Lubricants in Refrigerant Systems: Tests For Boundary Lubrication
Lubricants in Refrigerant Systems: Tests For Boundary Lubrication
gear-driven centrifugal compressors in which the dilution of the imparted momentum is converted into a pressure rise. Centrifugal
lubricant by a refrigerant is expected to be quite low. compressors function based on these principles.
However, because all these machines operate in air, available Refrigerant compressors require the lubricant to do more than
data may not apply to a refrigerant environment. Divers (1958) simply lubricate bearings and mechanism elements. Oil delivered to
questioned the validity of tests in air because several of the oils the mechanism serves as a barrier that separates the gas on the dis-
that performed poorly in Falex testing have been used successfully charge side from the gas on the suction sides. Oil also acts as a cool-
in refrigerant systems. Murray et al. (1956) suggest that halocar- ant, transferring heat from the bearings and mechanism elements to
bon refrigerants can aid in boundary lubrication. Refrigerant 12, the crankcase sump, which, in turn, transfers heat to the surround-
for example, when run hot in the absence of oil, reacted with steel ings. Moreover, oil helps reduce noise generated by moving parts
surfaces to form a lubricating film. These studies emphasize the inside the compressor. Generally, the higher the viscosity of the
need for laboratory testing in a simulated refrigerant environment. lubricant, the better the sealing and noise reduction capabilities.
In Huttenlocher’s (1969) method of simulation, refrigerant vapor A hermetic system, in which the motor is exposed to the lubri-
is bubbled through the lubricant reservoir before the test to displace cant, requires a lubricant with electrical insulating properties. The
the dissolved air. The refrigerant is bubbled continually during the refrigerant gas normally carries some lubricant with it as it flows
test to maintain a blanket of refrigerant on the lubricant surface. through the condenser, flow-control device, and evaporator. This
Using the Falex tester, Huttenlocher showed the beneficial effect of lubricant must return to the compressor in a reasonable time and
R-22 on the load carrying capability of the same lubricant compared must have adequate fluidity at low temperatures. The lubricant must
with air or nitrogen. Sanvordenker and Gram (1974) describe a fur- also be free of suspended matter or components such as wax that
ther modification of the Falex test using a sealed sample system. might clog the flow control device or deposit in the evaporator and
Both R-12 (a CFC) and R-22 (an HCFC) atmospheres had adversely affect heat transfer. In a hermetic system, the lubricant is
beneficial effects on a lubricant’s boundary lubrication character- charged only once, so it must function for the lifetime of the com-
istics when compared with tests in air. HFC refrigerants, which pressor. The chemical stability required of the lubricant in the pres-
are chlorine-free, provide beneficial effects to boundary lubrica- ence of refrigerants, metals, motor insulation, and extraneous
tion when compared to tests conducted in air. However, they con- contaminants is perhaps the most important characteristic distin-
tribute to increased wear as compared to a chlorinated refrigerant guishing refrigeration lubricants from those used for all other appli-
with the same lubricant. cations (see Chapter 5).
Komatsuzaki and Homma (1991) used a modified four-ball tester Although the compression components of centrifugal compres-
to determine the antiseizure and antiwear properties of R-12 and sors require no internal lubrication, rotating shaft bearings, seals,
R-22 in mineral oil and R-134a in a propylene glycol. and couplings must be adequately lubricated. Turbine or other types
Test parameters must simulate as closely as possible the system of lubricants can be used when the lubricant is not in contact or cir-
conditions (the base material from which the test specimens are culated with the refrigerant.
made, their surface condition, the processing methods, and the oper- As expected, an ideal lubricant does not exist; a compromise
ating temperature). There are several bearings or rubbing surfaces in must be made to balance the requirements. A high-viscosity lubri-
a refrigerant compressor, each of which may use different materials cant seals the gas pressure best, but may offer more frictional resis-
and may operate under different conditions. A different test may be tance. Slight foaming can reduce noise, but excessive foaming can
required for each bearing. Moreover, bearings in hermetic compres- carry too much lubricant into the cylinder and cause structural dam-
sors have very small clearances. Permissible bearing wear is mini- age. Lubricants that are most stable chemically are not necessarily
mal because wear debris remains in the system and can cause other good lubricants. The lubricant should not be considered alone,
problems even if the clearances stay within working limits. Com- because it functions as a lubricant-refrigerant mixture.
pressor system mechanics must be understood to perform and inter- The precise relationship between composition and performance
pret simulated tests. is not well defined. Standard ASTM bench tests can provide
Some aspects of compressor lubrication are not suitable for lab- such information as (1) viscosity, (2) viscosity index, (3) color,
oratory simulation. One aspect, the return of liquid refrigerant to the (4) specific gravity, (5) refractive index, (6) pour point, (7) aniline
compressor, can cause the lubricant to dilute or wash away from the point, (8) oxidation resistance, (9) dielectric breakdown voltage,
bearings, creating conditions of boundary lubrication. Tests using (10) foaming tendency in air, (11) moisture content, (12) wax sep-
operating refrigerant compressors have also been considered, and aration, and (13) volatility. Other properties, particularly those
one such wear test has been proposed as a German Standard (DIN involving interactions with a refrigerant, must be determined by
8978). The test is functional for a given compressor system and may special tests described in the refrigeration literature. Among these
permit comparison of lubricants within that class of compressors. nonstandard properties are (1) mutual solubility with various refrig-
However, it is not designed to be a generalized test for the boundary erants, (2) chemical stability in the presence of refrigerants and met-
lubricating capability of a lubricant. Other tests using radioactive als, (3) chemical effects of contaminants or additives that may be in
tracers in refrigerant systems have given useful results (Rembold the oils, (4) boundary film-forming ability, (5) solubility of air, and
and Lo 1966). (6) viscosity, vapor pressure, and density of oil-refrigerant mixtures.
