MV Cable Termination

This document provides information on high voltage cable accessories from 72 kV up to 170 kV made by NKT Cables GmbH. It discusses silicone rubber terminations for indoor and outdoor use, as well as switchgear and transformer terminations. Straight joints and other accessories for different applications are also mentioned. Technical specifications and diagrams are provided for various termination types. The document aims to inform potential customers about NKT Cables GmbH's product range of high voltage cable accessories.

Uploaded by

sulemankhalid
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views16 pages

MV Cable Termination

This document provides information on high voltage cable accessories from 72 kV up to 170 kV made by NKT Cables GmbH. It discusses silicone rubber terminations for indoor and outdoor use, as well as switchgear and transformer terminations. Straight joints and other accessories for different applications are also mentioned. Technical specifications and diagrams are provided for various termination types. The document aims to inform potential customers about NKT Cables GmbH's product range of high voltage cable accessories.

Uploaded by

sulemankhalid
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

H I G H V o lta G e cable accessorIes

for 72 kV up to 170 kV

Completing the picture


based on experience is the future

nkt cables GmbH


nKt was established in 1891 as cable manufacturer. in 1999 as the first company introducing silicone rubber termina-
nKt a/s denmark merged with felten & Guilleaume Kabel- tions already in the sixties, nkt cables GmbH, nordenham
werke Gmbh in Germany to form nkt cables group GmbH is specialized in production of silicone rubber power cable
with headquarters in cologne. nkt cables group GmbH is accessories.
owned by nKt holding a/s, an industrial group of compa-
the product range covers cable joints, cable connectors for
nies employing 9.110 people.
sf6-switchgears and transformers as well as indoor- and
nkt cables group GmbH bundles the expertise of around outdoor terminations. these types of cable accessories
2.500 employees in 10 production and development facili- are used for single- and 3-core cables as well as for paper
ties spread over five european countries and p.r. china. insulated cables.

Manufacturing and developing power cable accessories up


to 400 kV is one of the core businesses of nkt cables group
GmbH. since more than 50 years nkt cables group GmbH
nordenham, Germany (formerly f&G Kabelgarnituren Gmbh)
is one of the world market leaders in power cable accessories.
content

General
silicone rubber 5

stress control 5

Indoor and outdoor termInatIons


6
thV 72 dry type push-on technique without supporting function
7
KfeV-V dry type composite insulator without insulating liquid
8
feV-V composite insulator oil filled
feV-p porcelain insulator oil filled 9

swItcHGear and transformer termInatIons


KseV/KteV dry type plug-in termination 10-11

seV/teV epoxy insulator termination 12

straIGHt joInts
sM 72-170 premoulded straight joint 13

more accessorIes for dIfferent applIcatIons


screen separation 14

Link box 14

tools 14

requested cable InformatIon


cable data 15

certificates 16

contact 16

3
General

stress control
the specific electrical problems of the cable termination are figure 2 shows the field of the cable termination controlled
found at the point between the high-grade solid electrical capacitively by a funnel shaped electrode. it is dimensioned
insulation of the cable and the gaseous insulation air which in such a way that field intensities do not exceed at any
has a significantly lower dielectric strength. point. this prevents harmful corona or partial discharge.

in order to achieve sufficient insulating clearance, the outer


conductive layer of the cable must be stripped to below the
end of the core. this causes unacceptably high field intensi-
ties at the end of the outer conductive layer (figure 1) which
must be eliminated by means of special measures.

