Topic - 4A-Overcurrent Protection
Topic - 4A-Overcurrent Protection
│ Topic 4A │
Overcurrent protection
© VTC 2015 1
CONTENT
1. Introduction
2. Types of Overcurrent
3. Overcurrent Protective Devices
4.Overload Protective Devices
5. Fault Current
6. Determination of Short –circuit Current
7. Position of Overload Protective Device
8. Omission of Overload Protective Deivce
2
9. Discrimination
10. Back-up Protection
11. IDMT Relay
12. Per Unit System
3
1. Introduction
Purpose of overcurrent protection
For the prevention of electric shock
and fire hazards, and
maintain the life of equipment and
systems
• Overcurrent
• Any current in excess of the rated
current of a circuit or the current
carrying capacity of a conductor
4
2. Type of Overcurrent
(a) Overload Current (過載電流)
The current exceeds the design current caused by
connecting excessive loads to the circuit
(Normally less than 3 time the design current)
5
2. Type of Overcurrent
電 負
源 載
極低電阻的連接
6
2. Type of Overcurrent
7
3. Overcurrent Protective Devices
Requirements:
be operated automatically
have adequate breaking capacity and making
capacity
be suitably located
be constructed so as to prevent danger from
overheating, arcing or the scattering of hot
particles when they come into operation and
to permit ready restoration of the supply
without danger
(操作時防止過熱、產生電弧或熱碎片散播而發
生危險,及容許在無危險情況下恢復供電。)
8
3. Overcurrent Protective Devices
Types of Overcurrent Protective Devices
(a) Miniature Circuit Breaker (MCB)
(b) Moulded Case Circuit Breaker (MCCB)
(c) High Breaking Capacity Fuses (HBC/HRC) and Semi-
enclose fuse
(d) Circuit breakers incorporating overcurrent release
in the form of integral tripping device, or external
overcurrent relays (e.g. ACB + IDMTL relay)
(e) Circuit breakers in conjunction with fuses
(f) Protection for neutral conductor
9
3. Overcurrent Protective Devices
(a) Miniature Circuit Breakers (MCB) 微型斷路器
Acceptable standard: BSEN 60898 / IEC 60898
Isolation, switching and overcurrent protection for final
circuits
Two tripping mechanism:
overload trip by thermal mechanism
short-circuit trip by magnetic mechanism
Nominal current rating: up to 100A
Single/double/triple-pole arrangement
Breaking capacity:
MCB to BS3871: M1 to M9 (i.e. 1kA to 9kA)
MCB to BSEN / IEC 60898: 1500 to 25000A
10
3. Overcurrent Protective Devices
MCB Construction
11
3. Overcurrent Protective Devices
Miniature Circuit Breaker (MCB)
12
3. Overcurrent Protective Devices
Miniature Circuit Breaker (MCB)
(4) Terminals
(5) Bimetallic strip
(6) Calibration screw –
allows the manufacturer
to precisely adjust the trip
current of the device after
assembly.
(7) Solenoid
(8) Arc divider / extinguisher
13
3. Overcurrent Protective Devices
MCB
14
3. Overcurrent Protective Devices
Types of MCB
MCB is also classified into the following different types
according to the instantaneous tripping current:
MCB to BS 3871- Types 1,2, 3 and 4
MCB to BSEN 60898 – Types B, C and D
(Note: MCB to BS3871 has been replaced by MCB to
BSEN 60898)
15
3. Overcurrent Protective Devices
Type Tripping Applications
current
Type B 3-5 In Normal resistive loads, e.g. Low voltage
lighting
Type C 5-10 In Inductive load, e.g. Industrial application
motors
Type D 10-20 In Load with higher starting current, e.g.
Compressor Motor, X ray, welding M/C
etc.
16
3. Overcurrent Protective Devices
17
3. Overcurrent Protective Devices
(b) Moulded Case Circuit Breakers (MCCB)
模製外殼斷路器
18
3. Overcurrent Protective Devices
Moulded Case Circuit Breakers
19
3. Overcurrent Protective Devices
(c) High Breaking Capacity Fuses (HBC/HRC)
高斷流容量熔斷器
20
3. Overcurrent Protective Devices
High Breaking Capacity Fuses (HBC/HRC)
Acceptable standard: BS88, BS1361 and BS1362
Available ratings:
BS88: 2 to 1250A
BS1361: 5 – 100A
BS1362: 2 - 13A
Breaking capacity:
BS88: 80kA
BS1361: 16.5 – 33kA
BS1362: 6kA Cartridge Fuse to BS88
21
3. Overcurrent Protective Devices
Semi-enclosed Fuse (BS3036) 半封閉式熔斷器
Acceptable standard: BS 3036
Made of tinned copper wire with nominal diameter proportional
to its rating.
