Wireline Works Tech-Bulletins
Wireline Works Tech-Bulletins
"
Technical Bulletins
Technical Bulletin Number – 001
Example:
L1 = 25,500 Feet
R1 = 265.4 Ω
T1 = 75°F
r = (R1 / L1) x [(302.5) / (234.5 + T1)]
r = 0.01017 Ω/ft
As sections of cable are cut off, the remaining length, “L”, of cable on the drum can be calculated using the recorded
value of “r”, the Resistance “R” of the centre conductor of the remaining length, and the Temperature, “T” of the
remaining length of cable.
Example:
r = 0.01017245 (Ω/ft)
R = 195.4 Ω
T = 92°F
L = (R / r) x [(302.5) / (234.5 + T)]
L = 17796.7
To obtain the best results, it is recommended to use a Fluke or equal quality 4 or 5 digit 1% type Ohmmeter with good
leads. It is Important to use the same Ohmmeter to establish the value of “r” and later measurements of “R”.
05/2005
Technical Bulletin Number – 002
The fastest way of locating an electrical leak is to “burn it out” with a high voltage, high current source* and in doing this
you dry the leak and reduce it to a “ dead short”. There are several methods of easily locating a “ dead short”. When it is
known that the cable has been abused in some way, tension or temperature, then burning out the leak is the best
procedures. If, however you have a fairly new cable and a factory defect is suspected, the burn out method should not be
used as it completely destroys the area around the leak and the exact cause of the leak can not be determined. There are
methods of locating leaks within a few inches without first burning out the leak as will be covered in later technical bulletins.
Part-1, Method for locating a “dead short” leak. A dead short leak, as described above, is when the copper conductor is in
direct contact with the armor or the resistance between the conductor and armor is less than 100 ohms. The only instrument
required is an accurate digital ohmmeter that reads to at least 0.1 Ohm. Before any leak location process is started be sure
that both ends of the cable conductor are completely disconnected from any tools , collector, etc. and clean!
After both ends of the conductor are cleaned, using the digital Ohmmeter, measure and record, the following resistances.
• R: Total conductor resistance, end to end, Ohms.
• Rt: Resistance between conductor & armor measured at the Truck end, Ohms.
• Rw: Resistance between conductor & armor measured at the whip end, Ohms.
• L: The total length of the cable, feet.
To be sure your problem can be classified as a “dead short”, make the following calculation:
((Rw + Rt) - R) < 300 Ohms
If the this calculation is greater than 300 Ohms, you do not have a “dead short” and you should use another method of
locating the leak, (Part 2 & 3), or “burn out” the leak to obtain a more direct short. If the above calculation results with a
value less than 300 Ohms then the leak location can be calculated as follows:
• Lw: Distance of the leak from the whip end of the cable, feet.
• Lt: Distance of the leak from the truck end of the cable, feet.
Lw = [ R + Rw – Rt ] x [ L / 2R ]
Lt = [ R + Rt – Rw ] x [ L / 2R ]
Example:
Cable length:
L = 20,500 feet
R = 220.5 Ohms
Rw = 165.0 Ohms
Rt = 325.5 Ohms
Leak Location:
Lw = [ 220.5 + 165.0 – 325.5 ] x [ 20,500 / 2x220.5 ] = 2,789 feet from whip end
Lt = [ 220.5 + 325.5 – 165.0 ] x [ 20,500 / 2x220.5 ] = 17,711 feet from truck end
Methods for locating high resistance electrical leaks and eliminating the effects of a wet leak will be covered in later Technical Bulletins.
05/2005
Technical Bulletin Number – 003
Accuracy
• This type of instrument will only locate a leak to within +/-
200 feet.
• For maximum accuracy:
1. Burn out the leak to the lowest resistance possible
2. Be sure all test leads fit firmly in sockets
3. The lengths of the WHIP & TRUCK test leads must be equal.
4. The test leads should be as short as possible
• Check for a “ wet leak”. This is done by measuring the
resistance of the leak with an Ohm meter and then reversing
Setup: the leads of the Ohm meter and see if the leak resistance is
• Check that both ends of the cable are free, clean and NOT the same. If the leak resistance is the same you are ok. If
connected to anything. there is a significant difference between the two readings,
• Turn power switch OFF. you need to dry out the leak with a “burn out box”.
05/2005
Technical Bulletin Number – 004
Connection Summary
• TRUCK DRUM has the collector
• Connect leaking conductor to the collector
• Connect NEGATIVE METER lead to the Collector TRUCK
• Connect the test lead with the copper hook to the
METER POSITIVE
• Connect POSITIVE power source to frame of
TRUCK DRUM.
1. If the meter indicates a POSITIVE voltage, the leak is • Connect NEGATIVE power source to frame of
towards the SHOP DRUM. SHOP DRUM
2. If the meter indicates a NEGATIVE voltage, the leak is
towards the TRUCK DRUM. Miscellaneous
• Be sure the plastic insulation is CLEAN on both ends.
Setup Procedure • The pay off and take up stands must not be connected
• String the cable between the pay off, truck, and shop mechanically.
drums. Going around a sheave wheel is ok as long as this • Do not connect the power source leads directly to the
sheave wheel is electrically insulated from both pay off cable armor. This connection can spark when connected,
and take up drums. burning cable armor.
• Connect the leaking conductor to the collector on
TRUCK DRUM. 05/2005
Technical Bulletin Number – 005
1. Wet Leaks: An electrical leak occurs when there is a rupture in the plastic insulation surrounding the copper conductor.