such as sulfur, nitrogen, or oxygen in addition to carbon and flocs in certain refrigerant solutions (see the section on Wax Sepa-
hydrogen. ration). The branched chain paraffins and naphthenes are less vis-
The preceding structural components do not necessarily exist in cous at low temperatures and have extremely low pour points.
pure states. In fact, a paraffinic chain frequently is attached to a naph- Nonhydrocarbons are mostly removed during the refining of
thenic or aromatic structure. Similarly, a naphthenic ring to which a refrigeration oils. Those that remain are expected to have little effect
paraffinic chain is attached may in turn be attached to an aromatic on the physical properties of the lubricant, except, perhaps, on its
molecule. Because of such complications, mineral oil composition color, stability, and lubricity. Because not all the nonhydrocarbons
is usually described by carbon type and molecular analysis. (e.g., sulfur compounds) are dark, even a colorless lubricant does
In carbon type analysis, the number of carbon atoms on the par- not necessarily guarantee the absence of nonhydrocarbons. Kartz-
affinic chains, naphthenic structures, and aromatic rings is deter- mark et al. (1967) and Mills and Melchoire (1967) found indications
mined and represented as a percentage of the total. Thus, % CP, the that nitrogen-bearing compounds cause or act as catalysts toward
percentage of carbon atoms having a paraffinic configuration, the deterioration of oils. The sulfur and oxygen compounds are
includes not only the free paraffins but also those paraffinic chains thought to be less reactive, with some types considered to be natural
attached to naphthenic or to aromatic rings. inhibitors and lubricity enhancers.
Similarly, % CN includes the carbon atoms on the free naphthenes Solvent refining, hydrofinishing, or acid treatment followed by
as well as those on the naphthenic rings attached to the aromatic a separation of the acid tar formed are often used to remove more
rings, and % CA represents the carbon atoms on the aromatic rings. thermally unstable aromatic and unsaturated compounds from the
Carbon analysis describes a lubricant in its fundamental structure base stock. These methods also produce refrigeration oils that are
and correlates and predicts many physical properties of the lubricant. free from carcinogenic materials sometimes found in crude oil
However, direct methods of determining carbon composition are stocks.
laborious. Therefore, common practice uses a correlative method, The properties of the components naturally are reflected in the
such as the one based on the refractive index-density-relative molec- parent oil. An oil with a very high saturate content, as is frequently
ular mass (n-d-m) (Van Nes and Weston 1951) or one standardized the case with paraffinic oils, also has a high viscosity index, low spe-
by ASTM D2140 or ASTM D3288. Other methods are ASTM cific gravity, high relative molecular mass, low refractive index, and
D2008, which uses ultraviolet absorbency and a rapid method using low volatility. In addition, it would have a high aniline point and
infrared spectrophotometry and calibration from known oils. would be less miscible with polar refrigerants. The reverse is true of
Molecular analysis is based on methods of separating the struc- naphthenic oils. Table 1 lists typical properties of several mineral-
tural molecules. For refrigeration oils, important structural mole- based refrigeration oils.
cules are (1) saturates or nonaromatics, (2) aromatics, and (3)
nonhydrocarbons. All the free paraffins and naphthenes (cyclopar- SYNTHETIC LUBRICANTS
affins), as well as mixed molecules of paraffins and naphthenes are The limited solubility of mineral oils with R-22 and R-502 orig-
included in the saturates. However, any paraffinic and naphthenic inally led to the investigation of synthetic lubricants for refrigera-
molecules attached to an aromatic ring are classified as aromatics. tion use. In more recent times, the lack of solubility of mineral oils
This representation of lubricant composition is less fundamental in nonchlorinated fluorocarbon refrigerants, such as R-134a and
than carbon analysis. However, many properties of the lubricant rel- R-32, has led to the commercial use of some synthetic lubricants.
evant to refrigeration can be explained with this analysis, and the Gunderson and Hart (1962) describe a number of commercially
chromatographic methods of analysis are fairly simple (ASTM available synthetic lubricants such as synthetic paraffins, polygly-
D2549; ASTM D2007; Mosle and Wolf 1963; Sanvordenker 1968). cols, dibasic acid esters, neopentyl esters, silicones, silicate esters,
The traditional classification of oils as paraffinic or naphthenic and fluorinated compounds. Many have properties suited to refrig-
refers to the amount of paraffinic or naphthenic molecules in the eration purposes. Sanvordenker and Larime (1972) describe the
refined lubricant. Paraffinic crudes contain a higher proportion of properties of these synthetic lubricants, alkylbenzenes, and phos-
paraffin wax, and thus have a higher viscosity index and pour point phate esters in regard to refrigeration applications using chlorinated
than to naphthenic crudes. fluorocarbon refrigerants. The phosphate esters are unsuitable for
refrigeration use because of their poor thermal stability. Although
COMPONENT CHARACTERISTICS very stable and compatible with refrigerants, the fluorocarbon lubri-
Saturates have excellent chemical stability, but poor solubility cants are expensive. Among others, only the synthetic paraffins
with polar refrigerants, such as R-22; they are also poor boundary have poor miscibility relations with R-22. Dibasic acid esters, neo-
lubricants. Aromatics are somewhat more reactive but have very pentyl esters, silicate esters, and polyglycols all have excellent vis-
good solubility with refrigerants and good boundary lubricating cosity temperature relations and remain miscible with R-22 and
properties. Nonhydrocarbons are the most reactive but are benefi- R-502 to very low temperatures. At this time, the three synthetic
cial for boundary lubrication, although the amounts needed for that lubricants seeing the greatest use are alkylbenzene, for R-22 and
purpose are small. The reactivity, solubility, and boundary lubricat- R-502 service, and polyglycols and polyol esters, for use with
ing properties of a refrigeration lubricant are affected by the relative R-134a and refrigerant blends using R-32.
amounts of these components in the lubricant. There are two basic types of alkylbenzenes: branched and linear.
