NETYS PR

1000-3000 VA

INSTALLATION AND OPERATING MANUAL


NETYS

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
INSTALLATION AND OPERATING MANUAL

NETYS PR
1000-3000 VA

IOMNETPRXX00-GB_02 - 03.2008

Downloaded from www.Manualslib.com manuals search engine


Thank you for choosing NETYS, a SOCOMEC UPS product.
You have purchased a high professional UPS to provide you protection against black-outs and electrical impurities.
The NETYS range has been designed specifically for the protection of critical electronics and I.T. consumers such
as servers, UNIX workstations or networking peripherals which could suffer hardware damage and data losses as a
result of the disturbance deriving from the electrical mains.
For correct use and to obtain the best performance from this product, please read and follow carefully the instruc-
tions contained within.
Keep this manual at hand for rapid and easy consultation.
ITALIANO
ENGLISH

Reproduction of any part of this manual is forbidden without the manufacturer’s consent. The information and
drawings contained herein may be changed without prior notice and are not binding upon the manufacturer.
SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right to utilize the
document for the application indicated by SOCOMEC UPS is granted to the recipient of such document. All repro-
duction, modification, dissemination of this document whether in part or whole and by any manner are expressly
prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data without prior
notice.

4 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


TABLE OF CONTENTS NETYS PR
1000-3000 VA

1. CERTIFICATE AND CONDITIONS OF WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2. SAFETY STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3. GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4. UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

ENGLISH
4.1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Environmental requirements for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

5. FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

6. REAR VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

7. MIGRATION FROM TOWER TO RACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16


7.1 Migration kit from tower to rack for Netys PR 1500-2000 VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.2 Migration kit from tower to rack for Netys PR 3000 VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

8. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

9. CONFIGURATION AND START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20


9.1 Configuration of the output voltage/battery expansion units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.2 Configuration from mimic panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.2.1 Output voltage configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.2.2 Battery expansion configuration menu (after Output Voltage configuration). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

10. MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21


10.1 Switching the UPS on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.2 Switching the UPS off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.3 Normal mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.4 Battery mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
10.5 Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.6 Self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

11. COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.1 Communication solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.2 RS232 interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.3 USB interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.4 Net Vision card for slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

12. REMEDIES FOR MINOR PROBLEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

13. TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

IOMNETPRXX00-GB_02 5
Downloaded from www.Manualslib.com manuals search engine
ITALIANO

Downloaded from www.Manualslib.com manuals search engine


1
CERTIFICATE AND CONDITIONS
OF WARRANTY
NETYS PR
1000-3000 VA

This SOCOMEC UPS uninterruptible power system is guaranteed against manufacturing and material defects, for a
period of 24 months from the date of purchase and not however more than 27 months from the date of shipment
by SOCOMEC UPS.

The warranty is ‘carry-in’ type: free supply of parts and labour for repairs, with return of a product to be replaced to
SOCOMEC UPS, or authorized centres, at the customer’s cost and risk.

ENGLISH
In order to use the warranty service, the user must respect the following rules:
• The product must be returned exclusively in its original packaging. Any damage caused during shipping in pack-
aging other than the original is not covered by the warranty;
• The product must be accompanied by proof of purchase: a document (bill, invoice, receipt) showing the date
of purchase and the information necessary to identify the product (model, serial number). The number of the
authorization for return for repairs must also be attached, with a detailed description of the defect found in the
product. If any of these elements is missing, the warranty is invalid. The return authorization number is issued by
the service centres by telephone on receiving notification of the malfunction;
The warranty is recognised within Italian territory. If the UPS is exported outside Italian territory, the warranty shall
be limited to the cover of the parts used to repair the fault.

The warranty shall not apply in the following cases:


• Failures due to fortuitous circumstances or force majeure (lightning, floods, etc.);
• Failures due to negligence or improper use (use outside tolerance limits: temperature, humidity, ventilation, elec-
tric power supply, applied load, batteries);
• Insufficient or inadequate maintenance;
• Attempted maintenance, repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from
a support centre authorised by SOCOMEC UPS.
• If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual,
in cases of extended storage or UPS inactivity.

