Panelboards Specifications
Panelboards Specifications
PART 1 GENERAL
1.01 SECTION INCLUDES A. Lighting and Appliance Panelboard - Furnish and install lighting and
appliance panelboard(s) as specified herein and where shown on the
associated [schedules] [drawings].
1.02 REFERENCES The panelboard(s) and circuit breaker(s) referenced herein are designed
and manufactured according to the latest revision of the following
specifications.
A. NEMA PB 1 - Panelboards
E. UL 67 – Panelboards
1.03 SUBMITTAL AND A. Approval documents shall include drawings. Drawings shall contain overall
RECORD panelboard dimensions, interior mounting dimensions, and wiring gutter
DOCUMENTATION dimensions. The location of the main, branches, and solid neutral shall be
clearly shown. In addition, the drawing shall illustrate one line diagrams
with applicable voltage systems.
1.04 QUALIFICATIONS A. Company specializing in manufacturing of panelboard products with a
minimum of fifty (50) years documented experience.
1.05 DELIVERY, A. Inspect and report concealed damage to carrier within their required time
STORAGE, AND period.
HANDLING
B. Handle carefully to avoid damage to panelboard internal components,
enclosure, and finish.
1.06 OPERATIONS AND A. Manufacturer shall provide installation instructions and NEMA Standards
MAINTENANCE Publication PB 1.1 - Instructions for Safe Installation, Operation and
MATERIALS Maintenance of Panelboards Rated 600 Volts or Less.
1.07 WARRANTY A. Manufacturer shall warrant specified equipment free from defects in
materials and workmanship for the lesser of one (1) year from the date of
installation or eighteen (18) months from the date of purchase.
1.08 RELATED WORK A. Section 16440-9 - Remote Controlled Lighting Panelboard System
PART 2 PRODUCTS
2.01 MANUFACTURERS A. Shall be Square D Company NQOD – Class1630
2
d. Provide one (1) continuous bus bar per phase. Each bus bar shall
have sequentially phased branch circuit connectors suitable for
plug-on or bolt-on branch circuit breakers. The bussing shall be
fully rated. Panelboard bus current ratings shall be determined by
heat-rise tests conducted in accordance with UL 67. Bussing rated
100-400 amperes shall be plated [copper] [aluminum]. Bussing
rated for 600 amperes shall be plated copper as standard
construction. Bus bar plating shall run the entire length of the bus
bar. Panelboards shall be suitable for use as Service Equipment
when application requirements comply with UL 67 and NEC
Articles 230-F and -G.
3
all poles. Circuit breaker frame sizes above 100 amperes shall
have a single magnetic trip adjustment located on the front of the
circuit breaker that allows the user to simultaneously select the
desired trip level of all poles. Circuit breakers shall have a push-to-
trip button for maintenance and testing purposes.
g. The circuit breakers shall be UL Listed for use with the following
accessories: Shunt Trip, Under Voltage Trip, Ground Fault Shunt
Trip, Auxiliary Switch, Alarm Switch, Mechanical Lug Kits, and
Compression Lug Kits.
4
g. Breakers shall be UL Listed for use with the following factory
installed accessories: Shunt Trip, Auxiliary Switch, and Alarm
Switch.
4. Enclosures
a. Type 1 Boxes
b. Type 1 Fronts
4) Front shall have cylindrical tumbler type lock with catch and
spring-loaded stainless steel door pull. All lock assemblies
shall be keyed alike. One (1) key shall be provided with each
lock. A clear plastic directory cardholder shall be mounted on
the inside of door.
5
3) Maximum enclosure dimensions shall not exceed 21” wide and
6.5” deep.
PART 3 EXECUTION
3.01 INSTALLATION A. Install panelboards in accordance with manufacturer's written instructions,
NEMA PB 1.1 and NEC standards.
3.02 FIELD QUALITY A. Inspect complete installation for physical damage, proper alignment,
CONTROL anchorage, and grounding.
END OF SECTION
6
Schneider Electric
Engineered DE Marketing Head Office/Siège social
19, Waterman Avenue 19, Waterman Avenue
Toronto, Ontario M4B 1Y2 Toronto, Ontario M4B 1Y2
Tel.: (416) 752–8020 Tel.: (416) 752–8020
Fax: (416) 752–6230 Fax: (416) 752–8944
www.schneider-electric.ca