The saturate and aromatic fractions separated from a lubricant do The products are synthesized by reacting an olefin or chlorinated
not have the same viscosity as the parent lubricant. The saturate paraffin with benzene in the presence of a catalyst. Catalysts com-
fraction is much less viscous, and the aromatic fraction is much monly used for this reaction are aluminum chloride and hydrofluo-
more viscous than the parent lubricant. Both fractions have the same ric acid. After the catalyst is removed, the product is distilled into
boiling range. Thus, for this range, the aromatics are more viscous fractions. The relative size of these fractions can be changed by
than the saturates. For the same viscosity, the aromatics have a adjusting the relative molecular mass of the side chain (olefin or
higher volatility than the saturates. Also, the saturate fraction has a chlorinated paraffin) and by changing other variables. The quality of
lower density and a lower refractive index, but a higher viscosity alkylbenzene refrigeration lubricant varies, depending on the type
index and molecular mass than the aromatic fraction of the same (branched or linear) and manufacturing scheme. In addition to good
lubricant. solubility with refrigerants, such as R-22 and R-502, these lubri-
Among the saturates, the straight chain paraffins are undesirable cants have better high-temperature and oxidation stability than min-
for refrigeration applications because they precipitate as wax crys- eral oil-based refrigeration oils. Typical properties for a branched
tals when the lubricant is cooled to its pour point and tend to form alkylbenzene are shown in Table 1.
7.4 2002 ASHRAE Refrigeration Handbook (SI)
Fig. 1 Viscosity-Temperature Chart for 108 HVI and LVI Fig. 2 Variation of Refrigeration Lubricant Density
Lubricants with Temperature
Table 5 Absorption of Low Solubility Refrigerant Gases in Oil The vapor pressure of a lubricant-refrigerant solution is markedly
Ammoniaa (Percent by Mass)
lower than that of the pure refrigerant. Consequently, the evaporator
temperature is higher than if the refrigerant is pure. Another result
Absolute Temperature, °C is what is sometimes called the flooded start-up. When the crank-
Pressure, kPa 0 20 65 100 140 case and the evaporator are at about the same temperature, the fluid
98 0.246 0.180 0.105 0.072 0.054 in the evaporator (which is mostly refrigerant) has a higher vapor
196 0.500 0.360 0.198 0.144 0.108 pressure than the fluid in the crankcase (which is mostly lubricant).
294 0.800 0.540 0.304 0.228 0.166 This difference in vapor pressures drives the refrigerant to the
393 — 0.720 0.398 0.300 0.222
crankcase and it is absorbed in the lubricant until the pressures are
equalized. At times, the moving parts in the crankcase may be com-
979 — — 1.050 0.720 0.545 pletely immersed in this lubricant-refrigerant solution. At start-up,
Carbon Dioxideb (Percent by Mass) the change in pressure and turbulence can cause excessive amounts
Absolute Temperature, °C of liquid to enter the cylinders, causing damage to the valves and
Pressure, kPa 0 20 65 100 starving the crankcase of lubricant. The use of crankcase heaters to
101 0.26 0.19 0.13 0.10 prevent such problems caused by highly soluble refrigerants is dis-
aType of oil: Not given (Steinle 1950)
cussed in Chapter 2 and by Neubauer (1958). The problems associ-
bType of oil: HVI oil, 34.8 mm2/s at 38°C (Baldwin and Daniel 1953) ated with rapid outgassing from the lubricant are more pronounced
with synthetic oils than with mineral oils. Synthetic oils release
absorbed refrigerant more quickly and have a lower surface tension,
However, operating pressures in CO2 systems tend to be much which results in a lack of stable foam found with mineral oils (Swal-
higher (not shown in Table 5), and in that case, the quantity of gas low et al. 1995).
dissolved in the lubricant may be enough to substantially reduce
viscosity. At 2.7 MPa, for example, Beerbower and Greene (1961) Density
observed a 69% reduction when a 32 mm2/s lubricant (HVI) was
When estimating the density of a lubricant-refrigerant solution,
tested under CO2 pressure at 27°C.
the solution is assumed ideal so that the specific volumes of the
components are additive. The formula for calculating the ideal den-
LUBRICANT-REFRIGERANT SOLUTIONS sity (ρid ) is
Many chlorinated refrigerants are highly soluble in oils at any
temperature likely to be encountered. The only limit to the amount ρo
of these refrigerants that the lubricant can dissolve is established by ρ id Z -------------------------------------------- (2)
1 H W ( ρo ⁄ ρR Ó 1 )
the refrigerant pressure at a given temperature. Chlorinated refrig-
erants such as R-22 and R-114 may show limited solubilities with
some lubricants at evaporator temperatures (exhibited in the form of where
phase separation) and unlimited solubilities in the higher tempera- ρo = density of pure lubricant at the solution temperature
ture regions of a refrigerant system. In some systems using HFC ρR = density of refrigerant liquid at the solution temperature
refrigerants, a second, distinct two-phase region may occur at high W = mass fraction of refrigerant in solution
temperatures. For such refrigerants, solubility studies must there- Depending on the refrigerant, the actual density of a lubricant-
fore be carried out over an extended temperature range. refrigerant solution may deviate from the ideal by as much as 8%.