SOCOMEC UPS may, at its own discretion, opt for the repair of the product or for the replacement of the faulty or
defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and
performance.

Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS that becomes the
sole owner.

Replacements or repairs of parts and any modifications to the product during the warranty period shall not extend
the duration of the warranty.

In no case will SOCOMEC UPS be responsible for damages (including, without limitations, damage for loss of earnings,
interruption of activity, loss of information or other economic losses) deriving from the use of the product.

The present conditions are subject to Italian law. Any dispute falls under the province of the Court of Vicenza.

IOMNETPRXX00-GB_02 7
Downloaded from www.Manualslib.com manuals search engine
2 SAFETY STANDARDS NETYS PR
1000-3000 VA

This manual must be kept next to the UPS, so that the operator may consult it at any time for clarification on the
correct use of the UPS. Read the manual carefully before connecting the unit to the mains power supply and to
the devices to be powered. Before switching on the UPS (Uninterruptible Power Supply), the operator must be fully
aware of the functions and positions of all the controls and of the technical and functional characteristics of the
system, in order to avoid any risk to persons and to the equipment.
• Before starting, the unit must have an equipotential connection as established by the safety standards in force. The
ITALIANO
ENGLISH

earth cable of the UPS must be connected to an efficient earth point.


• If the unit is not earthed, all devices connected to the UPS will not have an equipotential connection. In this case
the manufacturer declines all responsibility for damage or accidents caused by non-observance of the aforemen-
tioned standards.
• This is a pluggable type A equipment with battery already installed by the supplier, it’s operator installable and
may be operated by layman.
• In case of power failure (UPS in back up mode), do not disconnect the input cable from the mains so as to ensure
earth connection to the powered loads.
• All subsequent maintenance operations must be carried out solely and exclusively by authorized personnel. Inside
the system high electric voltages are generated which may endanger maintenance personnel who are not suf-
ficiently prepared and trained for such tasks.
• If at any time a hazard condition is created during use, disconnect the mains power supply (if possible through the
control panel upstream of the unit) and shutdown the UPS completely following the appropriate procedure.
• When assembling and replacing the battery, the UPS should always be switched off and disconnected from the
mains power supply. Do not dispose of batteries in a fire, the battery may explode.

CAUTION.
A battery can present a risk of electric shock and high short circuit current.
The following precaution should be observed when working on batteries: remove watches, rings
or other metal objects and use tools with insulated handles.

• The batteries constitute an internal power source for the UPS and mean that the system output may be powered
even when the UPS is not connected to the mains power supply.
• Do not force, break or try to open the batteries. They are sealed and do not require any maintenance. They contain
substances that are toxic to health and that pollute the atmosphere. Do not switch the UPS on if any leakage of
liquid or white powder residue is noted.
• Replace batteries with the same number and type of batteries as originally installed in the equipment.
• Replace the fuses ONLY with other fuses of the same type.
• As the mains cable of the UPS is considered a disconnecting device, the mains socket to which the UPS is con-
nected and/or the rear of the UPS must be accessible and easy to disconnect.
• Avoid contact of the UPS unit with water or liquids in general. Do not introduce foreign bodies.
• If the unit needs to be scrapped, it must be handed over solely and exclusively to specialist disposal companies.
These companies are obliged to break up and dispose of the various components in accordance with the national
legal provisions in force.

8 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


2 SAFETY STANDARDS NETYS PR
1000-3000 VA

• The UPS generates a leakage current of about 1.5 mA. To guarantee the maximum limit leakage current of 3.5 mA,
make sure that the maximum leakage current of the load is 2 mA. If the load current exceeds this value, have
qualified personnel connect the UPS to an industrial type, IEC 309 compliant power supply mains, with a current
of correct dimensions for the UPS power rating.
• Netys UPS is intended for commercial and industrial use; it is not recommended for use in medical applications
that are essential to the survival of the patient.
• Use the UPS in accordance with the technical specifications given in the User Manual.

