How To Read The Chilled Water Schematic
How To Read The Chilled Water Schematic
The
symbols used are always similar, enough to recognise what they are, but always slightly
different. However, they will all show how the chilled and or condenser water system is
connected and distributed around a building. They will also show the main components
such as valves and pressure sensors etc. They should also show which floor the
component is located.
They usually will not display every Air handling unit and fan coil unit connected to the
system. Sometimes they will show the connection to the main AHU’s other times they will
refer you to a separate drawing to see this detail.
Additionally, remember schematic drawings will not show every bend or the exact route
through the building. They are simply a flat 2D representation of the system.
The schematics can be quite cramped and you’ll need to sometimes see through the
information to follow the system.
You can see the direction of flow in the pipe which is indicated by arrows.
The diameter of the pipe is sometimes listed next to the line.
Newer designs might show you the designed flow rate, velocity, pressure and
pipe diameter.
You’ll also often see letters around valves, this is just to identify what type of
fitting it is. For example, an IV stands for isolating valve.
The capitalised letters of “NC” will mean the valve is normally closed.
You’ll also see circles with numbers and letters inside, this is the unique ID for
the fitting, there should be a matching ID tag fixed to the physical fitting. You
can use this number to find the correct fitting and also lookup detail for it in the
log sheet such as size and type.
Dotted horizontal lines from one side to the other of the drawing mean there is a
floor there.
The arrow on the pump indicates the direction of flow.
So we’ll start with the chiller showing the condenser and evaporator, as well as the flow
and return lines coming in and out of this to join the rest of the system.
Then because we have a bypass line we’ll have some more isolating valves, this allows
the chiller to be cut off from the system but the bypass line can still be used. In newer
systems you will find a motorised control valve here which is connected to the Building
Management System and allows remote control.
We’ll usually find an almost identical setup on the condenser side so I’ll add that in.
Pump sets
Next we’ll need some pumps to push the water through the chiller and around the
building.
Pump set
For this we’ll usually have two or more pumps in parallel typically running in duty and
standby. Again the triangle points in the direction of flow.
We know the pumps need to push water through the chiller, so we can connect the pump
sets to the chillers evaporator inlets.
Chilled water is generated in the evaporator so we’ll need to connect that back around to
the pumps to create a circuit and distribute the chilled water.
Coming off the common header is another header, this allows the flow to be split and
each will receive equal distribution. On the outlets of the header you might find a
commissioning station or double regulating valve but in newer systems this is likely on
the return line.
From the header outlets we’ll have some more pumps to distribute the chilled water to
different parts of the building, for example the east and west side. Some designs won’t
have separate pumps for different parts of the building, they will simply have one pump
set which forces the chilled water around the entire building.
Secondary circuit pumps
These pumps will distribute the water off to the AHU’s and FCU’s, I explained about when
this detail is/isn’t shown earlier in the article but I’ll just briefly give you some examples
of Air Handling Unit connections and also some Fan coil units.
AHU
schematic
You’ll also find a pressurisation unit on the chilled water side as this is a closed system,
typically this is connected on the return line to the main circulating pumps as this area is
not affected by the pump. This unit just maintains a certain pressure in the system.
Condenser Water
Now for the condenser water side. Remember air cooled chillers do not require a
condenser system. We will need a set of pumps to push the water through the chiller
and around the system so we can drop those in.
Condenser water circuit
Then connect those pumps to the condenser inlets and another line out of the condenser
and up to the cooling towers, located on the roof.
Cooling Towers
The cooling towers are connected to the riser via a header. These connections will need
isolating valves and flexible connectors. Not all towers will use two inlets, some will have
just one.
Cooling tower
schematic
Another common version of the cooling tower you might come across will look something
like this. It has the flow and return lines for the condenser water. There is also a
balancing line between other cooling towers, they have a make-up line which tops up the
water in the water if it gets too low and there will also be an overflow and drain line.
Some have a flushing line between the flow and return lines for system cleaning. If you
want to know how cooling towers work we’ve covered this in a previous video, click
here to see.