Subject to deterioration due to oxidation and scaling, resulting
in a reduction of its current carrying capacity
Incorrect rated fuse element may be used for replacement by
unskilled person
Low breaking capacity
22
3. Overcurrent Protective Devices
Devices for Overcurrent Protection
Semi-enclosed Fuse 半封閉式熔斷器(BS3036)
23
3. Overcurrent Protective Devices
24
3. Overcurrent Protective Devices
Fuse
25
3. Overcurrent Protective Devices
Advantages of MCB over fuse in circuit protection
26
3. Overcurrent Protective Devices
(f) Protection for neutral conductor
Overcurrent detection of the NEUTRAL conductor is
NOT required for installation of a TT and TN systems if
100% Neutral conductor is used; or
protection already provided by protective device
for phase conductors of the circuit
Note that no fuse, circuit breaker, isolator or switch,
other than a linked circuit breaker, linked isolator or
linked switch should be inserted in a neutral conductor
as LOSS OF NEUTRAL must be avoided to eliminate the
risk of raising the potential of the load star point to
dangerous level
27
4. Overload protective devices
(a) Overload protective devices should be capable of breaking
any overload current flowing in the circuit conductors
before such a current could cause a temperature rise
detrimental to insulation, joints, terminations, or
surroundings of the conductors.
Condition 1:
The current setting (In) of the devices should not be less
than the design current (Ib) of the circuit
The In should not exceed the as-installed current carrying
capacities (Iz) (CCC of a cable for continuous service under the particular
installation conditions concerned) of any of the conductors in the
circuit
28
4. Overload protective devices
Condition 2:
The current causing effective operation of the
devices (I2) should not exceed 1.45 times the as-
installed current carrying capacities of any of the
conductors in the circuit (Iz) .
I2 1.45 x IZ
An Effective Overload Protection Device should Meet
Requirements of Both Conditions 1 & 2:
(i) Ib In Iz
(ii) I2 1.45 x IZ
(note: I1 = non-trip current=1.25 In)
29
4. Overload protective devices
Example:
Determine whether a 15A MCB is suitable to be used as the
overload protective device of a 220V single phase circuit wired by
1.5 mm2 PVC 2/C cu. cable supplying a 3kW water heater using
surface wiring at an ambient temperature of 300C? Assuming that:
As-installed CCC of the copper cable (Iz) = 20A
The effective operation current of the MCB (I2) = 1.6 x In
Solution:
Ib = 3000W/220V = 13.7A; In = 15A; Iz = 20A
Ib In Iz (Ref. to EIH Table 6.1, BS88 Fuse 1.6, BS1361 1.5)
30
4. Overload protective devices
(b). Fault Current Protected by Overload Protective
Device
The protective device is assumed to be adequate if it
(1) satisfies conditions for overload protective
device. That is, we sizes cable and protective
device by using the principle
(i) Ib ≤ In ≤ Iz
(ii) I2 ≤ 1.45 Iz and
(2) Breaking capacity of protective device Icu ≥
Maximum prospective fault current, Isc
(iii) Icu ≥ Isc
This is the most common way to protect a circuit,
since only ONE protective device is needed.
31
4. Overload protective devices
32
5. Fault current protective device
33
5. Fault current protective device
k2 S2
t
I2
I tk S
2 2 2
where
k is cable factor (value of k may refer to the next slide)
t is the duration in seconds,
S is the nominal cross-sectional area of conductor in mm2
I is the value of fault current in amperes
34
5. Fault current protective device
35
6. Determination of short-circuit current
It is important to determine the maximum prospective
short-circuit current at various location of the wiring
installation, and hence to select fault current
protection devices with suitable breaking capacities.