Sometimes there is direct contact between the copper and the armor wires, (dead short), other times there is burnt
plastic from the break down process that leaves a carbon trail between the copper and armor, and in other cases there
is moisture in the cable between the copper and armor forming a “wet leak”.
The armor wires are covered with a Zinc coating. Zinc is above and Copper is below Hydrogen in the electromotive
series of metals, so when they are in a conductive medium, such as salt water, there will be a voltage generated
between them. In the case of Zinc and Copper the voltage is about 0.83 volts. If you would like to run a little physics
experiment, simply clip a short piece of armor wire to the negative lead of a digital voltmeter and the positive lead to a
piece of copper wire and place them in a glass of salt water. The meter will indicate a voltage in the range of 0.83 volts.
This voltage in a leak can significantly distort the location of the leak.
To determine if you have a wet leak, first measure the resistance of the leak and then reverse the leads of the
ohmmeter. If you have a wet leak there will be a significant difference between the 2 resistance measurements. The
wet leak can be dried out by repeated application of voltage from a Hi-pot or a “ burn out box”.
If you are not equipped to burn out the leak, then using the resistance method, (Technical Bulletin 002), calculate the
distance to the leak, Lw, and then reverse the polarity of the Ohmmeter and again calculate the distance to the leak
Lw’. Take the average of these two values, (Lw +Lw’)/2 and this will be the correct location.
Some leak locator bridges have a polarity switch built in to obtain the values of Lw and Lw’. Again the correct location
will be the average of the two readings. If a reversing switch is not included, then swap the TRUCK and WHIP
connections to get the value of Lw’. Again the correct location will be the average of the two values.
2. Very High Resistance Leaks: are leaks of greater than 10 Meg Ohms and require the repeated application of Hi-pot
voltages of several thousand volts. Once the leak is less than one Meg Ohm, the burn out box can be used to reduce the
leak to several hundred or less Ohms. As mentioned in previous Bulletins, the “ burn out box” is a DC power supply
with an adjustable output up to 600 or 800 volts with a current capacity of 1 to 3 amps. This type of power supply is
LETHAL, so must be used very cautiously!!!
3. Multiple Leaks: There is no straight forward way of locating multiple leaks. Generally when multiple leaks occur they
are all fairly close together. The best approach is to use any of the described leak locating methods and cut the cable
and check both pieces of cable using the same locating methods and cut again. After all the cutting, be sure to Hi-pot
both lengths of cable, to ensure they are clear of leaks before they are spliced back together.
4. Intermittent Leaks: are leaks that are not always present. These type of leaks typically are noticed during a job, and
later when the cable is brought to the cable shop, the cable tests clear. If the leak does not appear when the cable is
tested at 1,000 VDC, then to get the leak to reappear the cable is spooled back and forth in a number of ways while
watching the ohmmeter to see when the leak occurs. Some shops pass the cable around a capstan, through a post
former or around several sheave wheels. Spooling is done at very low and then at very high tensions. Once the leak
reappears the spooling is stopped and the leak is located using one of the standard methods.
05/2005
Technical Bulletin Number – 006
The plot shown below shows the overall increase in conductor resistance as a tool is lowered in the hole. For this
example the total conductor resistance of a 25,000 foot Dakota Cable, type 7K-464-FTD, is shown as the tool is lowered
in a 20,000 foot well with bottom hole temperatures of 500°F and 300°F.
500°F
350
300
300°F
250
200
0 5 10 15 20
Depth – 1,000s of Feet
d
Ts + (Tb - Ts)
234.5 + Hd
2
(234.5 + Ts)
R=r (L - d) +d
(234.5 + 68) (234.5 + 68)
12/2005
Technical Bulletin Number – 007
The quick procedure for locating the approximate depth of the stuck point, (Ds) is as follows:
• Pull on cable to remove all slack and put the cable under strain.
• Note and record the indicated depth from the measuring device, (D1).
• Note and record the tension in the cable.
• Increase the tension exactly 1000 pounds (4.44 kN) & record the indicated depth, (D2).
• Calculate the depth of the stuck point: Ds = (D1 - D2) / K (1000 feet).
• K is the stretch coefficient of the cable, which is listed in the Wireline Works Catalogue, ft/Kft/Klbs.
• To convert from metres to feet: 1 foot = 0.3048 metres
Cable OD-Inches 3/16 7/32 1/4 9/32 5/16 3/8 7/16 15/32 0.49
K ft / Kft / Klbs 3.0 2.2 1.9 1.6 1.2 1.0 0.70 0.77 0.60
Example
Cable type-Dakota 1-R-322-FAH, 5/16” Mono-cable ; K = 1.2
Cable becomes stuck at an indicate depth of, D1 = 16500 ft.
With the cable under strain the line tension is = 3,300 lbs.
The tension is then increased to 4,300lbs and the indicated depth is D2= 16480 ft.
Ds = (D1 - D2)/K = (16500-16480) / 1.2 ( 1000 ft) = 16,600 feet
In this example the stuck point depth is close to the indicated tool depth, so it is the tool that has become stuck.
Depth Corrections
If a more accurate stuck point is important, then the following factors can be considered:
• The stretch, ( D2-D1) when measured at the truck includes the stretch in the cable from the truck to the well head. A
more accurate method of measuring the stretch is to mark the cable at the well head an then measure the stretch
when the tension is increased.