ENGLISH

IOMNETPRXX00-GB_02 9
Downloaded from www.Manualslib.com manuals search engine
3 GENERAL DESCRIPTION NETYS PR
1000-3000 VA

The main purpose of the UPS is to protect sensitive and critical equipment from electrical disturbances that can
compromise operation. Black-outs, brown-outs, variations in voltage and frequency, lightning, electrostatic dis-
charges and rapid over voltages are phenomena found in all office and industrial environments and which cause
damage to the hardware and loss of data.
Netys is an Uninterruptible Power Supply designed to power computers and connected peripherals, with the excep-
tion of any other electrical device (such as household appliances, television sets, stereo systems and video recorders).
ITALIANO
ENGLISH

3.1 INTRODUCTION.
The characteristic feature of these UPS is the constant monitoring of the power supply which, duly filtered and
stabilised (on models with AVR) and if considered suitable, is used to supply consumers. In cases of a mains failure or
if the mains is considered to be outside limits accepted by the load, the inverter (the heart of the UPS) is activated
immediately. Drawing on the power stored in the batteries, the inverter generates a voltage that instantly takes over
from the mains without any disruption to the equipment connected.
During operation under emergency conditions, the internal batteries discharge but are recharged again automati-
cally when mains power returns.
Being hermetically sealed, the batteries do not require maintenance of any kind at any stage of their working life.

3.1-1 Block diagram.

Automatic Voltage stabilizer


(AVR models only)

Mains input AVR


Output
(to power consumers)

Battery Battery Battery Inverter Automatic


charger for back-up (DC/AC) transfer switch
extensions
(optional)

10 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


4 UNPACKING AND INSTALLATION NETYS PR
1000-3000 VA

4.1 UNPACKING.
Remove the UPS and all the accessories that come with it (cables, CD-ROMs, etc) from its packing case.
It is always advisable to keep the original packaging that has been specially designed for safe transport, in case the
unit has to be moved again.

ENGLISH
4.2 ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION.

Please check what follows before installing the UPS.

• Netys has been designed for use in closed environments.


• Place the UPS on a flat and stable surface, in a ventilated environment away from heat sources and exposure to
direct sunlight.
• Keep ambient temperature between 0 °C and 40 °C and humidity less than 90% (non-condensing); the best tem-
perature to guarantee the longest battery life is 15-20 °C.
• Ensure that the environment where the UPS will be installed is not dusty, and leave a space of at least 20 cm
around it to allow for adequate ventilation and access to the rear panel.
• Make sure not to place the UPS or any other heavy object on the cables.
• Check that the voltage and frequency preset for operation is right for your electrical power supply looking the data
can be found on the data plate.
• Use only the manufacturer-supplied or recommended cables and accessories for connections to the RS232/USB
serial interface.

It is recommended to charge the batteries for 8 hours the first time the unit is used.

WARNING!
The lateral brackets supplied MUST be mounted on models designed for installation in standard
19” cabinets.

IOMNETPRXX00-GB_02 11
Downloaded from www.Manualslib.com manuals search engine
5 FRONT VIEW NETYS PR
1000-3000 VA

Acoustic alarm. Alarm LED.


• Intermittent every 4 seconds: • Flashing: alarm present.
BATTERY MODE. • Lit: fault.
ITALIANO
ENGLISH

• Intermittent every second:


battery low.
• Intermittent every second with
led flashing: overload. Overload LED.
• Continuous: UPS failure. Flashing: overload.

Operating mode LED.


• LED green lit:
NORMAL MODE (mains OK).
• LED green flashing: Load LED bar.
NORMAL MODE (AVR active). • Load level (power %): 25% steps.
• LED yellow flashing:
wide range input mode.
Battery level LED bar.
• Battery level (capacity %): 25% steps.

Battery LED.
• Flashing: battery disconnected.
• Lit: battery needs to be replaced.

Battery Mode LED. ON/OFF Configuration


• Low flashing: BATTERY MODE switch. mode button.
(mains absent or abnormal). Press for 3 seconds.
• Fast flashing: battery low.

Buzzer silence and Button to confirm.


self test mode button.