Methods
(a) by calculation
(b) by measurement
(c) by taking the reference information from COP
36
6. Determination of Short-circuit Current
(a) By Calculation
(i) Maximum Prospective Fault Current
3-phase : calculation based on symmetrical fault impedance
generally
1-phase : calculation based on line-neutral impedance at 20oC
generally
Breaking capacity of overcurrent protection devices should
exceed the max. prospective fault current
breaking capacity > max Isc
(ii) Minimum Prospective Fault Current
Calculation based on line-neutral impedance values generally
Significant in calculation regarding fault disconnection time
and withstanding capacity of cables.
k2S2 > I2t (熱容忍量 >通泄能量)
37
6. Determination of Short-circuit Current
(a) Location of Max and Min short-circuit current
38
6. Determination of Short-circuit Current
1-phase circuit
Vp
I sc
Z p Zn
Vp
Z p Zn
I sc
39
6. Determination of Short-circuit Current
6(a)(i) Calculation of max prospective short circuit current
The max. prospective 3-ph symmetrical short-circuit at the LV
source of supply provided by local electricity suppliers is 40kA
All Main Incoming Circuit Breaker (MICB) should therefore have
a breaking capacity not less than 40kA
Fault current protective devices with smaller breaking
capacities are generally acceptable if they are backed up by
BS88 Part 2 and 6 fuses. (Table 9(2) & (3) of COP)
The further away from the source of supply, the smaller the
maximum prospective short circuit current.
(Maximum prospective short circuit current is for estimation the
breaking capacity of the protective device)
40
6. Determination of Short-circuit Current
41
6. Determination of Short-circuit Current
6(a)(ii) Calculation of min. prospective short circuit
current ,Iq
3-phase symmetrical
Fault
Vp
I
Z p Z1
VL
I
2( Z p Z1 )
42
6. Determination of Short-circuit Current
6(a)(ii) Calculation of min. prospective short circuit current
Vp
I
Z p Z1 Z n1 Z n
43
6. Determination of Short-circuit Current
44
6. Determination of Short-circuit Current
(a)(iii) Example 1:
Zn Z2
45
6. Determination of Short-circuit Current
Example 1(cont)
The total impedance from the fuse to the remote load end,
Z1 + Z2 = 2 x 87m x 1.68 Ω/km = 0.292 Ω
47
6. Determination of Short-circuit Current
(a)(iii) Example 2:
48
6. Determination of Short-circuit Current
Example 2: (cont.)
49
6. Determination of Short-circuit Current
Example 3 (cont.)
50
6. Determination of Short-circuit Current
Example 3 (cont.)
51
6. Determination of short-circuit current
(b) By measurement
52
6. Determination of Short-circuit Current
6. (b) By Measurement
53
6. Determination of short-circuit current
(c) Approximate Prospective Fault Current from
COP
54
6. Determination of Short-circuit Current
(c) By CoP
Choice of breaking capacity of protective device
55
7. Position of Overload Protective Device
At or along the conductor where there is a reduction of CCC
Iz such due to the change:
csa of conductor,
method of installation, cable type,
in environmental condition
56
7. Position of Fault Current Protective Device
57
8. Omission of Overload Protective Device
58
8. Omission of Overload Protective Device
59
8. Omission of Overload Protective Device
For cases of “d” to “f” overcurrent protective devices are
not required
60
8. Omission of Overload Protective Device
61
8. Omission of Overload Protective Device
62
9. Discrimination (區分性)
In the occurrence of a fault in
the circuit, only the
protective device directly
before the fault will operate
and that other branch circuits
of the same or higher level
will not be affected.
OPENS
Analysis usually divided in 2
cases: NOT AFFECTED
Overload UNNECESSARY
POWER LOSS Fault
Short-circuit
63
Safe Time Margin(Grading Margin)
64
9. Discrimination (區分性)
65
9. Discrimination (區分性)
66
9. Discrimination (區分性)
67
9. Discrimination (區分性)
68
9. Discrimination (區分性)
(c) Short-circuit discrimination between CBs
(cont’d)
Chronometric selectivity
by delaying the action of
the short time release of
the major breaker to allow
the minor breaker to
interrupt the short-circuit
current during the short
delay time.
Suitable for upstream and
downstream having very
close prospective fault
currents
69
9. Discrimination (區分性)
Short-circuit Short-circuit
discrimination between CB discrimination between
and sub-ordinate fuses fuses and sub-ordinate CB
70
10. Back-up protection
A protective device with lower breaking capacity is permitted
provided the major protective device (on the supply side) has
the necessary interrupting capacity. The characteristics of
the devices should be coordinated so that the energy let-
through of these devices will not cause damage to the load
side device and the conductors protected by these devices
Table 9(2) of COP shows the minimum breaking capacities for
general guidance.
71
10. Backup Protection
Same device for providing overload and fault
current protection
Overload protective device and overcurrent
protective device may be the same device or
separate devices provided that the device can
satisfy both the requirements of overload
protective devices and fault current protective
devices.
72
10. Back-up protection
73