• If the rig-up distance is known, it can be subtracted from the calculated depth based on measurements of stretch at
the truck.
• For well seasoned cables the stretch coefficient should be reduced by 5%.
• In very deep hot holes the effective value of K can increase by 10%.
• If there are reasons not to increase the tension by 1000 lbs, then just increase the tension by 500 pounds and then
take the value of Ds. calculated using the above formula.
05/2005
Technical Bulletin Number – 008
The breaking strength of cable, listed in the Wireline Works Dakota cables are designed to exceed the catalog breaking
catalog, is the guaranteed minimum strength at which the strength. All incoming armor wire has certified tensile
cable will break when the ends of the cable are prevented strength. In addition Wireline Works routinely tests the wire
from rotating. When a cable is loaded, with no rotation and finished cables to verify the strength.
allowed, the outer armor wires are stressed slightly more than
the inner armor wires. For this reason when a cable breaks Calculating Cable Breaking Strength
with ends fixed, the outer armor wires will always break first EXAMPLE - Dakota Cable type 1-R-322-PH
and the inner armor wires stretch out before they break. ( units-- inches, square inches, psi, pounds, degrees)
D = 0.322 - Cable diameter
Oilfield cables are constructed with two layers of contra- do=0.0445 - Outer armor wire diameter
helically applied armor wires. Under load each layer of wires Do= D - do = 0.2775 - Pitch diameter outer armor layer
develop torque. The torque developed by the inner armor is in
opposition to the torque of the outer armor. The torque di = 0.0445 - Inner armor wire diameter
developed by each layer of armor wires is determined Di = Do - do - di = 0.1885 - Pitch diameter inner armor layer
primarily by the total area of steel in each layer and the Dc= Di - di = 0.144 - Effective core diameter after compression
distance of the wires from the cable center. The outer armor Ni = 12 - Number of inner armor wires
wires are always further from the cable center than the inner
armor and for practical reasons the outer armor layer has a No= 18 - Number of outer armor wires
greater area of steel. The outer armor layer, therefore, Ai = Ni(π/4)di2 = 0.018663 - Total cross sectional area of all inner armor wires
develops much greater torque than the than the inner armor Ao= N0(π/4)do2 = 0.027995 - Total cross sectional area of all outer armor wires
layer. This imbalance in torque can be partially but not
Li = 1.50 - Inner armor lay distance
completely offset by adjusting the lay angles of the inner and
outer armor wires. Lo= 2.50 - Outer armor lay distance
sinαi = πDi / [ (πDi )2 + ( Li )2 ]1/2 = 0.3672
If a cable under load is free to rotate, such as a cable hanging
sinαo = πDo / [ (πDo )2 + ( Lo )2 ]1/2 = 0.3293
in a vertical cased hole, the dominant torque of the outer
armor wires will cause the cable to rotate in such a direction cosαi = Li / [ (πDi )2 + ( Li )2 ]1/2 = 0.9301
as to unwind the outer armor and reduce its stress. As the cosαo = Lo / [ (πDo )2 + ( Lo )2 ]1/2 = 0.9442
outer armor wires unwind, the inner armor wires are forced to αi = 21.54 - Inner armor lay angle
wind tighter and this increases the stress in the inner armor. If
αo = 19.22 - Outer armor lay angle
allowed, this unwinding will continue until the torque
between the layers is equal and when this occurs the stress in P = 0.33 - Poisson’s ratio for plastic
the inner armor is much higher than in the outer armor. When S = 270,000 - Wire tensile strength
a cable is free to rotate or is forced to unwind by improper
operating conditions the breaking strength is significantly Breaking Strength - Ends Fixed
reduced and when it does break, the inner armor will break σF = [ cos2 αi - P(Dc / Di )sin2 αi] / [ cos2αo - P(Dc / Do)sin2 αo ] =0.9521
first. and then the outer armor wires will stretch out before - armor stress ratio, ends fixed
they break. BF = S[ σF ( Aicos αi ) + ( Ao Cos αo ) ]
BF = 11,370 - Calculated minimum
In normal operations, with proper tensions going in and out BF = 11,200 - Catalog minimum
of the well, the lower portion of the cable, if free to rotate
will unwind in proportion to the tension but due to friction in Breaking Strength - Free Rotation
the borehole, there is less unwinding near the surface, so the σR = [ AiDisinαi ] / [ AoDosinαo] = 0.50496 - armor stress ratio, ends free
cable breaking strength at the surface is close to “ ends fixed”
BR = S[ ( Aicos αi ) + σR ( Ao Cos αo ) ]
strength. The breaking strength will be reduced further by
field operations that force the cable to unwind. This includes: BR = 8,120 - Calculated minimum
trying to control pressure with a tight pack-off instead of BR = 7,900 - Catalog minimum
using more flow tubes; wide cable tension variations that
05/2005
Technical Bulletin Number – 009
Drum Crush
The term “drum crush” refers to a cable electrical failures that occur as a result of the cable being crushed, smashed or
distorted to such an extent that the armor wires press and distort the plastic insulation and in some cases cut through the
insulation and contact the conductor. It is possible to have the conductor insulation distorted to such an extent that it
affects the signal transmission characteristics of the cable with out an actual electrical short. These failures are caused by
cables at high tension being spooled over cable spooled at abnormally low tension, cable installed with an incorrect
tension profile or cable that is operated in a manner to cause excessive rotation. For these reasons a more correct term for
this type of failure would be “Cable Crush Failure, ( CCF)”.