Because halogenated refrigerants have such high solubilities, the The solutions are usually more dense than calculated, but some-
lubricating fluid can no longer be treated as a pure lubricant, but times they are less. For example, R-11 forms ideal solutions with
rather as a lubricant-refrigerant solution whose properties are mark- oils, whereas R-12 and R-22 show significant deviations. Density
edly different from those of pure lubricant. The amount of refriger- correction factors for R-12 and R-22 solutions are depicted in Fig-
ant dissolved in a lubricant depends on the pressure and ure 3. The corrected densities can be obtained from the relation
temperature. Therefore, the composition of the lubricating fluid is
different in different sections of a refrigeration system operating at ρ id
steady state and changes from the time of start-up until the system Mixture Density Z ρ m Z ------- (3)
attains the steady state. The most pronounced effect is on viscosity. A
The crankcase of a compressor can be used as an example. For
where A is the density correction factor read from Figure 3 at the
this case, the refrigerant and lubricant are assumed to be in equilib-
desired temperature and refrigerant concentration.
rium and the viscosity is as shown in Figure 37. If the lubricant in
the crankcase at start-up is 24°C, the viscosity of pure 32 ISO VG Van Gaalen et al. (1990, 1991a, 1991b) provide values of density
branched acid polyol ester is about 60 mm2/s. Under operating for four refrigerant/lubricant pairs: R-22/mineral oil, R-22/ alkyl-
conditions, the lubricant in the crankcase is typically about 52°C. At benzene, R-502/mineral oil, and R-502/alkylbenzene. Figures 4, 5,
this temperature the viscosity of the pure lubricant is about 6, and 7 provide data on the variation of density with temperature for
20 mm2/s. If R-134a is the refrigerant and the pressure in the crank- R-134a in combination with a 32 ISO VG polyol ester, a 100 ISO
case is 352 kPa, the viscosity of the lubricant-refrigerant mixture at VG polyol ester, a 32 ISO VG polyalkylene glycol, and an 80 ISO
start-up is about 10 mm2/s and decreases to 9 mm2/s at 52°C. VG polyalkylene glycol, respectively (Cavestri 1993).
Hence, if only lubricant properties are considered, an erroneous Cavestri (1993) provides density data as a function of tempera-
picture of the system is obtained. As another example, when the ture and pressure for R-134A/polyol ester oils as shown in Figures
lubricant returns from the evaporator to the compressor, the highest 4 through 7. Additionally, Cavestri and Schafer (2000) provide den-
viscosity does not occur at the lowest temperature, because the sity data as a function of temperature and pressure R-410A/ polyol
lubricant contains a large amount of dissolved refrigerant. As the ester oils as shown in Figures 8 through 11.
temperature increases, the lubricant loses some of the refrigerant
and the viscosity reaches a maximum at a point away from the cold- Thermodynamics and Transport Phenomena
est spot in the system. Dissolving lubricant in liquid refrigerant affects the thermo-
Similar to the lubricating fluid, the properties of the working dynamic properties of the working fluid. The vapor pressures of
fluid (a high refrigerant concentration solution) are also affected. refrigerant-lubricant solutions at a given temperature are always
Lubricants in Refrigerant Systems 7.9
Fig. 6 Density as Function of Temperature and Fig. 9 Density as Function of Temperature and
Pressure for Mixture of R-134a and Pressure for Mixture of R-410A and
32 ISO VG Polypropylene Glycol 68 ISO VG Branched Acid
Butyl Ether Lubricant Polyol Ester Lubricant
Fig. 7 Density as Function of Temperature and Fig. 10 Density as Function of Temperature and
Pressure for Mixture of R-134a and Pressure for Mixture of R-410A and
80 ISO VG Polyoxypropylene 32 ISO VG Mixed Acid
Glycol Diol Lubricant Polyol Ester Lubricant
Fig. 7 Density as Function of Temperature and Fig. 10 Density as Function of Temperature and
Pressure for Mixture of R-134a and Pressure for Mixture of R-410A and
80 ISO VG Polyoxypropylene 32 ISO VG Mixed Acid
Glycol Diol Lubricant Polyol Ester Lubricant
Fig. 12 P-T-S Diagram for Completely Miscible Refrigerants are classified as completely miscible, partially mis-
Refrigerant-Lubricant Solutions cible, or immiscible, according to their mutual solubility relations
with mineral oils. Because several commercially important refrig-
erants are partially miscible, further designation as having high,
intermediate, or low miscibility is shown in Table 6.
Completely miscible refrigerants and lubricants are mutually
soluble in all proportions at any temperature encountered in a refrig-
eration or air-conditioning system. This type of mixture always
forms a single liquid phase under equilibrium conditions, no matter
how much refrigerant or lubricant is present.
Partially miscible refrigerant-lubricant solutions are mutually
soluble to a limited extent. Above the critical solution temperature
(CST) or consolute temperature, many refrigerant/lubricant mix-
tures in this class are completely miscible, and their behavior is
identical to that just described. As mentioned previously, R-134a
and some synthetic lubricants exhibit a region of immiscibility at
higher temperatures.
Below the critical solution temperature, however, the liquid may
separate into two phases. Such phase separation does not mean that
the lubricant and the refrigerant are insoluble in each other. Each
liquid phase is a solution; one is lubricant-rich and the other
refrigerant-rich, depending on the predominant component. Each
phase may contain substantial amounts of the leaner component,
and these two solutions are themselves immiscible with each other.
The importance of this concept is best illustrated by R-502, which
is considered a low miscibility refrigerant exhibiting a high CST as
well as a broad immiscibility range. However, even at −20°C, the
lubricant-rich phase contains about 20 mass % of dissolved refriger-
ant (see Figure 15). Examples of partially miscible systems, in addi-
Fig. 12 P-T-S Diagram for Completely Miscible tion to R-502, are R-22, R-114, and R-13 with mineral oils.
