Sinteso™ / Cerberus™ PRO / Cerberus™ FIT

ASA linear smoke detector


FDL241-9

Linear smoke detector addressed or collective, ASAtechnologyTM

● Reliable smoke detection in large spaces (indoor application)


● Detection distance 10…100 m
● Signal processing with ASAtechnology
● Works according to the principle of light attenuation by smoke
● Microprocessor-controlled signal processing
● Automatic compensation for soiling
● High immunity to extraneous light and electromagnetic interference
● Transmitter and receiver in one housing
● Distance measurement between transmitter and receiver
● Communication via FDnet/C-NET (individually addressed) or collective detector
line (switchover)

007017_v_en_-- Smart Infrastructure


2019-06-18
Properties

Features
● Integrated line separator: The section of the detector line affected by the short-circuit is
located by the fire control panel and isolated between two FDnet/C-NET devices.
● The detector and base housing is made from hard-wearing glass-fiber-reinforced plastic.
● Protected electronics
● Built-in alarm indicator
● Self test function
● Detector heating unit in case of danger of moisture condensation
● 3 sensitivity levels and event-driven detection behavior
● Addressed signal processing:
– Transmission of 4 danger levels to the control panel: Enables activation of
differentiated measures and an early warning in the case of incorrect applications
– 4 functional states: As well as the normal state, the detector transmits a notice, an
impairment, or a fault (depending on the significance of the cause of the problem).
● Collective signal processing:
– The detector transmits alarm states and fault states to the control panel.

Eco-friendly
● Environmentally friendly processing
● Reusable materials
● Electronic parts and synthetic materials can be easily separated

Use
● Buildings with historically valuable ceilings
● Atriums, detection on multiple levels
● Large rooms and high halls
● Churches
● Long corridors, cable and energy ducts with a room height of more than 3 m
● Airplane hangars with stable building construction, in which flame detectors alone do not
suffice
● Saw-tooth roofs, where point detectors must be suspended lower

Intended use
The linear smoke detector FDL241-9 is only permitted for use on an FDnet/C-NET detector
line or a collective detector line in one of the following fire detection systems:
● FS20
● FS720
● FC360

2
Smart Infrastructure 007017_v_en_--
2019-06-18
Functions
The linear smoke detector smoke detector consists of a transmitter and a receiver and works
according to the principle of light attenuation by smoke.
The transmitter transmits to the reflector a highly focused infrared ray. If no smoke is
present, a large part of the infrared ray reaches the reflector and is returned to the receiver.
The incoming light generates an electric signal on the receiver's photo diode.
Smoke entering the measuring section weakens the infrared ray. If the signal reaches
specific measured values, the detector transmits the corresponding danger level to the
control panel.
● Distance measurement to detect foreign bodies
● The alarm state is signaled locally with the built-in alarm indicator.
1 2

max. 5...100 m

1 Detector / receiver 3 Detector / transmitter


2 Reflector

Environmental influences
● Digital signal compensation:
– Slow changes to the received infrared signal as a consequence of dusty lenses or
other environmental influences are automatically compensated by the detector.
● Multiple-coincidence circuit:
– Suppresses electrical and optical fault signals. In the case of an extremely strong
incidence of extraneous light, the extraneous light filter DLF1191-AC is used in
addition.
● Prism-shaped reflectors:
– Incident rays of light are reflected in parallel.
– The detector is not affected by mounting surface vibration phenomena.

3
Smart Infrastructure 007017_v_en_--
2019-06-18
Accessories

DLR1191 reflector for long distance (prism)


● For reflecting the infrared ray of the linear smoke detector
● Prism-shaped reflector
● Reflection distance: 20…100 m
● With a built-in heating unit

DLR1192 reflector for middle distance (foil)


● For reflecting the infrared ray of the linear smoke detector
● Micro-prismatic film
● Reflection distance: 30…65 m
● Dimensions: 200 x 200 x 2.5 mm
● Hole diameter: 4 mm

DLR1193 reflector for short distance (foil)


● For reflecting the infrared ray of the linear smoke detector
● Micro-prismatic film
● Reflection distance: 10…30 m
● Dimensions: 100 x 100 x 2.5 mm
● Hole diameter: 4 mm

DLH1191A detector heating unit


● For applications where there is danger of moisture condensation or
icing
● Incl. terminal block for the connection

DLF1191-AA short distance filter (7…10 m)


● For toning down the infrared ray over short distances
● Distance: 7…10 m

DLF1191-AB short distance filter (5…8 m)


● For toning down the infrared ray over short distances
● Distance: 5…8 m

DLF1191-AC extraneous light filter


● For filtering extraneous light during a high level of extraneous light

4
Smart Infrastructure 007017_v_en_--
2019-06-18
FDLU291 adjustment kit for linear smoke detector
● For commissioning the linear smoke detector
● Scope of delivery: Adjustment device, alarm test filter, visor, magnet,
spiral cable, MC link cable, 9 V battery, suspension fixture with cable
gripper and chain, case

Type Overview

Linear smoke detector FDL241-9

Type Designation Order number Weight [kg]