12 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


5 FRONT VIEW NETYS PR
1000-3000 VA

5.1 ALARM INDICATION.

Fan fault.

ENGLISH
LED flashing.

5.2 FAILURE INDICATION.

Fan failure. Overtemperature stop. Abnormal output voltage.

Abnormal battery recharge. Shortcircuit.

LED lit.

LED flashing.

IOMNETPRXX00-GB_02 13
Downloaded from www.Manualslib.com manuals search engine
6 REAR VIEW NETYS PR
1000-3000 VA

NTP protections (RJ45).


RS232 serial port.

Fan - Air vents.


ITALIANO
ENGLISH

Input socket.
Fuse.

Output sockets.

1000 VA

Slot for optional


communication boards.
Output sockets.
RS232 serial port.

USB port.
Emergency Power Off.

NTP protections (RJ45).

Fan - Air vents.


Input socket.
Fuse.
Battery connection
Battery connection for external extension.
for external extension.

1500 VA
2000 VA

14 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


6 REAR VIEW NETYS PR
1000-3000 VA

Fan - Air vents.


RS232 serial port.

USB port.

ENGLISH
Emergency Power Off.

Slot for optional


Battery connection communication boards.
for external extension.

Output sockets. Output sockets.

Output socket.

NTP protections (RJ45).


Input socket
with fuse.

3000 VA

IOMNETPRXX00-GB_02 15
Downloaded from www.Manualslib.com manuals search engine
7 MIGRATION KIT FROM TOWER TO RACK NETYS PR
1000-3000 VA

7.1 MIGRATION KIT FROM TOWER TO RACK FOR NETYS PR 1500-2000 VA.

7.1-1 7.1-2
ITALIANO
ENGLISH

7.1-3 7.1-4

Front bracket for rack


assembling mode

7.1-5 7.1-6

7.1-7 7.1-8

Rear bracket for rack


assembling mode

16 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


7 MIGRATION KIT FROM TOWER TO RACK NETYS PR
1000-3000 VA

7.2 MIGRATION KIT FROM TOWER TO RACK FOR NETYS PR 3000 VA.

7.2-1 7.2-2

ENGLISH
WARNING!
The lateral brackets supplied MUST be mounted!

7.2-3

Rack fixing accessories

IOMNETPRXX00-GB_02 17
Downloaded from www.Manualslib.com manuals search engine
8 CONNECTIONS NETYS PR
1000-3000 VA

Cables with the appropriate cross-section and conforming to the safety standards in force should
be used for connection to the mains and connection of the loads.

USE OF THE BATTERY EXPANSION (optional on models 1500-2000-3000 VA).


Back-up extension units are available on some models when long-life battery operation is required. By combining
ITALIANO
ENGLISH

the UPS with one or maximum two battery expansion units, back-up times of up to 60 minutes may be obtained.

DANGER!
Make sure that the safety switch on the battery expansion unit is in the “OFF” position during the
connection procedure!

Place the battery expansion unit beside the UPS on the side with no air vents. Connect the battery expansion unit
to the UPS using the special cable supplied.
Once connection has been completed, configure the back-up expansion unit using the special menu as described
in chapter 9.

IN 230 V~
Use the server’s supply
cord (IEC 320)

OUT 230 V~
6 x IEC320

1000 VA

18 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


8 CONNECTIONS NETYS PR
1000-3000 VA

UPS Battery External battery

OUT 230 V~
6 x IEC320

ENGLISH
IN 230 V~
Use the server’s
supply cord
(IEC 320)
1500 VA
2000 VA

Battery connection OUT 230 V~ OUT 230 V~ IN 230 V~


for external extension 8 x IEC320 16 A full load

3000 VA

IOMNETPRXX00-GB_02 19
Downloaded from www.Manualslib.com manuals search engine
9 CONFIGURATION AND START-UP NETYS PR
1000-3000 VA

9.1 CONFIGURATION OF THE OUTPUT VOLTAGE/BATTERY EXPANSION UNITS.

WARNING!
The factory default configuration for the Netys PR model is for operation with an output voltage
of 230 V, without any additional battery expansion units.
No configuration is required for normal use with standard back-up.
ITALIANO
ENGLISH

Parameter settings are configured by using free UPS communication software that can be downloaded from
www.socomec.com. If wide range has been configured the yellow LED will come flashing.
Parameter settings:
• Input mode: 184÷276 V (normal); 160÷276 V (wide range);
• Output voltage: 220/230/240 V;
• Battery expansion units: 0-1-2.