CCF, never occurs on the whip end of the cable. Typically the failures are found at a minimum of 4 or 5 layers down and
more commonly deeper than that. Failures can and often do occur in layers of cable that have never or not recently been
off the drum.
An important characteristic of CCF is that the failure frequently does not occur immediately. For a failure to occur the
plastic insulation must cold flow under pressure and this can be a slow process. A CCF condition in some cases may have
been setup several jobs, days or even weeks before the actual failure does occur. It is this time lag that makes it difficult to
always identify the actual cause of the failure.
slowly to avoid over run. The cable can also loose normal tension when any restriction is encountered going in the hole.
When this over run occurs the cable will start back on the drum at lower tension than the subsequent layers. If this
tension differential is too great, it sets up a condition for a CCF. As explained above this failure is usually not immediate
and therefore if a cable has been over run it might be saved by bringing it to a cable shop and have a normal tension
profile reestablished or by operating the cable in a deeper hole very soon after the previous problem. Any other
situation that causes a loss of normal spooling tension coming out of the hole, such as clamping off the cable to correct
a spooling problem or clamping off at a side entry sub, can also lead to a CCF. There are some radical operating
conditions where the friction in the hole and tool are such that a wide variation of the in and out tension can not be
avoid. In these cases special powered sheave or capstans must be used to reduce the tension differential and to avoid
cable crush.
7. One factor in the ability of a cable to withstand cable crush is the “hoop strength” of the armor wires. This is greatly
reduced when the outer armor unwinds and becomes loose. If the end of the cable is free to rotate then the outer
armor will try to unwind in proportion to the tension on the cable. This is the most frequent cause of failures in
pressure cable.
a. The cable should never be spooled out of the hole at a speed greater than a speed that results in a tension greater
than 125% of the static tension at that depth. Higher tensions result in excessive unwinding of the outer armor.
Further, going into the hole the speed should never be less than that speed that maintains a tension greater than
75% of static tension. Failure to follow these rules will cause the cable to progressively unwind the outer armor
setting up a condition for CCF. When cables are operated outside these limits, the cable should be brought into a
cable service center for normalizing, (tightening the outer armor), and post forming. when the outer armor becomes
loose. Examining the whip end of the cable, if you can easily move the outer armor with your finger nail or a small
screw driver, then it is time for service.
b. Coming out of the hole the cable unwinds and going back in the hole the cable attempts to tighten back up. If a
spring centralizer is used going into the hole a swivel head must be used to avoid sever unwinding of the outer armor.
c. The amount a cable unwinds under free conditions, depends not only on the tension in the cable but also the
friction between the armor layers. For this reason seasoned cables with mud and corrosion products between the
armor layers will rotate less and are less subject to CCF. New cables, however rotate very easily and new cable used in
high pressure wells, with grease in flow tubes, must be carefully checked for loose outer armor. It would be good
practice to have a new pressure cable brought to a service center to have the armor tighten after the first 20 or 30
operations and thereafter when the outer armor becomes loose.
d. Alloy cables used in sour gas operations, represent a special problem. The alloy armor does not rust or produce
corrosion byproducts and these cables are normally used with high pressure grease in the flow tubes, so these cables
rotate more freely throughout the life of the cables. These cables MUST be brought into the cable shop regularly for
normalizing and post-forming. Good practice for these alloy cables would be to have the armor tightened every 20
operations throughout the life of the cable.
e. Cables can be forced to unwind when pulled through a tight packer, dragging on any fixed object, run over a sheave
wheel that does not have the proper grove or the sheave and truck are not properly aligned. Any forced unwinding
of the cable further reduces its resistance to CCF.
f. Dakota cables are manufactured with a special, patent pending, compound called TCI, (torque, compression
inhibitor), that is placed between the armor layers. The material results in new cables that have sufficient friction
between the armor layers that a new Dakota Cable will closely act like a seasoned cable and will rotate 50% less
than a typical new cable under similar conditions.
8. In the manufacture of Dakota cables careful attention is paid to the inner armor coverage. Coverage is how completely
the surrounding inner armor wires cover the plastic core. This coverage is maintained between 98% and 99%. This
range of coverage provides the maximum protection to the core to withstand CCF and still provides the necessary gaps
to allow the cable to bend. It is also important that the inner armor wires are spaced evenly around the core. At
Wireline Works the inner armor spacing is carefully controlled and inner armor wires are pressed into the core so that
this spacing is maintained through the final armoring operation. When a CCF occurs the inner armor coverage should
be checked to determine if it was a contributing factor. The inner armor coverage should be checked on a new section
of cable as once the cable shape is distorted the coverage can not be judged.
The cost of cable and more importantly the cost of a cable failure on a job are so great, that the cost of bringing a cable
to a service center to have the armor tightened and the proper tension profile reestablished, is minor by comparison.
When ever a cable has encountered any of the conditions described above where a CCF could result, get your truck to a
service center before there is a failure.
05/2005
Technical Bulletin Number – 010
In field operations the higher tensions and temperature cause several important changes in the cable:
• When a new cable is first lowered in a well, the tension on the cable generates a torque and the cable end needs to
rotate to relieve this torque. If the end is carrying a tool that can easily rotate the cable will spin out hundreds of turns
to relieve this initial torque and become “normalized”. The amount of rotation depends on depth, tension and type
of cable.
