2 - Transmission Line Parameters
2 - Transmission Line Parameters
Transmission of electric power has been along the years and will still
continue one of the most important elements of today’s electric power
systems. Power transmission from generating stations to industrial sites
and to substations is the fundamental objective of the transmission
systems.
The Transmission line function is accomplished by overhead AC or DC
transmission lines or underground cables that connect the power plants in
to the transmission network, interconnect various areas of transmission
networks, interconnect one electric utility with another, or deliver the
electric power from various areas within the transmission network to the
distribution substations, from which the distribution systems supply
residential and commercial consumers.
INTRODUCTION
CONT’D
i.e. P = VI = V2/R
Therefore, very high voltage levels are used to transmit power over long
distances. Once the power reaches the area where it will be used, it is
stepped down to a lower voltages in distribution substations, and then
delivered to customers through distribution lines.
Introduction
Cont’d
There two types of transmission lines: overhead lines and buried cables.
Figure 1
Introduction
Cont’d
The transmission and distribution of three-phase electrical power on
overhead lines requires the use of at least three-phase conductors.
In addition, a few lines have been built with three, four or even six
three-phase circuits strung on the same tower structure in various
horizontal and/or triangular formations.
Introduction
Cont’d
Figure 2
OVERHEAD LINE CONT’D
An overhead transmission line usually consists of three conductors or
bundles of conductors containing the three phases of the power system.
The conductors are usually aluminum cable steel reinforced (ACSR),
which are steel core (for strength) and aluminum wires (having low
resistance) wrapped around the core.
OVERHEAD LINE CONT’D
These parameters are uniformly distributed along the whole line. Each
line has its own value, and it is not possible to concentrate or lump
them at discrete points on the line. For this reason the line parameters
are known as distributed parameters. Their values are given in per
unit length of line and they are denoted as R, L, C and G respectively.
The line parameters are functions of the line-geometry, construction
material and operational frequency.
The line resistance and inductance form the series impedance of the
line. While the capacitance and conductance form the shunt admittance
of the line.
CONT…
The term Long line refers to a line having its length more than 240
km. The long line treatment takes all the four parameters in to
account and allows for the fact that they are distributed uniformly over
the entire length of the line.
TRANSMISSION LINE PARAMETERS
CONT’D
RDC = l /A [Ω]
rDC = /A [Ω/m]
A. Skin Effect
The frequency of the AC voltage produces effect on the conductor
resistance due to the non uniform distribution of the current. This
phenomenon is known as skin effect or frequency effect.
As frequency increases, the current tends to go toward the surface of the
conductor and the current density decreases at the center.
Skin effect reduces the effective cross-section area used by the current, and
thus, the effective resistance increases.
Also, although in small amount, a further resistance increase occurs when
other current-carrying conductors are present in the immediate vicinity.
A skin correction factor k, obtained by differential equations and
Bessel functions, is considered to reevaluate the AC resistance.
For 60 Hz, k is estimated around 1.02
𝑅𝐴𝐶=𝑘𝑅𝐷𝐶
B. Temperature Effect
We notice that silver and copper would be among the best conductors.
However, aluminum, being much cheaper and lighter, is used to make
most of the transmission line conductors. Conductors made out of
aluminum should have bigger diameter than copper conductors to offset
the higher resistivity of the material and, therefore, support the necessary
currents.
D. PROXIMITY EFFECTS
Solution
28
L =λ/I
1. Internal inductance:
Consider a conductor of radius r carrying a current
I. At a distance x from the center of this conductor,
the magnetic field intensity Hx can be found from
Ampere’s law:
INDUCTANCE AND INDUCTIVE REACTANCE
CONT’D
I
Where Hx is the magnetic field intensity at each point along a closed path,
dl is a unit vector along that path and Ix is the net current enclosed in the
path. For the homogeneous materials and a circular path of radius x, the
magnitude of Hx is constant, and dl is always parallel to Hx. Therefore:
The flux linkages per meter of length due to flux in the tube is the product
of the differential flux and the fraction of current linked:
INDUCTANCE AND INDUCTIVE REACTANCE
CONT’D
The total internal flux linkages per meter can be found via integration…
Where μ0 = 4л*10-7
2. EXTERNAL INDUCTANCE BETWEEN 2 POINTS OUTSIDE
OF THE LINE
The flux links the full current carried by the conductor, therefore:
The total external flux linkages per meter can be found via integration…
Since the path of radius x2 encloses both conductors and the currents are
equal and opposite, the net current enclosed is 0 and, therefore, there are
no contributions to the total inductance from the magnetic fields at
distances greater than D.
INDUCTANCE OF A SINGLE-PHASE 2-WIRE TRANSMISSION LINE
CONT’D
The total inductance of a wire per unit length in this transmission line is a
sum of the internal inductance and the external inductance between the
conductor surface (r) and the separation distance (D):
By symmetry, the total inductance of the other wire is the same, therefore,
the total inductance of a two-wire transmission line is
INDUCTANCE
The series inductance per phase for the above single phase two wire line can
be expressed in terms of self inductance of each conductor and their mutual
inductance. Consider one meter length of the single phase circuit represented
by two coils characterized by the self inductances 𝐿11 and 𝐿22 and the mutual
inductance 𝐿12 . The magnetic polarity is indicated by dot symbols as shown
in the following Figure .
Consider one meter length of a three phase line with three conductors,
each with radius r, symmetrically spaced in a triangular configuration as
shown in the following Figure.