9.2 CONFIGURATION FROM MIMIC PANEL.


Output Voltage and Battery Expansion parameters are also settable by mimic panel following the below procedure.
9.2.1 Output voltage configuration menu.
• Press button for 3 seconds to start the procedure: first current set- 240 V
ting (230 V) LED flashing; 230 V
• Push button again: second current setting (240 V) LED flashing;
220 V
• Push button again: third current setting (220 V) LED flashing;
• Press button for 3 seconds to confirm, at the same time, change to
Battery extentions configuration menu.

9.2.2 Battery expansion configuration menu (after Output Voltage configuration).


• Push button: first configuration; 0 expansion (only UPS) LED flash- 2 battery expansion
ing; 1 battery expansion
• Push button: second configuration; 1 expansion LED flashing;
0 (no battery expansion)
• Push button: third configuration; 2 expansion LED flashing;
• Press button for 3 seconds to confirm configuration and exit.

20 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


10 MODES OF OPERATION NETYS PR
1000-3000 VA

10.1 SWITCHING THE UPS ON.


Switch the UPS on by pressing the ON button on the front panel. The Normal Mode LED will light up; allow ten
seconds for the self-teach procedures to run.
When you are sure that the UPS is functioning properly, the various loads may be switched on and work may com-
mence in protected mode.

ENGLISH
10.2 SWITCHING THE UPS OFF.
WARNING!
This UPS has been designed to control and maintain the battery charge; therefore only in excep-
tional circumstances are you advised to switch it off completely.
To shutdown the UPS completely, press and hold down the OFF button and take out or disconnect the mains
power supply.
The UPS switches off all the LEDs and is then fully deactivated. If the mains cable is not disconnected, the battery-
charger remains active.

10.3 NORMAL MODE.


When mains power is available and the voltage falls within the acceptable range, the Normal Mode LED on the
front panel remains on permanently. In this mode, the loads are powered from the mains power supply either direct-
ly or through the AVR stabiliser which intervenes in cases of voltage peaks. The batteries are constantly recharged.

10.4 BATTERY MODE.


The UPS switches automatically to this operating mode when mains power fails (spikes or lengthy black-outs) or
if the mains is at a value considered to be dangerous; the consumers are powered using the energy stored in the
batteries converted to AC voltage through the inverter.
In this mode, a slow intermittent acoustic alarm sounds, while the Battery Mode LED on the front panel flashes.
In cases of prolonged mains failure, the UPS powers the consumers until it shuts down when the batteries are fully
depleted (see the chapter on COMMUNICATION for orderly shutdown via software).
Just before shutdown when the battery charge runs out fully, low battery charge is signalled via a rapid intermittent
acoustic alarm.
The UPS automatically returns to normal operating mode about two seconds after the mains power is restored. The
time taken to transfer from normal to battery mode and vice-versa is imperceptible to the load.

IOMNETPRXX00-GB_02 21
Downloaded from www.Manualslib.com manuals search engine
10 MODES OF OPERATION NETYS PR
1000-3000 VA

10.5 OVERLOAD.
The UPS can power loads up to the power rating declared on the machine’s data plate; once this limit is exceeded,
the machine goes into overload condition. Overloads are signalled by a rapid sounding acoustic alarm .
WARNING!
Significant overloads could cause permanent damage to the UPS!
Avoid connecting laser printers that generate absorption peaks liable to cause overloads on the UPS.
ITALIANO
ENGLISH

10.6 SELF TEST.


In Normal Mode, when the button is pressed for more than five seconds, a procedure is run to check battery and
inverter operation.
If everything is working properly, the UPS automatically returns to Normal Mode; if not the test is suspended and the
battery failure is reported through the Battery failure LED .
If the test fails, however, it is recommended that you leave the battery to charge overnight and repeat the test the next
day.
It is advisable to perform the test with the batteries fully charged (LED bar fully lit up).