• During manufacturing, the inner armor wires are partially embedded into the plastic core by means of pinch rollers or
pre-form rollers. With the high tensions in field operations the armor wires exert an increased radial pressure on the
core causing further embedment in the core resulting in a reduction in diameter. Higher down hole temperatures
soften the plastic which will cause this diameter reduction to occur more rapidly. When the inner armor wires are “fully
embedded”, the diameter of the cable will stabilize, which normally occurs in 20 or 30 operations. In the case of mono-
cables the diameter reduction is only a few thousandths but unless the cable is allowed to rotate it will result in loose
outer armor wires which can accumulate into a “bird cage”.
• When the effective core diameter is reduced due to embedment, the armor wires wrap around this smaller diameter,
resulting in an increase in cable length.
• Cable can also be forced to excessively unwind as a result of using a hydraulic pack-off to control pressure, not enough
clearance in flow tubes, poor truck and sheave alignment or an incorrect sheave groove. Cables forced to unwind have
a reduced breaking strength, are more susceptible to drum crush and loose outer armor wires that can be ”milked” into
a “bird cage”. A typical new cable is more susceptible to all of the problems associated with cable torque and rotation
as there is minimal friction between the inner and outer armor wires. After a number of field operations the spaces
between the armor wires become filled with mud and corrosion byproducts which increases the friction between the
armor layers reducing the problem caused by forced cable rotation.
• During the manufacture of DAKOTA cables a special material called TCI is applied on the inner armor layer to fill the
interstitial spaces between the inner and outer armor wires. This compound not only controls the fluid and gas passage
between armor layers but by the inclusion of sharp particles the friction between the armor layers is significantly
increased, reducing cable rotation. A new DAKOTA cable with TCI will act more like a seasoned cable.
Based on the above explanations, here are a few DO’s and DON’T’s that should be observed when breaking in a
NEW cable:
DO:
• Run in and out of the well at half the normal speed.
• Run .004” clearance in flow tubes.
• Use sheave wheels with the proper grove size.
DON’T:
• Run tools that restrict cable rotation.
• Run in deviated holes.
• Apply any pressure with a hydraulic packer.
05/2005
Technical Bulletin Number – 011
It should be noted that no single method of leak • Measure the voltage between the armor and the
detection is fool-proof. Therefore it is highly conductor at the Collector end, Vc.
recommended that more than one technique be Measure on cable ground
used to provide confidence in the location of
Whip End
the leak. Vc
Collector End + –
Collector End + –
To get started the total length of the cable, L, must Battery
Battery Vb
Vb = 12.635 volts, measured at the cable ends
Leads
Vw = 2.456
Collector End + –
Battery
Vc = 10.179
DMM CHECK: Vw + Vc = 2.456 + 10.179 = 12.635 = Vb
*Measure at cable ends on the conductor
Lw = L(Vw / Vb) = 18,000( 2.456 / 12.635) = 3,498 Ft.
05/2005
Technical Bulletin Number – 012
Breaking Strength
The breaking strength of any Dakota cable can be found on both the Cable Specification Sheet and
in the Catalogue. These can either be found on the website www.wirelineworks.com or call your
Wireline Works Representative to send you physical copies. These values of breaking strength are
theoretical values assuming the cable is in new physical condition, and the cable is pulled straight
without rotating. Dakota cables are regularly tested to verify that the breaking strength exceeds the
catalogue values.
There are many factors which can effect the breaking strength of a cable after it has been in the
field which include:
• Physical wear on the cable which reduces the diameter of the outer armor wires; hence,
reducing the breaking strength of the cable
• Corrosion of the cable will reduce the effective diameter of both the inner and outer armor
wires and again reduce the breaking strength
• H2S exposure can embrittle the steel and drastically reduce its breaking strength, as it bends
over the sheave wheel.
• CO2 exposure will also cause accelerated corrosion
• Excessive rotation of the cable, caused by improper operating tensions or hydraulic packers
can reduce the breaking strength by as much as 30%
• Splices if done properly can withstand loads over 90% of the cables breaking strength.
However they loose much of their strength if put into compression (spudding), and tend to
deteriorate quickly when run over sheaves frequently. Shims used in splicing need to be
inspected regularly for wear.
• Fatigue of armor wires occurs when the cable is “yo-yoed” at high tension. When it is
necessary to “yo-yo” a cable, then at every 10 or 20 cycles the upper sheave wheel or truck
should be moved so that a fresh section of cable is passing under the measuring head and
over the sheave wheels.
• Physical Damage such as kinks, armor scratches, dents, etc. to the cable can result in a much
reduced breaking strength
Operating Strength of a cable is expressed as the percent of ends fixed breaking strength (BS) of the
cable. For GIPS cables Wireline Works recommends an Operating Strength of 60% of the breaking
strength. Sour service cables should not normally be operated over 50% of there breaking strength.
The cable will operate an unlimited number of tension cycles to its Operating Strength without
permanent damage to the cable. When the cable is stressed to above the operating strength, there
may be permanent irreversible damage. Above the recommended operating strength there can be
plastic forced out of the gaps in the inner armor resulting in less electrical insulation between the
conductor and armor. There may also be additional elongation of the cable and when tension is
released “Z” kinks may begin to form in the copper conductor. If these high tensions are repeated it
will lead to electrical failure.