Refrigerant-Lubricant Solutions The basic properties of the immiscible region can be recognized
by applying the phase rule. With three phases (two liquid and one
vapor) and two components, there can be only one degree of free-
Table 6 Mutual Solubility of Refrigerants and Mineral Oil dom. Therefore, either the temperature or the pressure automati-
Partially Miscible cally determines the composition of both liquid phases. If the
system pressure is changed, the temperature of the system changes
Completely High Intermediate Low and the two liquid phases assume somewhat different compositions
Miscible Miscibility Miscibility Miscibility Immiscible
determined by the new equilibrium conditions.
R-11 R-123 R-22 R-13 Ammonia Figure 13 illustrates the behavior of partially miscible mix-
R-12 R-114 R-14 CO2 tures. Point C on the graph represents the critical solution tem-
R-113 R-115 R-134a perature t 3 . There are three separate regions below this
R-152a R-407C temperature on the diagram. Reading from left to right, a family
of the smooth solid curves represents a region of completely mis-
R-C318 R-410A
cible lubricant-rich solutions. These curves are followed by a
R-502 wide break representing a region of partial miscibility in which
there are two immiscible liquid phases. On the right side, the par-
tially miscible region disappears into a second completely misci-
Pressure-temperature-solubility relations are usually presented ble region of refrigerant-rich solutions. A dome-shaped envelope
in the form shown in Figure 12. On this graph, P1° and P2° represent (broken line curve OCR) encloses the partially miscible region;
the saturation pressures of the pure refrigerant at temperatures t1 and everywhere outside this dome the refrigerant and lubricant are
t2, respectively. Point E1 represents an equilibrium condition, where completely miscible. In a sense, Figure 13 is a variant of Figure
one and only one composition of the liquid, represented by W1, is 12 in which the partial miscibility dome (OCR) blots out a sub-
possible at the pressure P1. If the temperature of this system is stantial portion of the continuous solubility curves. Under the
increased to t2, some of the liquid refrigerant evaporates, and the dome (i.e., in the immiscible region), the two points E1 and E2 on
equilibrium point shifts to E2, corresponding to a new pressure P2. the temperature line t 1 represent the two phases coexisting in
In either case, the lubricant-refrigerant solution exerts a vapor pres- equilibrium.
sure less than that of the pure refrigerant at the same temperature. These two phases differ considerably in composition (W1 and
W2) but have the same refrigerant pressure P1. The solution pres-
Mutual Solubility sure P1 lies not far below the saturation pressure of pure refrigerant
In a compressor, the lubricating fluid is a solution of refrigerant P1°. Commonly, refrigerant-lubricant solutions near the partial
dissolved in lubricant. In other parts of the refrigerant system, the miscibility limit show less reduction in refrigerant pressure than is
solution is a lubricant in liquid refrigerant. In both instances, either observed at the same lubricant concentration with completely mis-
the lubricant or the refrigerant could exist alone as a liquid if the cible refrigerants.
other were not present; therefore, any distinction between the dis- Totally immiscible lubricant-refrigerant solutions are de-
solving and dissolved component merely reflects a point of view. fined in this chapter as only very slightly miscible. In such mix-
Either of the liquids can be considered as dissolving the other. This tures, the immiscible range is so broad that mutual solubility
relationship is termed mutual solubility. effects can be ignored. Critical solution temperatures are seldom
7.12 2002 ASHRAE Refrigeration Handbook (SI)
Fig. 13 P-T-S Diagram for Partially Miscible Fig. 14 P-T-S Relations of R-22 with 43 White Oil
Refrigerant-Oil Solutions (0% CA, 55% CN, 45% CP)
Fig. 15 Critical Solubilities of Refrigerants with 32 Naph- Fig. 16 Critical Solubilities of Refrigerants with 32 Alkylben-
thenic Lubricant (CA 12%, CN 44%, CP 44%) zene Lubricant
Fig. 17 Effect of Oil Properties on Miscibility with R-22 Table 8 Critical Solution Temperatures for Selected
Refrigerant/Lubricant Pairs
Critical Solution
Temperature, °C
Refrig-
erant Lubricant Lower Upper
R-22 ISO 32 Naphthenic mineral oil −5 >60
ISO 32 Modified polyglycol −12 >60
ISO 68 Naphthenic mineral oil 15 >60
R-123 ISO 68 Naphthenic mineral oil −39 >60
ISO 58 Polypropylene glycol butyl monoether −50 14
R-134a ISO 58 Polypropylene glycol butyl monoether −50 56
ISO 32 Modified polyglycol 10 >90
ISO 22 Penta erythritol, mixed-acid ester −42 >90
ISO 58 Polypropylene glycol butyl monoether −46 6
ISO 100 Polypropylene glycol diol −46 11
ISO 100 Penta erythritol, mixed-acid ester −35 >32
ISO 100 Penta erythritol, branched-acid ester −46 12
Fig. 18 Viscosity of Mixtures of Various Refrigerants Fig. 20 Viscosity-Temperature Chart for Solutions
and 32 Paraffinic Oil of R-22 in 32 Naphthene and
Paraffin Base Oils
LUBRICANT RETURN FROM EVAPORATORS coldest regions in the evaporator, but at some intermediate point
Regardless of the miscibility relations of a lubricant with refrig- where much of the refrigerant has escaped from the lubricant. This
erants, for a refrigeration system to function properly, the lubricant condition is possibly in the suction line. The velocity of the return
must return adequately from the evaporator to the crankcase. vapor, which may be high enough to move the lubricant-refrigerant
Parmelee (1964) showed that the viscosity of the lubricant, solution in the colder part of the evaporator, may be too low to
saturated with refrigerant under low-pressure and low-temperature achieve the same result at the point of maximum viscosity. The
conditions, is important in providing good lubricant return. The vis- designer must consider this factor to minimize any lubricant return
cosity of the lubricant-rich liquid that accompanies the suction gas problems. Chapters 2 and 3 have further information on velocities in
changes as it sees rising temperatures on its way back to the com- return lines.
