0% found this document useful (0 votes)
135 views5 pages

Department of The Interior and Local Government Bureau of Fire Protection

This document is an inspection checklist from the Bureau of Fire Protection regarding an industrial occupancy. It provides general information about the property such as the owner, address, building details. It also contains checklists to evaluate the building's construction, classification, means of egress including exits, stairways and ramps, to ensure compliance with fire safety standards.

Uploaded by

Boy Clemente
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views5 pages

Department of The Interior and Local Government Bureau of Fire Protection

This document is an inspection checklist from the Bureau of Fire Protection regarding an industrial occupancy. It provides general information about the property such as the owner, address, building details. It also contains checklists to evaluate the building's construction, classification, means of egress including exits, stairways and ramps, to ensure compliance with fire safety standards.

Uploaded by

Boy Clemente
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Republic of the Philippines

Department of the Interior and Local Government


Bureau of Fire Protection
(Region)
(District/Province Office)
(Station)
(Station Address)
(Telephone No./Email Address)

____________________
(Name of Owner) DATE

(Name of Establishment)

(Address)

FOR : CITY/MUNICIPAL FIRE MARSHAL


ATTN : CHIEF, FIRE SAFETY ENFORCEMENT SECTION

REFERENCE: INSPECTION ORDER NO.______________________ DATE ISSUED___________________


DATE OF INSPECTION:____________________

NATURE OF INSPECT ION CONDUCTED: [ ] Check Appropriate Box


[ ] Building under Construction [ ] Periodic Inspection of Occupancy
[ ] Application for 0ccupancy Permit [ ] Verification Inspection of Compliance to NTCV
[ ] Application for Business Permit [ ] Verification Inspection of Complaint Received
[ ] Others (Specify) ___________________________________

INDUSTRIAL OCCUPANCY CHECKLIST

I. GENERAL INFORMATION
Name of Building __________________________________________________________________________________
Business Name____________________________________________________________________________________
Address _________________________________________________________________________________________
Nature of Business ________________________________________________________________________________
Name of Owner/Occupant____________________________________ Contact No. ____________________________
Name of Representative________________________________________ Contact No. _________________________
No. of Storey__________Height of B1dg. __________(m) Portion Occupied____________________________________
Area per floor _____________________________sqm Total Floor Area _____________________________sqm
Building Permit No ____________ Date Issue________ Occupancy Permit No._______ Date Issued ________________
Latest FSIC Issued Control No. ________________ Date Issued________________ FC Fee______________________
Certificate of Fire Drill ___________________Date Issued__________________ FC Fee_____________________
Latest Notice to Correct Violations Control No. _____________________________ Date Issued____________________
Name of Fire Insurance Co/Co-Insurer_________________ Policy No.____________ Date Issued_________________
Latest Mayor's/Bus. Permit __________ Date Issued________ Municipal License No._______ Date Issued___________
Latest Certificate of Electrical Inspection No. ___________________ Date Issued_______________________________
Other Information__________________________________________________________________________________

II.BUILDING CONSTRUCTION
Beams ________________________ Columns______________________ Flooring _____________________________
Exterior Walls___________________ Corridor Walls_________________Room Partitions _______________________
Main Stair______________________ Windows______________________Ceiling ______________________________
Main Door______________________ Trusses_________________________Roof _____________________________

III. SECTIONAL OCCUPANCY (Note: Indicate specific usage of each floor, section or rooms)

IV. CLASSIFICATION
Occupancy Classification: [ ] General Industrial [ ] Special Purpose Industrial [ ] Open Industrial
Occupant Load:___________________________ Egress Capacity __________________________________________
(Requirement: 9.3 m2/p)
Any renovations [ ] Yes [ ] No if Yes, specify _________________________________________________

BFP-QSF-FSED-014 Rev. 01 (07.05.19) Page 1 of 5


Republic of the Philippines
Department of the Interior and Local Government
Bureau of Fire Protection