05/2005
Technical Bulletin Number – 013
The more stable state of Hydrogen is H2. However the reaction we are discussing results in a large percentage of atomic
hydrogen which is extremely small. The molecules are so small they can diffuse and accumulate within the crystal
structure of steel. As the accumulation continues the atomic Hydrogen seeks a more stable state and combines with
another H forming H2, which is twice as large as H. In this larger state it does not diffuse back out of the structure as
easily as it went in. This packing of Hydrogen in the steel crystal structure generates an internal stress and in time can
lead to micro stress cracks in the steel. Even before there is advanced stress cracking, the accumulation of Hydrogen in the
steel crystals results in the crystals elements being unable to move internally, causing the steel to become extremely
brittle. A strand of GIPS wire exposed to sufficient Hydrogen Sulfide can result in the steel wire breaking like a glass rod
when bent.
After the Zinc has been used up in the chemical reaction the H2S continues to react with the Iron. This action can takes
place faster in the presence of water. If the well fluid is mostly oil, then the reaction of dissolved H2S on the cable is
slower but there are no safe or unsafe standards.
The presence of CO2 where there is water present results in the formation of Carbonic acid. This acid environment seems
to accelerate the action of H2S on iron, but again the published data is not complete enough for any standard guidelines
to be complete. Another catalyst occurs when the carbonic acid etches the steel surface providing additional surface area
exposed to the effects of H2S. Field experience has shown that when CO2 and H2S are both present in bore hole fluids
that include water, the embrittlement of steel is much faster and more severe. In addition to CO2, the well pressure,
temperature and the total time of exposure, are factors that can radically effect the degree of embrittlement.
The National Association of Corrosion Engineers has published a guide line for the use of GIPS in wells containing H2S:
“Maximum H2S in ppm for GIPS = (50.000 / Well pressure, psi)“
Example: Well pressure = 1000 psi , GIPS can be used with H2S concentrations up to 50 ppm.
The above guidelines are very general and what is safe depends on a number of other factors. The nature of H2S
embrittlement is that up to a point the embrittlement is reversible without permanent damage to the cable. Over time
the H2 will diffuse out of the wires and the cable will return to normal.
If a standard cable has been exposed to H2S and has successfully come out of the hole, you need to make a quick check of
the armor wire by bending a wire around a rod (2 to 3 times the wire diameter) 5 complete wraps. Unwrap the wire, if it
does not break then it is likely there has been no permanent damage by micro fracture, and the cable can be saved. The
H2 in the cable armor will ultimately diffuse out of the armor. If a wire breaks in this wrap test but there were no outer
armor wires broken coming out of the hole, then it is best to let the cable sit for a few days to allow the H2 to diffuse out
of the wires. Do not use this cable in an H2S well again until it has made several trips in normal wells and the wrap test
has passed.
Although not recommended, if you are considering running a standard, plow steel, cable in a well containing H2S, then
here are several pointers:
• Run an older cable, less Zinc.
• Use plenty of the pressure control grease, Liquid “O” Ring 4-I, ( or equal).
• Use the National Association of Corrosion Engineers guide lines, for allowable H2S.
• Use larger diameter sheave wheels
• No hydraulic pack off pressure .
• Use more flow tubes with greater clearance, 0.004”
• Get in and out of the hole as quickly as possible, within correct operating speeds.
If your operating conditions do not fall within these guidelines, then an alloy cable should be used. H2S and alloy
armored, MP35 & stainless steel, cables will be covered in another technical bulletin.
05/2005
Technical Bulletin Number – 014
With AC voltages there is always the threat of corona Now consider the heating effect of the cable on the drum.
discharge that can deteriorate the plastic insulation. A Power = (Current)2 x Resistance = Current x Current x
complete treatment of corona problems is very complex and Resistance
includes effects of temperature, pressure, conductor size, Power (watts) dissipated in drum cable, Pd = (Imax x Imax) x
frequency as well as insulation thickness. A simplified (4.0 x Ld) = (2.6 x 2.6) x (4.0 x 5) = 135 Watts. In this example
conservative formula, ( NTIS), for calculating the volts per mil the heat from 135 watts, a typical light bulb, dissipated in the
for the onset of corona for this cable is: 500 pounds of cable on the drum plus the steel drum will have
little effect on the cable temperature.
E =0. 868 / d[ log(D / d)]
Where: E – Volts / mil for the onset of corona Example #2:
d – diameter of conductor – inches Lh =5; Ld = 20; Vb = 700; Vmax = 1200; Calculate Imax
D – Diameter over insulation – inches
E =0. 868 / 0.059[log(0.108 / 0.059)] = 56 Volts / mil, is where Rc = (4.0 x 20) + (4.0 x 5) + (4.4 x 5) = 122 Ohms
corona could start to be a problem. Vd = 1200 – 700 = 500 Volts
By rating Dakota Cables at 50 Volts / mil, corona should never Imax = 500 / 122 = 4.1 amps
be a problem.