pressor. Two opposing factors then come into play. First, the in- Another aspect of viscosity data at the evaporator conditions is
creasing temperature tends to decrease the viscosity of the fluid. shown in Figure 35, which compares a synthetic alkylbenzene lubri-
Second, since the pressure remains unchanged, the increasing tem- cant with a naphthenic mineral oil. The two oils are the same vis-
perature also tends to drive off some of the dissolved refrigerant cosity grade, but the highly aromatic alkylbenzene lubricant has a
from the solution, thereby increasing its viscosity (Loffler 1960). much lower viscosity index in the pure state and shows a higher
Figures 32 through 34 show the variation in viscosity with tem- viscosity at low temperatures. However, at 135 kPa or approxi-
perature and pressure for three lubricant-refrigerant solutions rang- mately −40°C evaporator temperature, the viscosity of the lubri-
ing from −40°C to 21°C. In all cases, the viscosities of the solutions cant/R-502 mixture is considerably lower for alkylbenzene than for
passed through maximum values as the temperature was changed at naphthenic lubricant. In spite of the lower viscosity index, alkylben-
constant pressure, a finding that was also consistent with previous zene returns more easily than naphthenic lubricant.
data obtained by Bambach (1955) and Loffler (1960). According to Estimated viscosity-temperature-pressure relationships for a
Parmelee, the existence of a viscosity maximum is significant, naphthenic lubricant with R-502 are shown in Figure 36. Figures
because the lubricant-rich solution becomes most viscous not in the 37 and 38 show viscosity-temperature-pressure plots of alkylben-
Lubricants in Refrigerant Systems 7.17
Fig. 25 Viscosity-Temperature Curves for Solutions of R-11 Fig. 27 Solubility of R-12 in Refrigerant Oils
in 65 Naphthene Base Oil
zene and R-22 and R-502, respectively. These data are based on
experimental data from Van Gaalen et al. (1991a, 1991b). Figures
39 and 40 show viscosity-temperature-pressure data for mixtures of
R-134a and a 32 ISO VG polyalkylene glycol and an 80 ISO VG
polyalkylene glycol, respectively. Figures 41 and 42 show similar Solid lines: 32 naphthene base oil.
data for R-134a and a 32 ISO VG polyol ester and a 100 ISO VG Also 52 German base oil (Bambach 1955).
Broken lines: 32 and 70 mixed base oils.
polyol ester, respectively (Cavestri 1993). Cavestri and Schafer
(2000) provide viscosity data as a function of temperature and
pressure for R-410A/polyol ester oils as shown in Figures 43 Fig. 27 Solubility of R-12 in Refrigerant Oils
7.18 2002 ASHRAE Refrigeration Handbook (SI)
through 46. Viscosity and pressure data at constant concentrations Fig. 30 Solubility of R-114 in HVI Oils
are given in Figures 47 through 50.
Sundaresan and Radermacher (1996) observed oil return in a
small air-to-air heat pump. Three refrigerant lubricant pairs (R-22/
mineral oil, R-407C/mineral oil, and R-407C/polyol ester) were
studied under four conditions—steady-state cooling, steady-state
heating, cyclic operation, and a simulated lubricant pumpout situa-
tion. The lubricant returned rapidly to the compressor in the R-22/
mineral oil and R-407C/polyol ester tests, but oil return was unreli-
able in the R-407C/mineral oil test.
Kesim et al. (2000) developed general relationships for calculat-
ing the required refrigerant speed for carrying lubricant oil up ver-
tical sections of refrigerant lines. For these relationships they
assumed the thickness of the oil film to be 2% of the inner pipe
diameter. They converted these minimum speeds to the correspond-
ing refrigeration load or capacities for R-134a and copper suction
and discharge risers.
SOLUBILITY OF
HYDROCARBON GASES
Hydrocarbon gases such as propane (R-290) and ethylene
(R-1150) are miscible with the compressor lubricating oil and are
absorbed by the lubricant. The lower the boiling point or critical
temperature, the less soluble the gas, all other values being equal.
Gas solubility increases with decreasing temperature and increasing
Fig. 36 Viscosity-Temperature-Pressure Chart for pressure (Figures 51 and 52). As with other lubricant miscible
Solutions of R-502 in refrigerants, absorption of the hydrocarbon gas reduces lubricant
32 mm2/s Naphthenic Oil viscosity.
Lubricants in Refrigerant Systems 7.21
Fig. 38 Viscosity-Temperature-Pressure Chart line carrying liquid refrigerant or in a line returning lubricant to the
for Solutions of R-502 in compressor. The material in the filter/dryer must be compatible with
32 mm2/s Alkylbenzene Oil the lubricant. Also, desiccants can remove some additives in the
lubricant.
Spot checks show that water solubility data for transformer oils
obtained by Clark (1940) also apply to refrigeration oils (Figure 53).
A simple method, previously used in industry to detect free water
in refrigeration oils, is the dielectric breakdown voltage (ASTM
D877), which is designed to control moisture and other contaminants
in electrical insulating oils. The method does not work with polyester
and polyalkylene glycol oils, however. According to Clark (1940),
the dielectric breakdown voltage decreases with increasing moisture
content at the same test temperature and increases with temperature
for the same moisture content. At 27°C, when the solubility of water
in a 32 mm2/s naphthenic lubricant is between 50 to 70 mg/kg, a
dielectric breakdown voltage of about 25 kV indicates that no free
water is present in the lubricant. However, the lubricant may contain
dissolved water up to the solubility limit. Therefore, a dielectric
breakdown voltage of 35 kV is commonly specified to indicate that
the moisture content is well below saturation.