43
44
5. INDUCTANCE OF THREE PHASE TRANSMISSION LINES -
ASYMMETRICAL SPACING
A three double circuit line consists of two identical three phase circuits. The
circuits are opened with 𝑎1−𝑎2,𝑏1−𝑏2 𝑎𝑛𝑑 𝑐1−𝑐2 in parallel. Because of
geometrical differences between conductors, voltage drop due to line
inductance will be unbalanced. To achieve balance, each phase conductor must
be transposed within its group and with respect to parallel three phase line.
Consider a three phase double circuit line with relative phase positions
𝑎1𝑏1𝑐1−𝑐2𝑏2𝑎2, as shown in the following Figure
55
56
INDUCTANCE OF A TRANSMISSION LINE
CONT’D
A two-conductor A four-conductor
bundle bundle
CONCLUSIONS ON INDUCTANCE OF A TRANSMISSION
LINE
1.The greater the radius of the conductors in a transmission line, the lower
the inductance of the line. In practical transmission lines, instead of using
heavy and inflexible conductors of large radii, two and more conductors
are bundled together to approximate a large diameter conductor. The
more conductors included in the bundle, the better the approximation
becomes. Bundles are often used in the high-voltage transmission lines.
INDUCTIVE REACTANCE OF A LINE
The series inductive reactance of a transmission line depends on both the
inductance of the line and the frequency of the power system. Denoting
the inductance per unit length as l, the inductive reactance per unit length
will be
xI = jωɭ = j2лfɭ
XI = xId
The charge on the conductor gives rise to an electric field with radial flux lines. The
total electric flux is numerically equal to the value of charge on the conductor. The
intensity of the field at any point defined as the force per unit charge and is termed
electric field intensity designated as E. Concentric cylinders surrounding the
conductor are equipentential surfaces and have the same electric flux density.
From Gauss’s law for one meter length of the conductor, the electric flux
density at a cylinder of a radius x is given by
where E is the electric field intensity at that point; is the permittivity of the material:
Ԑ = ԐrԐo
or
CAPACITANCE OF A SINGLE PHASE TWO-WIRE TRANSMISSION
LINE CONT’D
The capacitance per unit length between the two conductors of the line is
CAPACITANCE OF A SINGLE PHASE TWO-WIRE TRANSMISSION
LINE CONT’D
Thus:
The potential difference between each conductor and the ground (or
neutral) is one half of the potential difference between the two conductors.
Therefore, the capacitance to ground of this single-phase transmission
line will be
Recalling 𝜖0=8.85×10−12 𝐹/𝑚 and converting to 𝜇𝐹 per kilometer, we have
1 1
ZC j
YC 2 fcd
POTENTIAL DIFFERENCE IN A MULTICONDUCTOR CONFIGURATION
Multi-conductor configuration.
Assume that the distortion effect is negligible and charge is uniformly distributed
around the conductor, with the following constraint
Using superposition, the potential difference between conductor I and j due to
the presence of all charges is given by:
When k=I, 𝐷𝑖𝑖 is the distance between the surface of the conductor and its
center, namely its radius r.
Consider one meter length of a three phase line with three long conductors, each
with radius r, with conductor spacing as shown in the following figure:
For a balanced three phase system
We shall neglect the effect of ground and the shield wires. Assume that the lines
is transposed. We proceed with the calculation of the potential difference
between a and b for each section of transposition. Applying ( 80) to the first
section of the transposition, 𝑉_𝑎𝑏 is
EFFECT OF EARTH ON THE CAPACITANCE
For an isolated charged conductor the electric flux lines are radial and are
orthogonal to the cylindrical equipotential surfaces. The presence of earth will
alter the distribution of electric flux lines and equipotential surfaces, which will
change the effective capacitance of the line.
The earth level is an equipotential surface, therefore the flux lines are forced to
cut the surface of the earth orthogonally. The effect of the presence of earth can
be accounted for by the method of image charges introduced by Kelvin.
To illustrate this method, consider a conductor with a charge q coulombs/meter at a
high H above ground. Also, imagine a charge –q at a depth –H below the surface of
earth. This configuration without the presence of the earth surface will produce the
same field distribution as a single charge and the earth surface. Thus, the earth can
be replaced for the calculation of electric field potential by a fictitious charged
conductor with charge equal and opposite to the charge on the actual conductor and
at a depth below the surface of the earth the same as the height of the actual
conductor above earth. This, imaginary conductor is called the image of the actual
conductor.
The effect of the earth is to increase the capacitance. But normally the height of
the conductor is large as compared to the distance between the conductors, and
the earth effect is negligible. Therefore, for all line models used for balanced
steady state analysis, the effect of earth on the capacitance can be neglected.
However, for unbalanced analysis such as unbalanced faults, the earth’s effect as
well as the shield wires should be considered.
Example 1:
If a single phase line has parameters D=5ft, r=0.023 ft, and a flat horizontal spacing
H=18ft average line height, determine the effect of the earth on capacitance.
Assume a perfectly conducting earth plane.
Solution:
The earth plane is replaced by a separate image for each overhead conductor, and
the conductors are charged as shown in the above figure. The voltages between
conductors x and y is:
Example 2:
A 500kV three phase transposed line is composed of one ACSR 1,272,000 cmil,
45/7 Bittern conductor per phase with horizontal conductor configuration as shown
in the following Figure. The conductors have a diameter of 1.345 in and a GMR of
0.5328 in. find the inductance and capacitance per phase per kilometer of the line.
8.854 1012
cab 1000 1000 6.794 109 F km
D 1.2
ln ln
r 0.02
d. The series impedance per kilometer of the transmission line is
1 1
Z sh 5
j13.0k
Ysh j 7.684 10