FDL241-9 Linear smoke detector A5Q00002298 0.440

Accessories for linear smoke detector FDL241-9

Type Designation Order number Weight [kg]


FDLB291 Base for linear smoke detector A5Q00003941 0.305
– M20 x 1.5 metal cable gland A5Q00004478 0.036
DLF1191-AA Short distance filter (7…10 m) BPZ:4933030001 0.005
DLF1191-AB Short distance filter (5…8 m) BPZ:4933160001 0.005
DLF1191-AC Extraneous light filter BPZ:5221480001 0.005
DLH1191A Detector heating unit BPZ:4787970001 0.010
DLR1191 Reflector for long distance (prism) BPZ:4787710001 0.510
DLR1192 Reflector for middle distance (foil) BPZ:4788490001 0.075
DLR1193 Reflector for short distance (foil) BPZ:4787840001 0.025
FDLU291 Adjustment kit for linear smoke A5Q00004905 0.840
detector
RE10 Detector tester for linear smoke BPZ:3685190001 0.345
detectors
TF04 Alarm test filter (absorption 77 %) BPZ:4931090001 0.005

5
Smart Infrastructure 007017_v_en_--
2019-06-18
Product documentation

Document ID Name
007016 Technical manual Linear smoke detector FDL241-9
008164 Equipment overview Sinteso™ Detector system FD20
008331 List of compatibility (for 'Sinteso™' product line)
A6V10229261 List of compatibility (for 'Cerberus™ PRO' product line)
A6V10332811 Mounting/Commissioning Linear smoke detector FDL241-9
A6V10882301 List of compatibility (for 'FC360' product line)

Related documents such as the environmental declarations, CE declarations, etc., can be


downloaded from the following Internet address:
https://siemens.com/bt/download

Notes

Mounting

Mounting options
● Easy mounting of the housing on stable surfaces. Wood and steel girder constructions
are usually unsuited, as temperature and humidity fluctuations, wind or snow pressure
can affect them.
● 6 openings for M20 metal cable gland
● External alarm indicator can be connected
● Between the detector and the reflector there must be an uninterrupted and clear line of
sight. Obfuscation of sight caused by operational generation of dust, vapor or smoke
may decisively impair the system. The monitoring ray must not be interrupted by moving
objects, e.g., overhead cranes, ladders, transportable objects, cobwebs, etc.
● The adjustment kit FDLU291 provides an effective means of aligning the lens with the
reflector single-handedly.
● Corresponding reflectors are available for different distances.

Disposal

The device is considered an electronic device for disposal in accordance


with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.

6
Smart Infrastructure 007017_v_en_--
2019-06-18
Technical data

Linear smoke detector FDL241-9


Operating voltage addressed / collective DC 12…33 V / DC 14…28 V
Operating current (quiet) addressed / collective 0.8 mA / 0.7 mA
Number of external alarm indicators that can 2
be connected
Detection distance 10…100 m
Operating temperature -25…+60 °C
Operating temperature checked in accordance -10…+55 °C
with EN 54-12
Storage temperature -30…+75 °C
Air humidity (no moisture condensation) ≤95 % rel.
Communication protocol FDnet/C-NET or collective (with and without current limitation)
Conductor cross section 0.2…1.5 mm²
Color ~RAL 9010 pure white
Protection category (IEC 60529) IP65
Standards EN 54-12 1, EN 54-17, EN 62471
(1 with detection distance of 10…100 m)
Approvals
● VdS G204063
● LPCB 126bd/02
● FM 3029351
System compatibility
● FDnet FS20, AlgoRex, SIGMASYS
● C-NET FS720, FC360
Collective system compatibility CZ10, BC10, FC10, XC10, CS11, FC700A, FC330A,
SIGMASYS, BMS, SM80/88/D100

Detector heating unit DLH1191A


Operating voltage DC 20…33 V
Operating current (quiescent) 30…50 mA
Resistance 600 Ω

7
Smart Infrastructure 007017_v_en_--
2019-06-18
Dimensional drawings

ASA linear smoke detector FDL241-9 with base FDLB291


135 M20 x 1.5

135

115
3
15
4.
5
Reflector for long distance (prism) DLR1191 with base FDLB291
135

M20 x 1.5

45
135

65
3
15
4.
5

Reflector for short distance (foil) DLR1193/


Reflector for middle distance (foil) DLR1192
2.5 100/200
100/200
4.0

Siemens Schweiz AG; Theilerstrasse 1a


19 0786 FDL241-9 CH-6300 Zug
Technical data: see doc. 007016
FDL241-9 - Linear optical smoke detector incl. short-circuit isolator for use in fire detection and fire alarm systems installed in buildings.
305/2011/EU (CPR): EN 54-12 / EN 54-17 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581
The declared performance and conformity can be seen in the Declaration of Performance (DoP) and the EU Declaration of Conformity (DoC), which is
obtainable via the Customer Support Center: Tel. +49 89 9221-8000 or https://siemens.com/bt/download
DoP No.: DOP190401; DoC No.: CED-FDL241-9

Issued by © Siemens Switzerland Ltd, 2007


Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.