V. EXIT DETAILS
Capacity of Horizontal Exit (Corridor Hallway):_____________ (Requirement: 100 persons per unit of exit width per min)
Capacity of Exit Stair: _______________________________ (Requirement: 60 persons per unit of exit width per min)
No. of Exits_____________________________________________________________ Remote [ ] Yes [ ] No
Minimum Requirement: No. of Exits: Two (2) units per floor
Location of Exit____________________________________________________________________________________
Maximum Travel Distance Requirement •from Farthest Room: 31 m without AFSS & 46 m with AFSS
Any Enclosure Provided? [ ] Yes[ ] No
Min of 2-hr fire rating- 4-storey or more, Min of 1 hr,
fire rung- less than 4-storey

MEANS OF EGRESS

Readily accessible [ ] Yes [ ] No Obstructed [ ] Yes [ ] No


Travel distance within limits [ ] Yes [ ] No Dead-ends within limits [ ] Yes [ ] No
Adequate illumination [ ] Yes [ ] No Proper rating of illumination [ ] Yes [ ] No
Panic hardware operational [ ] Yes [ ] No Door swing in the direction of exit [ ]Yes [ ] No
Doors open easily [ ] Yes [ ] No Self-closure operational [ ] Yes [ ] No
Bldg w/Mezzanine [ ] Yes [ ] No Mezzanine with proper exits [ ]Yes [ ]No
Corridors & aisles of sufficient size [ ] Yes [ ] No
A. VERTICAL EXITS
1.Main stairway: Width___________________________ Construction ___________________________________
Are there railings provided [ ] Yes [ ] No Made of __________________________________________________
Any enclosure provided [ ] Yes [ ] No Enclosure construction_________ Any opening [ ] Yes [ ] No
Fire door construction_________________________ Door equipped w/ Self-closing device [ ] Yes [ ] No
Door proper rating: [ ] Yes [ ] No Door provided w/ vision panel: [ ] Yes [ ] No If Yes, made of _______________________

Door swing in the direction of exit travel (when required) [ ] Yes [ ] No


Stairways Pressurized [ ] Yes [ ] No [ ] N/A If pressurized, what type or method ________________________________
Date Last Tested __________________________________________________________________________________
2. Secondary Stair/Fire Escape: Number______________________________ Width ___________________________
Construction__________________ Are there railings provided [ ] Yes [ ] No Made of ____________________________
Location: [ ] Interior [ ] Exterior Exits accessible [ ] Yes [ ] No
Any obstruction [ ] Yes [ ] No Termination/Discharge of Exits ____________________________________________
Any enclosure provided [ ] Yes [ ] No Enclosure construction____________________________________________
Any opening [ ] Yes [ ] No Opening protected [ ] Yes [ ] No
Are fire door provided [ ] Yes [ ] No Width_____________ Fire door construction___________________________
Door provided with vision panel [ ] Yes [ ] No If Yes. made of___________________________________________
Door equipped w/ Self-closing device [ ] Yes [ ] No Doors & enclosure proper rating [ ] Yes [ ] No
Doors open easily [ ] Yes [ ] No Self-closing device operable [ ] Yes [ ] No
Door equipped w/ panic hardware [ ] Yes [ ] No Operable [ ] Yes [ ] No
Door swing in the direction of exit travel [ ] Yes [ ] No Enclosure properly protected [ ] Yes [ ] No
Fire escape pressurized [ ] Yes [ ] No [ ] N/A If pressurized, what type or method________________________________
Date Last Tested___________________________________________________________________________________
B. HORIZONTAL EXITS
Width of door/s ________________ Construction___________________________ With vision panel [ ] Yes [ ] No
Door swing in the direction of egress travel [ ] Yes [ ] No With Self-closing device [ ] Yes [ ] No
Width of corridors or hall ways _________________________ Construction ________________________________
Corridor walls extended from slab to slab [ ] Yes [ ] No Properly illuminated [ ] Yes [ ] No
Exit readily visible [ ] Yes [ ] No Clear and unobstructed [ ] Yes [ ] No
Properly marked w/ illuminated exit sign [ ] Yes [ ] No With illuminated directional sign [ ] Yes [ ] No
Properly located [ ] Yes [ ] No
C. RAMPS
Provided [ ] Yes [ ] No Type: [ ] Interior [ ] Exterior Width_______________ class ____________________________
Railings provided [ ] Yes [ ] No Height from the floor ________________________________ (Requirement: 91 cm)
Any enclosure provided [ ] Yes [ ] No Construction ____________________________________________________
Are fire doors provided [ ] Yes [ ] No Width__________ Fire door construction _______________________________
Door equipped w/ Self-closing device [ ] Yes [ ] No Door with proper rating [ ] Yes [ ] No