22 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


11 COMMUNICATION NETYS PR
1000-3000 VA

The UPS provides excellent protection against interruptions or imperfections in the mains power supply. In these
cases the computer (load) is powered by the UPS using battery power until this runs out.
Various software applications and communication options are available to optimise operation of the UPS and to
correctly manage shutdown when back-up power ends. The status of the UPS can be monitored, keeping track of
all the mains failures and battery discharges so as to activate an automatic and orderly procedure to close the pro-
grams and shutdown the system. When mains power returns the system will restart automatically.
All Netys models are equipped with RS232 and USB communication interface (USB not available on the Netys PR

ENGLISH
1000 model).

11.1 COMMUNICATION SOLUTIONS.


Depending on the model, there are different types of connections and software compatibility as shown in the table
below:
• Uni Vision: local management software for local shutdown of Windows™ & Linux systems, free on
www.socomec.com - RS232 interface
• Uni Vision Pro: network management software for local and remote shutdown: supports the major operating
systems through Java Shutdown Client technology - RS232 interface
• HID: UPS management based on Windows™ embedded service - USB interface
• NetVision: Web/SNMP manager for UPS control over LAN with TCP/IP protocol. Allows remote shutdown through
Java Shutdown Client technology - Web/SNMP card
• BMS: possibility to integrate the UPS with BMS (Building Management Systems) - JBUS protocol

11.2 RS232 INTERFACE.


Communication with the server can take place directly via the RS232 interface.
In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters
regarding battery status and the automatic programming of the UPS start-up and shutdown procedures.
For a complete description of the software features, refer to the Uni Vision and Uni Vision Pro documentation.

11.3 USB INTERFACE.


In addition to the RS232 serial link, it is also possible to establish communication directly through USB with the
HID protocol, when this is available in the operating system. In this case, no SW needs to be installed. A standard
USB cable is used and once this is connected, it is recognised just as any normal peripheral. The control param-
eters of the unit can be set directly via the operating system service menu.

11.4 NET VISION CARD FOR SLOT.


Net Vision permits direct connection of the UPS to a LAN (RJ45 Ethernet) and remote control of the UPS through
TCP/IP using a WEB browser. For a complete description, refer to the Net Vision documentation.

IOMNETPRXX00-GB_02 23
Downloaded from www.Manualslib.com manuals search engine
12 REMEDIES FOR MINOR PROBLEMS NETYS PR
1000-3000 VA

This section examines some of most likely problems that can compromise correct operation of the UPS, attempting
to solve them and identifying the possible causes and remedies.

WARNING!
THE UPS INTERNALLY GENERATES HAZARDOUS ELECTRICAL VOLTAGES.
ALL MAINTENANCE MUST BE PERFORMED SOLELY AND EXCLUSIVELY BY AUTHORIZED
PERSONNEL.
ITALIANO
ENGLISH

If you have difficulty in getting the UPS to work, the reason may be among those listed below. For any other prob-
lem, you are advised to get in touch with your dealer or service organisation directly.
For quick and effective action, when you call it is important to give precise details of the defect, the model number
and the manufacturing serial number that can be found on the conformance and inspection certificate or on the
data plate on the bottom of the UPS.

Troubleshooting for minor problems


Problem Possible cause Solution

Poor connection to the input mains. Check the connection of the cable to
the UPS and to the mains outlet.

The UPS works in battery mode even if The mains voltage is out of range. No solution because mode of opera-
mains power is available. tion is correct.

Input protection triggered Replace the input fuse with another of


(blown fuse or automatic switch). the same type or reset the automatic
switch.

Batteries not fully charged. Leave the batteries to charge for 8


hours consecutively.
Back-up time shorter than expected.
Have the batteries replaced by author-
Batteries not working properly
ised personnel.

The UPS stalls/goes into overload Check that the load applied is not
alarm. Overload on the load line greater than the maximum permitted
or reduce the load power requirement.