The ASTM D877 test is not sensitive below about 60% satura-
tion. Current practice is to measure directly the total moisture con-
tent by procedures such as the Karl Fischer (ASTM D1533) method.
Fig. 39 Viscosity-Temperature-Pressure Plot for 32 ISO VG Polypropylene Glycol Butyl Mono Ether with R-134a
Fig. 39 Viscosity-Temperature-Pressure Plot for 32 ISO VG Polypropylene Glycol Butyl Mono Ether with R-134a
Fig. 41 Viscosity-Temperature-Pressure Plot for 32 ISO VG Branched Acid Polyol Ester with R-134a
Fig. 41 Viscosity-Temperature-Pressure Plot for 32 ISO VG Branched Acid Polyol Ester with R-134a
Fig. 42 Viscosity-Temperature-Pressure Plot for 100 ISO VG Branched Acid Polyol Ester with R-134a
Fig. 42 Viscosity-Temperature-Pressure Plot for 100 ISO VG Branched Acid Polyol Ester with R-134a
7.24 2002 ASHRAE Refrigeration Handbook (SI)
REFERENCES
Albright, L.F. and J.D. Lawyer. 1959. Viscosity-solubility characteristics of
mixtures of Refrigerant 13B1 and lubricating oils. ASHRAE Journal
(April):67.
Albright, L.F. and A.S. Mandelbaum. 1956. Solubility and viscosity charac-
teristics of mixtures of lubricating oils and “Freon-13 or -115.” Refrig-
erating Engineering (October):37.
API. 1970. Technical data book—Petroleum refining, 2nd ed. American
Petroleum Institute, Washington, D.C.
ASHRAE. 1994. Methods of testing the floc point of refrigeration grade oils.
Standard 86.
Baldwin, R.R. and S.G. Daniel. 1953. Journal of the Institute of Petroleum
39:105.
Fig. 52 Solubility of Ethylene in Oil Bambach, G. 1955. The behavior of mineral oil-F12 mixtures in refrigerat-
(Witco) ing machines. Abhandlungen des Deutschen Kältetechnischen Vereins,
No. 9. (Translated by Carl Demrick.) Also see abridgement in Kältetech-
nik 7(7):187.
the degradation of lubricants that might be used with them. Hygro- Beerbower, A. and D.F. Greene. 1961. The behavior of lubricating oils in
scopic synthetic POE and PAG lubricants are less chemically stable inert gas atmospheres. ASLE Transactions 4(1):87.
with chlorinated refrigerants than mineral oil due to the interaction Bosworth, C.M. 1952. Predicting the behavior of oils in refrigeration sys-
tems. Refrigerating Engineering (June):617.
of moisture with the refrigerant at high temperatures.
Brewer, A.F. 1951. Good compressor performance demands the right lubri-
cating oil. Refrigerating Engineering (October):965.
CONVERSION FROM
OTHER FROM
CONVERSION Cavestri, R.C. 1993. Measurement of the solubility, viscosity and density of
CFCCFC REFRIGERANTS
REFRIGERANTS
REFRIGERANTS TO
TO OTHER synthetic lubricants with HFC-134a. Final Report for ASHRAE 716-RP.
Cavestri, R.C. and W.R. Schafer. 2000, Measurement of solubility, viscosity,
REFRIGERANTS and density of R-410A refrigerant/lubricant mixtures, ASHRAE Trans-
The most common conversion from a CFC refrigerant to another actions 106(1):277.
Clark, F.M. 1940. Water solution in high-voltage dielectric liquids. Electri-
refrigerant is retrofitting to use HCFC or HFC refrigerants. A con-
cal Engineering Transactions 59(8):433.
version may require draining each component to completely remove Divers, R.T. 1958. Better standards are needed for refrigeration lubricants.
an incompatible lubricant. Often, flushing in some manner is the Refrigeration Engineering (October):40.
only way to remove old lubricant. The flushing medium may be liq- Doderer, G.C. and H.O. Spauschus. 1965. Chemical reactions of R-22.
uid refrigerant, an intermediate fluid, or the lubricant that will be ASHRAE Transactions 71(I):162.
charged with the alternate refrigerant. Liquid CFC refrigerants cir- Fuller, D.D. 1984. Theory and practice of lubrication for engineers. John
culated through the entire system are preferable for flushing, Wiley and Sons, New York.
although other refrigerants are used. The refrigerant is recovered Goswami, D.Y., D.O. Shah, C.K. Jotshi, S. Bhagwat, M. Leung, and A.S.
with equipment modified for this use. Gregory. 1997. Foaming characteristics of HFC refrigerants. ASHRAE
The refrigeration equipment must be operated if intermediate Journal 39(6):39-44.
Gunderson, R.C. and A.W. Hart. 1962. Synthetic lubricants. Reinhold, New
fluids and lubricants are used for flushing. The system is charged York.
with the flushing material and CFC refrigerant and operated for at Huttenlocher, D.F. 1969. A bench scale test procedure for hermetic compres-
least eight hours. After operation, the lubricant charge is drained sor lubricants. ASHRAE Journal (June):85.
from the compressor. This process is repeated until the lubricant in Kartzmark, R., J.B. Gilbert, and L.W. Sproule. 1967. Hydrogen processing
the drained material is reduced to a specified level. Chemical test of lube stocks. Journal of the Institute of Petroleum 53:317.
Lubricants in Refrigerant Systems 7.27
Kesim, S.C., K. Albayrak, and A. Ileri. 2000. Oil entrainment in vertical Short, G.D. 1990. Synthetic lubricants and their refrigeration applications.
refrigerant piping. International Journal of Refrigeration 23(2000):626- Lubrication Engineering 46(4):239.
