Section 3 Power Transformers
Section 3 Power Transformers
TRANSFORMERS
ESE 470 – Energy Distribution Systems
Power Transformers
2
www.exportersindia.com
Ampere’s law
1
∮ 𝑯𝑯 ⋅ 𝑑𝑑𝑑𝑑 = 𝜇𝜇
∮ 𝑩𝑩 ⋅ 𝑑𝑑𝑑𝑑 = 𝐼𝐼 (1)
𝑑𝑑𝑑𝑑
𝑣𝑣 𝑡𝑡 = −𝑁𝑁
𝑑𝑑𝑑𝑑
The negative sign in Faraday’s law
gives the voltage polarity
Close the loop with an external
resistance
Current flows and generates a magnetic
field
Magnetic field opposes the original
change in magnetic flux
This is Lenz’s law
Often see Faraday’s law written without the negative sign
� 𝑯𝑯 ⋅ 𝑑𝑑𝑑𝑑 = 𝐼𝐼
We define the turns ratio as the ratio of the number of turns on the
primary winding to the number of turns on the secondary winding
𝑁𝑁1
𝑎𝑎𝑡𝑡 = (14)
𝑁𝑁2
Using the turns ratio, the current relationships are
1
𝑰𝑰𝟏𝟏 = 𝑰𝑰 and 𝑰𝑰𝟐𝟐 = 𝑎𝑎𝑡𝑡 𝑰𝑰𝟏𝟏 (15)
𝑎𝑎𝑡𝑡 𝟐𝟐
Step-up transformer
𝑎𝑎𝑡𝑡 < 1, 𝑁𝑁1 < 𝑁𝑁2
Voltage increases from primary to secondary
Current decreases
Step-down transformer
𝑎𝑎𝑡𝑡 > 1, 𝑁𝑁1 > 𝑁𝑁2
Voltage decreases from primary to secondary
Current increases
The impedance seen looking into the primary side of a transformer is the
impedance connected to the secondary side multiplied by the turns ratio
squared
The reflected load impedance
K. Webb ESE 470
20 Real Transformer Models
Core losses
𝑁𝑁2 𝑅𝑅
𝑰𝑰𝟏𝟏 − 𝑰𝑰 = −𝑗𝑗 2 𝑽𝑽𝟏𝟏 (24)
𝑁𝑁1 𝟐𝟐 𝑁𝑁1 𝜔𝜔
Open-circuit test
Rated voltage applied to the primary
Secondary is open – no load
Measure current and power loss at the primary
Neglect series impedances
Short-circuit test
Rated current applied at the primary side
Secondary side is shorted
Measure voltage and power loss at the primary side
Neglect shunt admittance
1 1
𝑅𝑅𝑐𝑐 = = 2.3 𝑀𝑀Ω and 𝑋𝑋𝑚𝑚 = = 9.62 𝑘𝑘Ω
𝐺𝐺𝑐𝑐 𝐵𝐵𝑚𝑚
K. Webb ESE 470
Transformer Model – Example
35
The selected base values are all related by transformer turns ratios
Transformers are eliminated from the per-unit schematic
Initial schematic:
Per-unit schematic:
Transformers have
been eliminated
All values are in
per-unit (p.u.)
Zone 3:
𝑉𝑉𝑏𝑏3 = 4.8 𝑘𝑘𝑘𝑘
2
𝑉𝑉𝑏𝑏3 4.8 𝑘𝑘𝑘𝑘 2
𝑍𝑍𝑏𝑏3 = = = 46.1 Ω
𝑆𝑆𝑏𝑏 500 𝑘𝑘𝑘𝑘𝑘𝑘
𝑉𝑉𝑏𝑏3 4.8 𝑘𝑘𝑘𝑘
𝐼𝐼𝑏𝑏3 = = = 104.1 𝐴𝐴
𝑍𝑍𝑏𝑏3 46.1 Ω
Next, calculate the per-unit circuit impedances, starting with zone 1:
𝑋𝑋1 2Ω
𝑋𝑋1,𝑝𝑝𝑝𝑝 = = = 0.174 𝑝𝑝. 𝑢𝑢.