conductor conductor

core isulation core isulation

equipotential lines

equipotential lines

field lines field lines

stress cone

outer
outer conductive layer
conductive layer

screening wires screening wires

outer sheath outer sheath

electrical field without stress control (figure 1) electrical field with capacitive stress control (figure 2)

silicone rubber
silicone rubber is a preferred material for cable accessories outstanding features of the silicone rubber insulation
due to its excellent mechanical and electrical properties. material are:

for more than 40 years silicone has been used successfully ✓ uV and ozone resistance
as high-quality electrical insulation for voltages up to 400 ✓ durable water rejection
kV. silicone rubber features high quality electrical insulation, ✓ weather and aging resistance
superior corona and tracking resistance, combined with high ✓ non-flammable, self-extinguishing, heat resistant
elasticity. ✓ applicable for use at temperatures between -50° c
and +180° c
it facilitates multi range application, where one silicone rubber ✓ high elasticity
body can be used for various conductor cross sections. opti- ✓ high tracking resistance
mal flexibility ensures easy assembly of the accessories. ✓ unlimited storage life
✓ friendly to the enviroment

5
Indoor and outdoor termination
tHV 72 kV dry type without
supporting function
this two versions of silicone rubber terminations are designed Øa Øa
for indoor and outdoor conditions. Main components of the
termination are the pretested push-on silicone components with
integrated stress cone for electrical field control.
100 100
✓ integrated capacitive stress control system
✓ piece tested silicone components
✓ screw type top bolt, no special tools are required
✓ top bolt covered by top part of silicone rubber
✓ Quick and easy assembly
✓ Long creepage distance due to optimised shed design
✓ type test certificate in accordance with iec 60840 available
L

operation
voltage 72 L
um (kV)
thV thV 72 thV 72 thV 72 thV thV 72
typ 72 ii iV ii size iV size 72 ii iV
size 36 size 36 46 46 size 56 size 56
conductor
cu/al max. ...800 ... 800 ... 1200 ... 1200 ... 1600 ... 1600
(mm²)
diameter
over dielectric 40.0 - 40.0 - 51.5 - 51.5 - 63.0- 63.0-
min. - max. 54.0 54.0 65.0 65.0 78.0 78.0
(mm)
diameter approx. approx. approx. approx. approx. approx.
over sheath
80-190 80-190 100-200 100-200 110-210 110-210
max. (mm)
screw / press
connection s s s s s s
s/p

Length 1100 - 1450 - 1000 - 1250 - 1250 - 1250 -


L (mm) 1160 1540 1040 1280 1280 1280
pollution
ii iV ii iV ii iV
level
creepage
distance > 1450 > 2248 > 1450 > 2248 > 1450 > 2248
min. (mm)
diameter
30 30 30/50 30/50 50 50
a (mm)

no. of sheds 8 11 8 11 8 11
indoor and outdoor terminations

dry type outdoor termination


KfeV 145-V dry type outdoor
termination
this new generation of dry type termination is free of any liquid
Øa
and gaseous insulation medium. Main components of the ter-
mination are the push-on silicone components with integrated
stress cone for electrical field control and the liquid free epoxy 100
resin insulator with silicone sheds.

✓ free of insulation liquid, no filling procedure


✓ Less parts to be assembled therefore faster installation
✓ prefabricated capacitive silicone stress control system
✓ plug-in part comprising four components (stress cone made
of silicone rubber, cable gland, connection bolt, spring
loaded compression device)
✓ easy to fit screw type conductor connector
✓ all metal work made of corrosion resistant aluminium alloy
✓ type test certificate in accordance with iec 60840 available
L ±50

operation voltage 145


um (kV)

typ KfeV 145-V

conductor cu/al
... 1200
max. (mm²)

diameter
over dielectric 42.0 - 74.0
min. - max. (mm)

diameter
over sheath ... 99
max. (mm)

screw / press
connection s
s/p 450 345

Length
1750
L (mm)

pollution level iV
creepage
distance > 4495
min. (mm)

diameter
50
a (mm)

7
outdoor termination
feV-V with composite
insulator
the different versions of this outdoor termination type feV-V are Øa
designed for operation under severe outdoor conditions. Main
components of the termination are the composite insulator with
upper metal work, metal base plate with supporting insulators 100
and premoulded stress cone for electrical field control.