Now consider the heating effect of the cable on the drum
Current Pd = (Imax x Imax) x Rd
The maximum current in a cable is determined by the Rd = 4.0 x Ld
allowable voltage drop and the heat generated by the current Pd = (4.1 x 4.1) x (4.0 x 20) = (16.8 x 80) = 1,344 watts.
in the cable that is on the drum. Unless the maximum current
is on continuously for several hours, the maximum current will This is nearly 10 times the wattage of the other example but
normally be limited by the maximum voltage. still not a serious problem for short periods. 1,344 Watts is
about the power of a kitchen “hot plate”. It would take a very
Using a 25,000 ft. 1-R-224-FTH cable as an example, the long time to heat up a 2,000 pound cable on the drum plus a
maximum allowable current can be calculated using the values steel drum with a kitchen hot plate. This example does
of resistance and voltage rating listed in the catalog. however, illustrate that the problem of maximum current
• Ld = cable length on drum (kft); becomes more serious when most of the cable is on the drum.
• Lh = cable length in bore hole (kft); There are too many variables to calculate the maximum
• The conductor resistance, of the cable on the drum is: allowable time limit, including: ambient temperature, layers of
(4.0 x Ld) Ohms (from Wireline Works Catalogue) cable on the drum, air circulation, spooling tensions, etc.
• The armor of the cable on the drum has no resistance as it Experience has indicated that cable on the drum can tolerate,
is all shorted on its self and the drum. without damage, 1/10 watt per foot for periods of 24 hours. In
• The conductor resistance, of the cable in the hole is this example that would be 1,250 watts.
(4.0 x Lh) Ohms .
• The armor resistance, Ohms, of cable in the hole is
(4.4 x Lh) Ohms (from Wireline Works Catalogue)
08/2005
Technical Bulletin Number – 015
Comparing 7/32” Standard GIPS Comparing 7/32” Alloy, Stainless & MP35
15 X15 Construction The very high costs of alloy cables and their resistance to
• Larger outer armor wires wear longer. corrosion makes the decision on the best armor package
• Larger outer wires are stiffer and therefore easier to different. The primary consideration is on obtaining maximum
thread through flow tubes. cable life. With these armor materials the cost of the frequent
• Larger outer wires do not become “crossed over” as cable service is small compared to the cost of the cables.
easily during re-heading.
• Smaller inner wires will corrode to brittleness faster, 15 X 15 Construction
reducing cable life. • Larger outer armor wires will wear longer.
• The larger Torque Factor means this type of cable, • Alloy wires do not corrode, so smaller inner armor
especially when new, will try to unwind more , which wires are not a problem.
can result in loose outer armor wires. • With no corrosion of the armor wires, the normal
• The outer armor of the 15 X 15 construction will corrosion products, that inhibit cable rotation, are not
require more frequent trips to a service center for present between the armor wires, so the cable under
“normalization” and post forming, to tighten the load will unwind more, loosening the outer armor.
outer armor. • This cable construction, with a high torque factor and
low rotational resistance, requires frequent trips to the
12 X 18 Construction service center to have the outer armor tightened and
• Larger inner armor wires will not corrode and become post formed.
brittle as fast.
• The smaller Torque Factor means the cable will not 12 X 18 Construction
unwind as easily, so the outer armor will stay tight • The lower torque factor means this construction will
longer, requiring less service. unwind less than the 15X15 construction and will
• The outer and inner armor wires are the same require less frequent service.
diameter making a better head termination. • The same diameter armor wires make a better
head termination.
• This construction would be favored for use in
extremely remote locations where cable service is not
readily available.
09/2005
Technical Bulletin Number – 016
The cable length is the primary method of determining the depth of If the original length of the cable, L is 25,000 feet then the increase
a tool in open hole operations. In using either magnetic marks or of the inner armor length, li is:
measuring wheels, accurate depth measurements depend on known • li = ( 25,000 )(0.0044) = 110 feet
stretch characteristics of the cable. There are two types of cable
stretch; elastic and inelastic. The outer armor in contact with the inner armor layer experiences
the same reduction in diameter but this is a smaller fraction of its
Elastic stretch is an elongation of the cable that is directly original diameter, so the elongation, lo, of the outer armor is less
proportional to the tension applied and when tension is removed than the inner armor:
the cable returns to its original length. This is a characteristic of a • lo = L[(Dc’-Dc)/( Dc+2di +do)]X[Tan Ao]^2 =
“seasoned” cable. Since elastic elongation or stretch is proportional L[(0.008)/(0.243+2*0.0535+0.067)](Tan 19)^2 =L[ 0.0023]
to tension, the elastic stretch can be calculated from the measured • lo = (25,000)(0.0023) = 58 feet.
tension on the cable.
It is conventional cable manufacturing practice to embed the inner
Inelastic stretch is a permanent elongation of a cable that occurs armor in the core to “season” it by subjecting the finished cable to
when sufficient tension is applied to a new cable and the cable a prestressing operation. This operation typically applies a tension
remains elongated after the tension is removed. In the manufacture of about 1/3 of the cable rated breaking strength as it passes
of new cables when the inner armor is applied to the core there are between two capstans. The tension in the cable is lost as it leaves
voids between the underside of the inner armor and the core, the final capstan and goes on the shipping reel.
figure 1. After adequate tension is applied to the cable the inner
armor will embed into the plastic core material, figure 2. When the If the tension in this standard prestressing operation has embedded
inner armor wires are fully embed, essentially all inelastic stretch the inner armor in the core, then when the tension is removed, the
will have occurred and the cable is “seasoned”. A seasoned cable inner armor, now wound around a smaller core, would like to be
will have predictable elastic stretch characteristics as long as it is not longer than the outer armor as the above calculations demonstrate.
subjected to tensions over 60% of rated breaking strength. Because of the friction between the inner and outer layers the
outer armor can not shrink back over the inner armor . Since the
With full embedment there is also a permanent change in the shorter outer armor has much greater strength, it will push back on
effective cable core diameter. In manufacturing a cable the amount the inner armor, which will reduce the pressure on the core.
of this diameter change is important, so that after full embedment
has occurred, the finished cable, will have the correct outside The nature of plastics is that they have a memory and though the
diameter. The desired final effective diameter, Dc, of the core is prestressing operation may have initially fully embedded the inner
easily calculated: armor into the plastic core, when the inner armor pressure is
• Dc = D – 2do – 2 di reduced the core will start to recover its original shape. When this
D = required finished cable diameter occurs, the cable is not fully seasoned and will have excessive
• do & di = outer and inner armor wire diameters inelastic stretch.
