Calculate the relative humidity from the psychrometric graph by comparing the wet and dry bulb
readings of the psychrometer at the air inlet. (Fig 128)
30
HOW TO READ THIS GRAPH: (86)
)
(%
Y
After measuring the temperatures of the wet- and
IT
ID
dry-bulb thermometers at the evaporator air inlet,
M
HU
relative humidity can be obtained.
VE
25
TI
Example: Supposing dry- and wet-bulb tempera-
LA
tures at the evaporator air inlet are 25˚C (77˚F) and (77)
RE
90
19.5 ˚C (67˚F) respectively. The point of intersection
)
80
of the dotted lines in the graph is 60%. (˚F
C 70
e˚ 20
60
ur
rat (68)
pe 50
m
Te 15
ulb (59) 40
etB
W 10 0
10 0 30
9
(50) 80
5 70
60
20
0 (41) 50
40
(32) 10
30
20
10
-5 0 5 10 15 20 25 30 35 40
(23) (32) (41) (50) (59) (68) (77) (86) (95) (104)
9. Measure the dry-bulb temperature at the cool air outlet, and calculate the difference between the
inlet dry bulb and outlet dry bulb temperatures (Fig. 129).
10. Check that the intersection of the relative humidity and temperature difference is above the line. If
the intersection is within the two lines, cooling performance is satisfactory.
˚C ˚F
between inlet and outlet
22 39.6
Temperature difference
20 36
18 32.4
16 28.8
14 25.2
12 21.6
10 18
50 60 70
Relative Humidity (%)
69
WIRING DIAGRAMS
Terminal Terminal
30 85 86 87 87A No. 21A 2B 50 18B
No.
Battery Battery
Voltage Voltage
Not Not
Supplied Supplied
Supplied Supplied +
Indicates there is continuity between these terminals Indicates there is continuity between these
terminals
Indicates terminals to which battery voltage is supplied
Indicates terminals to which battery voltage
is supplied
Main Relay connector
Blower High Relay connector
85
3L
4 18B
87 87 30 0.5YG
2 2B
86
NO NC 1 21A 0.5Br
3 5O 3WB
2A
87 86 85 87A 30
1A 5B 4A 1A 2A 3A 5B 4A
1 3
2B 18B
3LR
0.5YG
0.5RB
0.5WB
3LW
3A
2 4
21A 5O
L = BLUE
G = GREEN
R = RED
Y = YELLOW
W = WHITE
B = BLACK
Br = BROWN
70
WIRING DIAGRAMS
Terminal
No. 13A 4I 12A 4E
Battery A
Voltage M M
Not
Supplied 7 6 5 4 3 2 1
FOOT
FACE
DEF
B/L
(+)
(-)
2 3 4 5 6 7 1
9A 8A 7A / 6A 5 A 2O
0.5RW
0.5YB
0.5GW
0.5YR
0.5WB
0.5YG
5A 6A / 7 A 8A 9A 2O
Supplied +
1 4I 0.5LW
3 12A 0.5BW
1 3
4I 4E
2 4
13A 12A
L = BLUE
G = GREEN
R = RED
Y = YELLOW
W = WHITE
B = BLACK
Br = BROWN
71
WIRING DIAGRAMS
To check for voltage at the Air Intake Servo Sub Harness female
connector, use chart below
Main
Harness
1 2 4
Pin
Switch .5YG .5YG .5YL
Position
2
Recirc 3 4
(in) 1 2 3 4
1
(recirc out)
0.5GR
0.5WR
0.5Br
0.5Y
42A
44A 43A
Indicates terminals to which battery voltage is supplied 41A
44A 42A
M
41A 42A 43A 44A 43A 41A
4 3 2 1
13A 14A 15A 16A
0.5WR
0.5GL
0.5Br
0.5GR
4 3 2 1
47B 46B 45B 47B 46B 45B
15A 13A
0.5YL
0.5YW
0.5YG
16A 14A
L = BLUE
G = GREEN
R = RED
Y = YELLOW
W = WHITE
B = BLACK
Br = BROWN
72
DENSO SALES CALIFORNIA, INC.
TECHNICAL SERVICE DEPARTMENT
First Issue: January 1999
DSCA P/N: LA990009-0427
Printed in USAv