✓ integrated premoulded stress control system made of silicone


rubber
✓ all metal work made of corrosion resistant aluminum alloy
✓ termination is standing on supporting pedestal insulators, so
that the cable screen can be isolated from earth
✓ top bolt available in two versions, screw type or press type
✓ different top bolt diameter available suiting to the cable
dimensions
✓ type test certificate in accordance with iec 60840 available
L ±50

operation voltage 72 145 170


um (kV)
typ feV 72-V feV 145-V feV 170-V
conductor cu/al
... 1200 1* ... 1200 1* ... 1200 1*
max. (mm²)
diameter
over dielectric 34.5 - 97.0 34.5 - 84.0 34.5 - 108.0
min. - max. (mm)

diameter ~100
over sheath ... 105 ... 105 ... 105
max. (mm)

screw / press
connection s/p s/p s/p
s/p

Length
1400 1900 / 2100 2100 450 305 345 381
L (mm)
pollution level iii ii / iV iV
creepage di-
> 3075
stance > 1813 > 5270
> 5270
min. (mm)
diameter
30 / 50 30 / 50 30 / 50
a (mm)
*1
>1200 up to 2500 mm² special crimping tool is required
indoor and outdoor terminations

outdoor termination
feV-p with porcelain
insulator
the different versions of outdoor termination type feV-p are Øa
designed for operation under severe outdoor conditions. Main
components of the termination are the porcelain insulator with
upper metal work, metal base plate with supporting insulators 100
and premoulded stress cone for electrical field control.

✓ integrated premoulded stress control system made of silicone


rubber
✓ all metal work made of corrosion resistant aluminum alloy
✓ termination is standing on supporting pedestal insulators, so
that the cable screen can be isolated from earth
✓ top bolt available in two versions, screw type or press type
✓ different top bolt diameter available suiting to the cable
dimensions
✓ type test certificate in accordance with iec 60840 available
L ±50

operation voltage 72 145 170


um (kV)

typ feV 72-p feV 145-p feV 170-p


conductor cu/al
... 1200 1* ... 1200 1* ... 1200 1*
max. (mm²)

diameter
over dielectric 34.5 - 84,0 34.5 - 97,0 34.5 - 108.0
min. - max. (mm)
~100
diameter
over sheath ... 105 ... 105 ... 105
max. (mm)

screw / press
connection s/p s/p s/p
s/p
450 305 345 381
Length
1500 1950 2150
L (mm)

pollution level iV iV iii

creepage di-
stance > 2248 > 4495 > 4250
min. (mm)
diameter
30 / 50 30 / 50 30 / 50
a (mm)
*1
>1200 up to 2500 mm² special crimping tool is required

9
switchgear and transformer termination
KseV / KteV dry type plug-in
termination up to 145 kV
all versions of dry-type termination are designed for installation Gis KseV transformer KteV
in sf6 gas insulated switchgear (Gis) or for installation in the
oil filled cable box of the transformer. the complete terminati- Ø110
on consists of epoxy resin insulator with embedded electrode, Ø110
fixing ring which is fitting to the cable, comprising metal cable
gland, compression device and premoulded plug-in stress cone
for electrical field control.

✓ plug-in part comprising four components (stress cone made L2


of silicone rubber, cable gland, connection bolt, spring
loaded compression device) L2
✓ insulator according with iec 62271-209 for Gis and din en
L1
50299 for transformer termination L1
✓ conductor connection bolt designed as mechanical screw
type connector
✓ combination with different adapter and additional elec-
trodes are available to fulfil the requirements from iec 60859
part 1 and 2 and older switchgear housings ~304 ~304
✓ type test certificate in accordance with iec 60840 available
✓ dead-end plug available (see page 14)

operation voltage 72 123 ... 145


um (kV)

typ
switchgear KseV 72 KseV 145 d1 d2 d1 d2
transformer KteV 72 KteV 145

conductor cu/al
... 1000 ... 1200
max. (mm²)

diameter
over dielectric 38.5 - 74.0 38.5 - 74.0
min. - max. (mm)

diameter
over sheath ... 99 ... 99
max. (mm)

screw / press
connection s s
s/p

L1
310 ±0.5 470 ±0.5
(mm)