IF THE EQUIPMENT IS TO BE LEFT IDLE FOR A LONG PERIOD, WAIT FOR THE BATTERIES TO
CHARGE FULLY BEFORE SWITCHING OFF. WHILE THE UPS IS LEFT IDLE, MAKE SURE THAT THE
BATTERIES ARE RECHARGED FOR 24 HOURS AT LEAST ONCE EVERY 4 WEEKS.

24 IOMNETPRXX00-GB_02

Downloaded from www.Manualslib.com manuals search engine


13 TECHNICAL SPECIFICATIONS NETYS PR
1000-3000 VA

Models
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Power (VA) 1000 1500 2000 3000
Power (W) 700 1000 1340 2100

Electrical specifications - Input


PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT

ENGLISH
Voltage 160 (selecting wide mode) - 276 V (230 V nominal)
Frequency 50/60 Hz with automatic selection
Mains connection IEC320 (10 A) IEC320 (10 A) IEC320 (10 A) IEC320 (16 A)
Spike protection IEC 61000-4-5 300 V, 230 j / 6500 A 300 V, 460 j / 6500 A 300 V, 460 j / 6500 A 300 V, 460 j / 6500 A

Electrical specifications - Output


PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Voltage (in Normal Mode with AVR) The AVR increases (boost 1) the output voltage by 15%
when the input voltage drops below 90% of the nominal value.
The AVR decreases (bucks) the output voltage by 12%
when the input voltage rises above 110% of the nominal value.
Voltage (in Battery Mode) 230 V ± 5% (-10% after battery low)
Frequency 50/60 Hz
Wave form Sinusoidal
Transfer time 2-4 milliseconds (typical)
Normal Mode protections overload (110% for 3 minutes); shortcircuit protected
Battery Mode protections overload (110% for 30 seconds); shortcircuit protected
Load connection socket IEC 320 6 (10 A) 6 (10 A) 6 (10 A) 8 (10 A) + 1 (16 A)

Battery
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Typical back-up time (selecting wide mode) 8 min 8 min 8 min 8 min
Battery recharge 4 hours 80% Cn (after full discharge).
Under permanent charge even when the UPS is off (mains present).

Communication
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Communication interface RS232 RS232 - USB RS232 - USB RS232 - USB
Ethernet adapter NET-VISION (TCP/IP & SNMP) optional card (not for 1000 VA model)
Local communication software UPS Management software – Windows™ & Linux (free download)
Local and remote communication software Optional UNI VISION PRO CD Windows™, AIX4.3/5.1, HP-UX10.20/11, Solaris 8/9, GNU/Linux, Novell.5/6
Data line protection NTP data line suppressor: RJ45 10 Base T

Environment
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Noise level (normal mode) < 45 dBA (at 1 meter)
Temperature 0÷40 °C (10÷25 °C for optimum battery life)
Environment Altitude: 2000 m, humidity: 95% non-condensing
Reference standards (EN) IEC62040-1-1 (safety), EN 62040-1-2 (EMC), EN 61000-4-5/C62.41:1991 (surge)

Mechanical characteristics
PR 1000 MT PR 1500 MT PR 2000 MT PR 3000 RT
Dimensions (WxDxH mm) 87 x 385 x 235 2 x (87x 415 x 220) 2 x (87x 415 x 220) 87 x 585 x 440
Dimensions (WxDxH mm) 2U, RM - 435 x 415 x 87 435 x 415 x 87 440 x 585 x 87
Net weight (kg) 9.6 18 19 31.5

IOMNETPRXX00-GB_02 25
Downloaded from www.Manualslib.com manuals search engine
SOCOMEC UPS WORLDWIDE.
HEAD OFFICE. SALES AND MARKETING MANAGEMENT.
SOCOMEC UPS Strasbourg SOCOMEC UPS Paris
11, route de Strasbourg - B.P. 10050 - F-67235 Huttenheim Cedex - FRANCE 95, rue Pierre Grange
Tel. +33 (0)3 88 57 45 45 - Fax +33 (0)3 88 74 07 90 F-94132 Fontenay-sous-Bois Cedex - FRANCE
[email protected] Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
[email protected]
SOCOMEC UPS Isola Vicentina
Via Sila, 1/3 - I - 36033 Isola Vicentina VI - ITALY
Tel. +39 0444 598 611 - Fax +39 0444 598 622 www.socomec.com
[email protected]