Door provided w/ vision panel [ ] Yes [ ] No If Yes, made of ___________________________________________


Door swing in the direction of exit travel (when required) [ ] Yes [ ] No
Any obstruction ________________________ Termination/Discharge of exit _________________________________
D. AREA OF SAFE REFUGE
Provided [ ] Yes [ ] No Type: [ ] Interior [ ] Exterior Location__________________________________________
Any enclosure provided [ ] Yes [ ] No Construction _________________________________________________
Are fire door provided [ ] Yes [ ] No Width________________ Fire door construction _________________________
Door equipped w/ self-closing device [ ] Yes [ ] No Door with proper rating [ ] Yes [ ] No
Door provided w/ vision panel [ ] Yes [ ] No If Yes, made of ___________________________________
Door swing in the direction of exit travel [ ] Yes [ ] No

BFP-QSF-FSED-014 Rev. 01 (07.05.19) Page 2 of 5


Republic of the Philippines
Department of the Interior and Local Government
Bureau of Fire Protection

VI. LIGHTINGS & SIGNS


A. EMERGENCY LIGHTS
Automatic Emergency Lights Provided [ ] Yes [ ] No Source of Power [ ] AC/DC [ ] Others _____________________
No. of Units per Floor___________ Located at: Hallways _____________ Stairway Landings ___________________
Operational: [ ] Yes [ ] No Exit path properly illuminated [ ] Yes [ ] No
Tested Monthly: [ ] Yes [ ] No Minimum AEL Power Duration: at least one (1) hour
B. EXIT SIGNS
Exit Signs Illuminated [ ] Yes [ ] No Location __________________________________________________
Source of Power [ ] AC/DC [ ] Others Readily visible [ ] Yes [ ] No
Minimum Letter Size _______________________________________ Min. Requirement: Height of 11.5 cm & width of 19.0 mm
Exit Route Plan posted on: Lobby/Hallways [ ] Yes [ ] No Rooms [ ] Yes [ ] No
Directional Exit Signs [ ] Yes [ ] No Location ____________________________________________________
C. WARNING/SAFETY SIGNS
[ ]”No Smoking” [ ] “Dead End” [ ] Elevator Sign [ ] Keep Door Closed
Other, specify _____________________________________________________________________________________

VII. FEATURES OF FIRE PROTECTION


A. PROTECTION OF VERTICAL OPENINGS
Properly protected [ ] Yes [ ] No Atrium [ ] Yes [ ] No Fire Doors good condition [ ] Yes [ ] No
Elevator opening protected [ ] Yes [ ] No Pipe Chase opening protected [ ] Yes [ ] No
Aircon Ducts system with damper [ ] Yes [ ] No Dumb Waiter opening protected [ ] Yes [ ] No
Garbage Chute opening protected [ ] Yes [ ] No
Between Floor & Glass Curtain opening protected [ ] Yes [ ] No
Date Last Tested___________________________________________________________________________________

