0% found this document useful (0 votes)
81 views

Supply Side: Project: MOI Pressure Loss For AHU-01 - CENTRAL LAUNDARY Prepared By: Eng - ASHRAF

This document contains a pressure loss calculation for an air handling unit (AHU-01) duct system. It includes the duct sizes, air flow rates, velocities and lengths for the supply and return sides of the system. Pressure losses are calculated for each duct section and fitting using friction coefficients. The total pressure losses are summarized.

Uploaded by

collins014
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views

Supply Side: Project: MOI Pressure Loss For AHU-01 - CENTRAL LAUNDARY Prepared By: Eng - ASHRAF

This document contains a pressure loss calculation for an air handling unit (AHU-01) duct system. It includes the duct sizes, air flow rates, velocities and lengths for the supply and return sides of the system. Pressure losses are calculated for each duct section and fitting using friction coefficients. The total pressure losses are summarized.

Uploaded by

collins014
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Project: MOI

Pressure loss For AHU-01 -CENTRAL LAUNDARY prepared by : Eng . ASHRAF


SUPPLY SIDE
DUCT SIZE DUCT SIZE FLOW VELOCITY DUCT SUMMARY OF DUCT TOTAL
AHU -01 DUCT DUCT AIR FLOW mm EQUIVALENT AREA VELOCITY PRESSURE LENGTH FRICTION LOSS PRESSURE LOSS, PRESSURE LOSS REMARKS
SECTION ELEMENT L/S W H W H FIITINGS ROUND m² m/s Pa m COEFFICIENT Pa/m Pa
sandtrap louver 260 800 400 45
GENERAL ITEMS ADDITIONAL
5920 1000 750 50
ATTENUATOR CONSIDERD
2 TRANSITION 260 800 400 400 250 SR4-2 0.44 0.06 0.00
3 STRAIGHT DUCT 260 400 250 343.33 0.10 2.60 4.06 0.33 0.02 0.29 0.10
4 MD 260 400 250 CR 9-3 0.37 2.00
5 PLENUM BOX 260 2400 500 1116.43 1.20 0.22 0.03 0.50 0.02 0.00 0.00
6 STRAIGHT DUCT 5920 1000 750 944.27 0.75 7.89 37.38 3.46 0.02 0.61 2.10
7 FD 5920 1000 750 CR9-7 0.12 5.00
8 ELBOW 5920 1000 750 CR3-4 0.02 1.00
9 STRAIGHT DUCT 5920 1000 750 944.27 0.75 7.89 37.38 3.00 0.02 0.61 1.82
10 JUCTION 2480 700 550 0.58 2.00
11 VCD 2480 700 550 CR9-3 0.37 9.00
12 STRAIGHT DUCT 2480 700 550 677.06 0.39 6.44 24.90 1.91 0.02 0.63 1.20
13 TRANSITION 1350 700 550 500 500 SR4-2 0.57 0.05 1.00
14 STRAIGHT DUCT 1350 500 500 546.58 0.25 5.40 17.50 0.68 0.02 0.59 0.40
15 STRAIGHT DUCT 1350 500 500 546.58 0.25 5.40 17.50 2.03 0.02 0.59 1.20
16 TRANSITION 1150 500 500 500 450 SR4-2 0.30 0.01 0.00
17 STRAIGHT DUCT 1150 500 450 518.35 0.23 5.11 15.67 2.75 0.02 0.57 1.58
18 VCD 630 400 350 CR9-3 0.37 5.00
19 STRAIGHT DUCT 630 400 350 408.80 0.14 4.50 12.15 3.12 0.02 0.61 1.91
20 TRANSITION 530 400 350 350 350 SR4-2 0.30 0.02 0.00
21 STRAIGHT DUCT 530 350 350 382.61 0.12 4.33 11.23 2.94 0.02 0.62 1.81
22 ELBOW 530 350 350 CR3-1 0.17 2.00
23 STRAIGHT DUCT 530 350 350 382.61 0.12 4.33 11.23 1.12 0.02 0.62 0.69
24 TRANSITION 300 350 350 300 300 SR4-2 0.30 0.03 0.00
25 STRAIGHT DUCT 330 300 300 327.95 0.09 3.67 8.07 5.65 0.02 0.55 3.13
26 TRANSITION 230 300 300 300 250 SR4-2 0.53 0.02 1.00
27 STRAIGHT DUCT 230 300 250 299.07 0.08 3.07 5.64 3.78 0.02 0.45 1.71
28 TRANSITION 80 300 250 200 200 SR4-2 0.35 0.07 0.00
29 STRAIGHT DUCT 80 200 200 218.63 0.04 2.00 2.40 2.61 0.02 0.31 0.81
30 TRANSITION 40 200 200 200 150 SR4-2 0.30 0.04 0.00
31 STRAIGHT DUCT 40 200 150 188.85 0.03 1.33 1.07 4.59 0.02 0.18 0.84
32 ELBOW 40 200 150 CR3-1 0.19 0.00
33 STRAIGHT DUCT 40 200 150 1.97
24 SCD 150X150 40 20.00

Sub-Total (SUPPLY FAN) 162.29

RETURN SIDE
DUCT SIZE DUCT SIZE FLOW VELOCITY DUCT SUMMARY OF DUCT TOTAL
AHU-01 DUCT DUCT AIR FLOW mm EQUIVALENT AREA VELOCITY PRESSURE LENGTH FRICTION LOSS PRESSURE LOSS, PRESSURE LOSS REMARKS
SECTION ELEMENT L/S W H W H FIITINGS ROUND m² m/s Pa m COEFFICIENT Pa/m Pa
ADDITIONAL
GENERAL 5660 1000 750 50
ATTENUATOR CONSIDERED
1 BELLMOUTH 3000 800 600 ER1-3 0.15 3.00
2 STRAIGHT DUCT 3000 800 600 755.42 0.48 6.25 23.44 0.98 0.02 0.52 0.51
3 VCD 3000 800 600 CR 9-3 0.37 9.00
4 JUNCTION 5660 1000 750 ER5-4 0.26 3.00
5 STRAIGHT DUCT 5660 1000 750 944.27 0.75 7.55 34.17 5.00 0.02 0.56 2.79
6 ELBOW 5660 1000 750 CR3-4 0.02 1.00
7 FD 5660 1000 750 CR 9-7 0.12 4.00
8 STRAIGHT DUCT 5660 1000 750 944.27 0.75 7.55 34.17 0.46 0.02 0.56 0.26
9 ELBOW 45 5660 1000 750 CR3-4 0.01 1.00
10 STRAIGHT DUCT 5660 1000 750 944.27 0.75 7.55 34.17 1.47 0.02 0.56 0.82
11 ELBOW 45 5660 1000 750 CR3-4 0.01 1.00
12 STRAIGHT DUCT 5660 1000 750 944.27 0.75 7.55 34.17 3.30 0.02 0.56 1.84
13 ELBOW 5660 1000 750 CR3-4 0.02 1.00
14 STRAIGHT DUCT 5660 1000 750 944.27 0.75 7.55 34.17 0.92 0.02 0.56 0.51
15 PLENUM 5660 1100 800 2.40 0.01 0.00
ADDITIONAL
16 0.37 13.00
MD 5660 1000 750 CR 9-3 CONSIDERED

Sub-Total (RETURN FAN) 92.74

TOTAL (SUUPLY+RETURN) 255.04

`
Factor Of Safety 15% 38.26
TOTAL Calculated 293.29 Pa
PRESSURE LOSS Design 400 Pa

You might also like