𝑍𝑍𝑏𝑏𝑏 11.5 Ω
For transformer T1, the base voltages are the same as the
nameplate rating for the transformer
Per-unit leakage reactance is the same as the nameplate value
𝑋𝑋𝑇𝑇1,𝑝𝑝𝑝𝑝 = 0.08 𝑝𝑝. 𝑢𝑢.
K. Webb ESE 470
Single-Phase Per-Unit Conversion – Example
48
In zone 2:
20 Ω
𝑋𝑋2,𝑝𝑝𝑝𝑝 = = 0.109 𝑝𝑝. 𝑢𝑢.
184.3 Ω
For the circuit from the previous example, determine the per-unit
and actual load current
Very simple when using the per-unit circuit
𝑉𝑉𝑠𝑠,𝑝𝑝𝑝𝑝
𝑰𝑰𝐿𝐿,𝑝𝑝𝑝𝑝 =
𝑅𝑅𝐿𝐿 + 𝑗𝑗 𝑋𝑋1,𝑝𝑝𝑝𝑝 + 𝑋𝑋𝑇𝑇1,𝑝𝑝𝑝𝑝 + 𝑋𝑋2,𝑝𝑝𝑝𝑝 + 𝑋𝑋𝑇𝑇2,𝑝𝑝𝑝𝑝 + 𝑋𝑋𝐿𝐿,𝑝𝑝𝑝𝑝
1∠0°
𝑰𝑰𝐿𝐿,𝑝𝑝𝑝𝑝 = = 1.33∠ − 73.2° 𝑝𝑝. 𝑢𝑢.
0.217 + 𝑗𝑗𝑗.717 𝑝𝑝. 𝑢𝑢.
2
𝑉𝑉𝑏𝑏,𝐿𝐿𝐿𝐿2 69 𝑘𝑘𝑘𝑘 2
𝑍𝑍𝑏𝑏𝑏 = = = 31.74 Ω
𝑆𝑆𝑏𝑏𝑏𝑏𝑏 150 𝑀𝑀𝑀𝑀𝑀𝑀
Now, use the per-unit circuit to determine the per-unit load current
∗ ∗
𝑺𝑺𝐿𝐿,𝑝𝑝𝑝𝑝 0.745∠26.6°
𝑰𝑰𝐿𝐿,𝑝𝑝𝑝𝑝 = =
𝑽𝑽𝐿𝐿,𝑝𝑝𝑝𝑝 1∠0°
𝑰𝑰𝐿𝐿,𝑝𝑝𝑝𝑝 = 0.745∠ − 26.6° 𝑝𝑝. 𝑢𝑢. = 𝑰𝑰𝑠𝑠,𝑝𝑝𝑝𝑝
Δ-Δ
Y-Δ
Δ-Y
One-line diagram:
Phasor diagram:
Note nomenclature:
High-voltage terminals: H1, H2, H3
Low-voltage terminals: X1, X2, X3
Terminal labels serve as dots
High-voltage phases: A, B, C No phase shift through the
Low-voltage phases: a, b, c transformer
One-line diagram:
Phasor diagram:
For the Y-Δ or Δ-Y transformer, we must account for the phase shift
Per-unit includes a conceptual phase-shifting transformer
Voltage bases must be related by the effective turns ratio – must include
the 3 factor
Simplified Y-Δ per-unit circuit:
Δ connection advantages:
Third harmonic current confined to the core
Due to non-linear B-H characteristics of the core
Y connection advantages
Neutral point simplifies grounding
Reduced insulation requirement
𝚫𝚫-Y transformers
Most common type of transformers
Step-up/step-down with Y connection at high-voltage side to reduce insulation
requirements
Δ winding confines third harmonic currents
𝚫𝚫-𝚫𝚫 transformers
Attractive from repair/maintenance standpoint
Can remove one transformer and still deliver (reduced) 3𝜙𝜙 power
Y-Y transformers
Not commonly used due to problems with third harmonic currents
K. Webb ESE 470
Transformer Nameplate Ratings
83
Neighborhoods are
typically in the range of
7.2 kV, line-to-neutral
Pole-mounted
distribution transformers
step voltage down
Single phase 120/240 V
Pad-mounted or vault
(underground)
distribution transformers
are also common