B. ALARM SYSTEM
Fire Alarm Provided [ ] Yes [ ] No Type: [ ] Manual [ ] Automatic Centralized [ ] Yes [ ] No
Location of Central Control __________________________________________________________________________
No. of Bells per Floor ___________________ Location_____________________________________________________
Coverage: [ ] Budding [ ] Air Handling Unit [ ] Portion Specify____________________ Monitored [ ] Yes [ ]No
Type of Initiation Device [ ] Smoke [ ] Heat [ ] Manual [ ] Water Flow [ ] Others____________________________
No. of Pull Stations per Floor ____________________________________ Max. Horizontal Distance Bet. Pull Stations: 61.0 m
Smoke Detectors [ ] Yes [ ] No No. of Units per Room___________________________ Integrated [ ] Yes [ ] No
Heat Detectors [ ] Yes [ ] No No. of Units per Room___________________________ Integrated [ ] Yes [ ] No
Power Source of Detectors [ ] AC/DC [ ] Others____________________Total Detectors per Floor_______________
Date Last Tested___________________________________________________________________________________

C. STANDPIPE SYSTEM
Type: [ ] Wet [ ] Dry Tank Capacity_________________ Location________________________________________
Siamese Intake Provided [ ] Yes [ ] No Location_______________________________________________
Size _____________ No. of Units _______________________ Accessible [ ] Yes [ ] No
Fire Hose Cabinets Provided [ ] Yes [ ] No With Complete accessories [ ] Yes [ ] No
Location _________________________________________________________________________________________
No. of Units per Floor_____________ Size of Hose__________________ Length of Hose ________________________
(Note: Min Required Size of Riser & Distribution Pipe: 2 1/2 inch and 1 1/2 inch in diameter, respectively)
Type of Nozzle _______________________ Date Last Tested_____________________________________________
Fire Lane Provided: [ ] Yes [ ] NoLocation of nearest Fire Hydrant ____________________________________

D. FIRST AID FIRE PROTECTION EQUIPMENT (PORTABLE FIRE EXTINGUISHERS)


Type__________________ Capacity ____________________________No. of Units_____________________________
With PS Mark [ ] Yes [ ] No With ISO Mark [ ] Yes [ ] No
Properly Maintained [ ] Yes [ ] No Conspicuously Located [ ] Yes [ ] No Accessible [ ] Yes [ ] No
Other Types provided, if any__________________________________________________________________________

E. AUTOMATIC FIRE SUPPRESSION SYSTEM (SPRINKLER SYSTEM)


Type of Extinguishing Agent Used____________ Jockey Pump Capacity___________ hp ____________GPM
Fire Pump Capacity: __________________ hp _____________GPM Tank Capacity________________ gallons
Maintaining Line Pressure ___________________ Farthest Sprinkler Head Pressure___________________________
Riser Size______________________ Type of Heads Installed____________________________________________
No. of Heads per Floor ___________________ Total_______________ Spacing of Heads _____________________
Location of Fire Department Connection ________________________________________________________________
Date Last Tested __________________________Conducted_______________________________________________
Plan Submitted ___________________________ Certificate of Installation ___________________________________
BFP AFSS Certificate payment under Section 13 B (5) and Fund Code No. D2531–151
F. FIREWALL
Building required with firewalls [ ] Yes [ ] No Provided [ ] Yes [ ] No
Any Opening [ ] Yes [ ] No

BFP-QSF-FSED-014 Rev. 01 (07.05.19) Page 3 of 5


Republic of the Philippines
Department of the Interior and Local Government
Bureau of Fire Protection