L2
583 ±0.5 757 ±0.5
(mm)

d1
270 ±0.5 320 ±0.5
(mm)

d2
300 350
(mm)
switchgear and transformer terminations

switchgear and transformer termination


KseV / KteV dry type plug-in
termination up to 170 kV
the new version of dry-type plug-in termination is designed for Gis KseV transformer KteV
the voltage level up to um=170 kV and to the biggest conductor
Ø110
cross-section up to 2500 mm². With this large application range
the termination still fulfils the dimensions according to the iec Ø110
standards. the termination is also applicable in the 145 kV vol-
tage level with conductor cross section above 1200 mm².

✓ Very large application range for conductor cross sections up


to 2500 mm² L2
✓ insulator according with iec 62271-209 for Gis and din en
50299 for transformer termination
L2
✓ conductor connection bolt designed as mechanical screw type
connector. L1
L1
✓ combination with different adapter and additional electrodes
are available to fulfil the requirements of iec 60859 part 1 and
2 and older switchgear housings
✓ type test certificate in accordance with iec 60840 available
✓ dead-end plug available (see page 14)
~304 ~304

operation voltage 123 ... 170


um (kV)

typ
switchgear KseV 170
transformer KteV 170

conductor cu/al
... 2500
max. (mm²)
d1 d2 d1 d2
diameter
over dielectric 65.0 - 97.0
min. - max. (mm)

diameter
over sheath ... 135
max. (mm)

screw / press
connection s
s/p

L1
470 ±0.5
(mm)

L2
757 ±0.5
(mm)

d1
320 ±0.5
(mm)

d1
350
(mm)

11
switchgear and transformer termination
seV / teV epoxy insulator
termination
the termination is designed for direct installation in sf6 gas seV 72 kV teV 145/170 kV
insulated switchgear (Gis) or in the oil filled cables box of the
transformer. Major components of the termination are the pres- Ø110 Ø100
sure tight epoxy resin insulator with embedded electrode, metal
fixing ring, metal cable gland and prefabricated stress cone for
electrical field control.

✓ integrated prefabricated stress control system with silicon


rubber
✓ pressure tight epoxy resin insulator is cast in one piece with L1
integratedinsulation ring at the bottom allowing to separate
the cable screen from earth.
L1
✓ cable gland made of corrosion resistant aluminium alloy
✓ possible installation position vertical up to 45° then up to 90°
oil expansion vessel required
✓ type test according to iec 60840 is available 330

L2
operation voltage 72 145 170 330
um (kV)
L2
typ
switchgear seV 72 seV 145 seV 170
transformer teV 72 teV 145 teV 170

conductor cu/al
... 1000 ... 1200 ... 1200 d1 d2
max. (mm²)

diameter
over dielectric 34.4 - 74.0 41.6 - 84.0 41.6 - 84.0 d1 d2
min. - max. (mm)

diameter
over sheath ... 85 ... 105 ... 105
max. (mm)

screw / press
connection s/p s/p s/p
s/p

creepage
distance 500 650 750
(mm)

L1
583 ±1 757 ±1 757 ±1
(mm)

L2
~ 630 ~ 630 ~ 630
(mm)

d1
270 ±0.5 320 ±0.5 320 ±0.5
(mm)