IN EUROPE. IN ASIA.
BELGIUM CHINA
Schaatsstraat, 30 rue du Patinage - B - 1190 Bruxelles No.1 Yuanda Road Haidian District, Beijing 100089
Tel. +32 (0)2 340 02 34 - Fax +32 (0)2 346 16 69 Golden Resources Times Shopping Mall
[email protected] No. 1010 section B the 2nd issue of business building
Tel: + 86 10 82 62 10 28 - Fax: +86 10 82 62 03 62
FRANCE
[email protected]
95, rue Pierre Grange - F - 94132 Fontenay-sous-Bois Cedex
www.socomec.com.cn
Tel. +33 (0)1 45 14 63 90 - Fax +33 (0)1 48 77 31 12
[email protected] INDIA
SOCOMEC NUMERIC
GERMANY
No 5 Sir P.S. Sivasamy Salai
Heppenheimerstraße 57 - D - 68309 Mannheim
Mylapore - Chennay - 600 004
Tel. +49 (0) 621 7168 40 - Fax +49 (0) 621 7168 444
Tel: +91 44 2499 3266 - Fax: +91 41 2499 8210
[email protected]
[email protected]
ITALY
MALAYSIA
Via Leone Tolstoi, 73 - Zivido - 20098 San Giuliano Milanese MI
31 Jalan SS 25/41 - Mayang Industrial Park
Tel. +39 02 98 242 942 - Fax +39 02 98 240 723
47301 Petaling Jaya. - Selangor, Malaysia
[email protected]
Tel: +603 7804 0850 Fax: +603 7803 8489
NETHERLANDS [email protected]
Bergveste 2F - NL - 3992De Houten
SINGAPORE
Tel. +31 (0)30 63 71 504 - Fax +31 (0)30 63 72 166
31 Ubi Road 1, Aztech Building
[email protected]
# 01-00 (Annex) - SG - Singapore 408694
POLAND Tel : +65 6745 7555 Fax : + 65 6458 7377
Nowowiejska St 21/25 - 00-665 Warszawa [email protected]
Tel. +48 22 2345 223 - Fax +48 222345 223 www.socomec.com.sg
[email protected]
THAILAND
RUSSIA 17/178 Prachachuen Road - Tungsonghong, Laksi
Kutuzovsky pr. 13, 44-45 - 121248 - Moscow TH - 10210 Bangkok
Tel. +7 495 775 19 85 - Fax +7 495 764 31 55 Tel. +66 2 503 92 43 - Fax +66 2 503 99 23
[email protected] [email protected]
SLOVENIA
Savlje 89 - SI - 1000 Ljubljana
Tel. +386 1 5807 860 - Fax +386 1 5611 173
[email protected]
SPAIN
C/Nord, 22 Pol. Ind. Buvisa - E - 08329 Teià (Barcelona)
Tel. +34 93540 7575 - Fax +34 93540 7576
[email protected] - www.socomec-aron.com
UNITED KINGDOM
Units 7-9 Lake Side Business Park - Broadway Lane SOCOMEC UPS retains the full and exclusive ownership rights over this document. Only a personal right
to utilize the document for the application indicated by SOCOMEC UPS is granted to the recipient of such
South Cerney - Cirencester GL7 5XL document. All reproduction, modification, dissemination of this document whether in part or whole and
Tel. +44 (0) 1285 863300 - Fax +44 (0) 1285 862304 by any manner are expressly prohibited except upon Socomec’s express prior written consent.
This document is not a specification. SOCOMEC UPS reserves the right to make any changes to data
[email protected] without prior notice.
Valid for France Valid for Italy

IOMNETPRXX00-GB_02 - 03.2008

Downloaded from www.Manualslib.com manuals search engine

You might also like