631. Shubkin, R.L. 1993. Polyalphaolefins, in Synthetic lubricants and high per-
Komatsuzaki, S. and Y. Homma. 1991. Antiseizure and antiwear properties formance functional fluids. Marcel Dekker, New York.
of lubricating oils under refrigerant gas environments. Lubrication Engi- Soling, S.P. 1971. Oil recovery from low temperature pump recirculating
neering 47(3):193. halocarbon systems. ASHRAE Symposium PH-71-2.
Little, J.L. 1952. Viscosity of lubricating oil-Freon-22 mixtures. Refrigerat-
Spauschus, H.O. 1963. Thermodynamic properties of refrigerant-oil solu-
ing Engineering (Nov.):1191. tions. ASHRAE Journal (April):47; (October):63.
Loffler, H.J. 1957. The effect of physical properties of mineral oils on their
miscibility with R-22. Kältetechnik 9(9):282. Spauschus, H.O. 1964. Vapor pressures, volumes and miscibility limits of
Loffler, H.J. 1959. Density of oil-refrigerant mixtures. Kältetechnik. R-22-oil solutions. ASHRAE Transactions 70:306.
11(3):70. Spauschus, H.O. and G.C. Doderer. 1961. Reaction of Refrigerant 12 with
Loffler, H.J. 1960. Viscosity of oil-refrigerant mixtures. Kältetechnik. petroleum oils. ASHRAE Journal (February):65.
12(3):71. Spauschus, H.O. and L.M. Speaker. 1987. A review of viscosity data for oil-
Mills, I.W., et al. 1946. Molecular weight-physical property correlations for refrigerant solutions. ASHRAE Transactions 93(2):667.
petroleum fractions. Industrial and Engineering Chemistry 38:442. Steinle, H. 1950. Kaltemaschinenole. Springer-Verlag, Berlin, Germany, 81.
Mills, I.W. and J.J. Melchoire. 1967. Effect of aromatics and selected addi- Sundaresan, S.G. and R. Radermacher. 1996. Oil return characteristics of
tives on oxidation stability of transformer oils. Industrial and Engineer- refrigerant oils in split heat pump system. ASHRAE Journal 38(8):57.
ing Chemistry (Product Research and Development) 6:40. Swallow, A., A. Smith, and B. Greig. 1995. Control of refrigerant vapor
Mosle, H. and W. Wolf. 1963. Kältetechnik 15:11. release from polyol ester/halocarbon working fluids. ASHRAE Transac-
Murray, S.F., R.L. Johnson, and M.A. Swikert. 1956. Difluoro-dichlo- tions 101(2):929.
romethane as a boundary lubricant for steel and other metals. Mechanical
Engineering 78(3):233. Van Gaalen, N.A., M.B. Pate, and S.C. Zoz. 1990. The measurement of sol-
Neubauer, E.T. 1958. Compressor crankcase heaters reduce oil foaming. ubility and viscosity of oil/refrigerant mixtures at high pressures and
Refrigerating Engineering (June):52. temperatures: Test facility and initial results for R-22/naphthenic oil mix-
Parmelee, H.M. 1964. Viscosity of refrigerant-oil mixtures at evaporator tures. ASHRAE Transactions 96(2):183.
conditions. ASHRAE Transactions 70:173. Van Gaalen, N.A., S.C. Zoz, and M.B. Pate. 1991a. The solubility and vis-
Pate, M.B., S.C. Zoz, and L.J. Berkenbosch. 1993. Miscibility of lubricants cosity of solutions of HCFC-22 in naphthenic oil and in alkylbenzene at
with refrigerants. Report No. DOE/CE/23810-18. U.S. Department of high pressures and temperatures. ASHRAE Transactions 97(1):100.
Energy. Van Gaalen, N.A., S.C. Zoz, and M.B. Pate. 1991b. The solubility and vis-
Rembold, U. and R.K. Lo. 1966. Determination of wear of rotary compres- cosity of solutions of R-502 in naphthenic oil and in an alkylbenzene at
sors using the isotope tracer technique. ASHRAE Transactions 72:VI.1.1. high pressures and temperatures. ASHRAE Transactions 97(2):285.
Sanvordenker, K.S. 1968. Separation of refrigeration oil into structural com- Van Nes, K. and H.A. Weston. 1951. Aspects of the constitution of mineral
ponents and their miscibility with R-22. ASHRAE Transactions oils. Elsevier, New York.
74(I):III.2.1. Walker, W.O., A.A. Sakhanovsky, and S. Rosen. 1957. Behavior of refriger-
Sanvordenker, K.S. and W.J. Gram. 1974. Laboratory testing under con- ant oils and Genetron-141. Refrigerating Engineering (March):38.
trolled environment using a falex machine. Compressor Technology Walker, W.O., S. Rosen, and S.L. Levy. 1960. A study of the factors influ-
Conference, Purdue University. encing the stability of the mixtures of Refrigerant 22 and refrigerating
Sanvordenker, K.S. and M.W. Larime. 1972. A review of synthetic oils for oils. ASHRAE Transactions 66:445.
refrigeration use. ASHRAE Symposium, Lubricants, Refrigerants and
Systems—Some Interactions. Walker, W.O., S. Rosen, and S.L. Levy. 1962. Stability of mixtures of refrig-
Schwing, R.C. 1968. Polyisobutyl benzenes and refrigeration lubricants. erants and refrigerating oils. ASHRAE Transactions 68:360.
ASHRAE Transactions 74(1):III.1.1. Wahlstrom, A. and L. Vamling. 2000. Development of models for prediction
Seeman, W.P. and Shellard, A.D. 1963. Lubrication of Refrigerant 22 of solubility for HFC working fluids in pentaerythritol ester compressor
machines. IX International Congress of Refrigeration, Paper III-7, oils. International Journal of Refrigeration 23(2000):597-608.
Munich, Germany. Witco. Sonneborn Division, Bulletin 8846.