d2
300 350 350
(mm)
switchgear and transformer terminations + straight joints

straight joint
sm 72 – sm 170 premoulded
straight joint
this premoulded straight joint in three piece design with com- operation type conductor diameter diameter connection
pact dimensions is made of silicone rubber. Main components voltage cu / al over diel- Joint type
of the standard straight joint are conductor connection sleeve, max. ectric approx.
cable adapters, main joint sleeve and outer protective covering. um (kV) (mm²) min. - max. (mm) screw / press
(mm)
✓ integrated premoulded stress control system with silicone 72 sM 72 size 36 ...630 40.0 - 54.0 150 s
rubber 72 sM 72 size 46 ...1000 51.5 - 65.0 150 s
✓ three piece design with compact dimensions 72 sM 72 size 56 ...1600 63.0 - 78.0 150 s
✓ screw type conductor connector
✓ Minimum tool requirement 145 sM 145-1 ...1200*1 34.5 - 75.0 180 s/p
✓ Version with screen separation available 145 sM 145-2 ...1200*1 72.0 - 84.0 195 s/p
✓ type test certificate in accordance with iec 60840 available 145 sM 145-3 ...1200*1 81.5 - 108.0 230 s/p

170 sM 170-1 ...1200*1 50.0 - 84.0 225 s/p


170 sM 170-2 ...1200*1 81.5 - 108.0 230 s/p
*1
>1200 up to 2500 mm² special crimping tool is required

sM 72
~800

sM 145

~1210

13
accessories
more accessories for different
applications
✓ Link box for special bonded or earthed cable systems available
· indoor and outdoor gantry mounted
· outdoor within concrete pit in horizontal position
· With 3 zinc oxide sheath voltage limiters
· all metal work in stainless steel
✓ all joints are available with screen separation for special
bonded or earthed cable systems
✓ tools for cable preparation
· sheath stripper
· cable peeling tool to remove outer conductive layer
✓ trainingcourseandsupervisiontoguaranteeperfectinstallation
in our assembly department or on side are possible
Link box with voltage limiters

cable peeling tool sheath stripper

dead-end plug for KseV / KteV 72 / 145 / 170

straight joint with screen separation


accessories + cable data

cable data
requested cable information
to supply the optimal accessories solution detailed cable data customer name / project name:
are required. please send the completed cable data form with
your inquiry.

remarks
offer no.:

order no.:

date:

name:

conductor semicon- dielectric semicon- screen screen / special special oversheath


ductive ductive amouring
inner layer outer layer

diameter (mm) ________ ________ ________ ________ ________ ________ ________ ________ ________
diameter (mm) min. ________ ________ ________
diameter (mm) max. ________ ________ ________
cross section (mm²) ________ ________ ________
thickness (mm) ________ ________ ________ ________ ________ ________ ________ ________ ________

 al  xLpe  cu wires  cu wires  cu wires  cu wires  pe


 cu  epr  cu tapes  cu tapes  cu tapes  cu tapes  pVc
 solid round  rubber  Lead  Lead  Lead  Lead
 solid sector  paper  al screen  al screen  al screen  al screen
 stranded  al wire  al wire  al wire  al wire
 circular  al tape  al tape  al tape  al tape
 Milliken  steel wire  steel wire  steel wire  steel wire
 Keystone  steel tape  steel tape  steel tape  steel tape
 corrug. al  corrug. al  corrug. al  corrug. al
 corrug. cu  corrug. cu  corrug. cu  corrug. cu
 filler  filler  filler
 Laminated  Laminated  Laminated  Laminated
dfffoil al dfffoil al dfffoil al dfffoil al
 Laminated  Laminated  Laminated  Laminated
dfffoil cu dfffoil cu dfffoil cu dfffoil cu

network data:
operation voltage kV
basic impulse level kV
short circuit current (conductor) ka
short circuit current (shield) ka system grounding  solid  isolated  resonant

15
nkt 72-170 kV Gb Katalog - ausgabe 1.09.2009
printed in Germany / www.ostedruck.de
technische Änderungen vorbehalten

nkt cables GmbH


Cable Accessories
Helgoländer Damm 75
D-26954 Nordenham
Phone: +49 (0) 4731 / 364 - 436
Fax: +49 (0) 4731 / 364 - 364
E-Mail: [email protected]
Internet: www.nktcables-acc.com

Completing the picture