VIII. BUILDING SERVICE EQUIPMENT


A. Boiler Provided [ ] Yes [ ] No No. of Units provided_____________________________________________
Fuel: [ ] Diesel [ ] Kerosene [ ] Coal [ ] Bunker [ ] PG Capacity__________________________________________
Container: [ ] Above-ground [ ] Underground Location ____________________________________________________
LPG Installation Covered with Permit [ ] Yes [ ] NoFuel with Storage Permit: [ ] Yes [ ] No
B. Generator Set Provided [ ] Yes [ ] No [ ] Automatic [ ] Manual Fuel: [ ] Diesel [ ] Gasoline
Capacity ___________________ Location_________________________ Dikes/Bund wall Provided [ ] Yes [ ] No
Container: [ ] Above-ground [ ] Underground Dispensing System [ ] By pump [ ] By gravity
Output Capacity__________________ kva Mechanical Permit ____________ Date Issued________________
Fuel with Storage Permit [ ] Yes [ ] No Others (specify) __________________________________________
Automatic Transfer Switch Provided [ ] Yes [ ] No Time Interval_____ sec (Requirement: Max 10 secs)
C. Refuse (Garbage) Handling Facility: Provided [ ] Yes [ ] No
Enclosure provided [ ] Yes [ ] No Fire resistive [ ] Yes [ ] No
Fire protection provided [ ] Yes [ ] No Type__________________________________________________________
Frequency of collection/disposal___________ How collected ____________________________________________
D. Electrical System
Is there any electrical hazard [ ] Yes [ ] No Specify location___________________________________________
E. Mechanical System
Is there any mechanical hazard [ ] Yes [ ] No Specify location___________________________________________
No. of elevators provided____________________________________________________________________________
Fireman's elevator provided [ ] Yes [ ] No Fireman's key/switch provided [ ] Yes [ ] No
F.Other Building Service Systems
[ ] Water Treatment Facility [ ] Waste Water/Sewage Treatment Facility

IX. HAZARDOUS AREA


[ ] Kitchen [ ] Laundry [ ] Windowless Basement [ ] Storage Room [ ] Others__________________________
Separation Fire Rated [ ] Yes [ ] No Type of Fire Protection provided ____________________________________
No. of Units______________ Capacity__________________ Accessible [ ] Yes [ ] No
Fuel Used_______________ Where Stored ___________________ Covered by BFP Permit______________________
Chimney: Made of ___________________Spark Arrester____________ Smoke Hood____________________________
Presence of hazardous materials [ ] Yes [ ] No Properly stored and handled [ ] Yes [ ] No

Kinds Container Volume Location


1.___________________ _____________________ ____________________ ___________________
2.___________________ _____________________ ____________________ __________________
3.___________________ _____________________ ____________________ ___________________\

Storage Permit for Flammables/Combustibles Covered by BFP Permit ________________________________________


Clearance of Stocks From Ceiling _____________________________________________________________________
Minimum Ceiling Clearance: 1.0m for Flammable Liquids and 0.5m for Combustible Materials

X. OPERATING FEATURES
Fire Safety Program (Under the supervision of the Chief Local Fire Service)
Fire Brigade Organization [ ] Yes [ ] No
Fire Safety Seminar [ ] Yes [ ] No
Employees trained in emergency procedures [ ] Yes [ ] No
Fire/Evacuation Drill [ ] Yes [ ] No
1st______________________________________ 2nd _____________________________________________

BFP-QSF-FSED-014 Rev. 01 (07.05.19) Page 4 of 5


Republic of the Philippines
Department of the Interior and Local Government
Bureau of Fire Protection

XI. DEFECTS / DEFICIENCIES NOTED DURING INSPECTION (Attached pictures, sketch and others)
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________.

XII. RECOMMENDATIONS
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________.

ACKNOWLEDGED BY:

________________________________________ ____________________________________________
Signature Over Printed Name of Owner/ Fire Safety Inspector/s
Representative

Date & Time ____________________________ _____________________________________________


Team Leader

RECOMMEND ISSUANCE OF FSIC/NTC/NTCV:

____________________________________________
CHIEF, FIRE SAFETY ENFORCEMENT SECTION

APPROVED / DISAPPROVED:

______________________________________________
CITY / MUNICIPAL FIRE MARSHAL

PAALALA: “MAHIGPIT NA IPINAGBABAWAL NG PAMUNUAN NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG
MAGBENTA O MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”

“FIRE SAFETY IS OUR MAIN CONCERN”


DISTRIBUTION:
Original (Applicant/Owner’s Copy)
Duplicate (BO or BPLO, as the case may be)
Triplicate (BFP Copy)

BFP-QSF-FSED-014 Rev. 01 (07.05.19) Page 5 of 5

You might also like