The initial diameter of the core required for full embedment can be Wireline Works Inc. has a proprietary cable seasoning process
closely approximated by: known as “Compound Pre-StressingTM (patent pending). With this
• Dc’ = [ (Dc+di)^2 – (N/2Cos Ai )(di)^2]^1/2 procedure the inner armor, core assembly is first pre-stressed with
N = number of inner armor wires sufficient tension to fully embed the inner armor wires into the
• Ai = lay angle of inner armor wires core. After pre-stressing the inner armor, the outer armor is then
applied to the already embedded and elongated inner armor. This
Using the Dakota slammer cable type 7-Y-484 as an example, the permits the outer armor to add rather than reduce the pressure on
required finished effective core diameter is: the core ensuring a fully seasoned cable.
• Dc = 0.484” – 2 X 0.0670” – 2 X 0.0535” = 0.243”
To allow for full embedment the initial core diameter required is:
• Dc’ = [ (0.243” + 0.0535”)^2 –(16 / 2Cos22 )( 0.0535”)^2]^1/2 Figure 1 Figure 2
= 0.251”
• Dc’- Dc = 0.251 - 0.008” is the core compression.
02/2006
Technical Bulletin Number – 017
Armor Coverage
Armor coverage is a very important property of A cable under load generates a pressure on the core and if the
electromechanical wireline cables. Proper design and armor inner armor wires are not close enough (low coverage %), the
coverage permits cables to operate under tough operating plastic insulation can be squeezed out between the armor
conditions of high temperatures and high tensile loads. The wires. With an inner armor coverage over 98% cables can
term “armor coverage” refers to how close the armor wires operate under rated operating conditions of temperature and
are together. If a layer of armor wires were to have 100% tension without the plastic insulation being squeezed out in
coverage, it would mean that all of the armor wires in that the gap between the inner armor wires. When a cable is
layer were touching their adjacent wires. subjected to high downhole temperatures and excessive
tension some plastic insulation may be forced out between
There are a number of very important reasons why the armor the inner armor wires, even when the armor coverage is in an
coverage of both the inner and outer armor layers must be acceptable range. Excessive operating conditions, stuck tools,
carefully controlled. If the coverage on either layer were and pulling out of the weak point can often create this
100%, the cable would be so stiff it would not be able to phenomena. In these cases it is good operational practice
bend around a sheave wheel without forcing one of the wires to cut back on the cable end to be assured of full
out of the layer, creating a high wire. If the armor coverage is electrical insulation.
too low a premature electrical short could result under high
temperature and high load conditions. Outer Armor Coverage acceptable range: 96.5% to 98.5%,
ideal is 97.5%.
The range and requirements for the coverage of the inner and
outer armor layers is quite different. To calculate coverage The importance of allowing a lower coverage on the outer
there are at least 4 good formulas. In the case of oil field armor is to give the cable sufficient flexibility to wrap around
electro mechanical cables (wirelines), there is little difference standard sheave wheels. On cables used in high pressure
in the calculated coverage values using any of these formulas. operations it is important to keep the outer armor coverage
The formula that has been accepted by the major oil field on the high side to better control pressure in the flow tubes.
service companies and Wireline Works is:
The outer armor being applied over the inner armor can not
di be embedded to control spacing. For this reason, new cables
% Ci = x100
π
(Dc - 2 do - di) Sin[ Ni ] Cos [αi] when they are first spooled may cause the outer armor wires
to shift around resulting in what appears to be an excessively
wide gap. This is perfectly normal. When a new cable has a
do dark protective grease applied, this grease will collect in this
% Co = π
x100 wider gap giving an appearance that the cable is “gappy”.
(Dc - do) Sin[ Ni ] Cos [αo]
After a few runs in the hole the outer armor will equalize the
gap between the adjacent armor wires and the appearance of
Ci = Percent coverage of the inner armor layers a “gappy” cable will disappear.
Co = Percent coverage of the outer armor layers
di = Diameter of the individual inner armor wires Sample inner armor coverage calculation:
do = Diameter of the individual outer armor wires Wireline Works 1-R-288-TH
Ni = The number of wires in the inner armor layers
No = The number of wires in the outer armor layers di
Ci = (100);
αi = the lay angle of the inner armor wires π
(Dc - 2 do - di) Sin[ Ni ] Cos [αi]
αo = the lay angle of the outer armor wires di = 0.0405;
Dc = Finished cable outside diameter do = 0.040;
Dc = 0.288;
Inner Armor Coverage acceptable range: 97.5% to 99.5%, Ni = 12;
ideal is 98.5%.
π
αi = 19.5
The importance of keeping the inner armor coverage as high 180
as possible is to contain the plastic insulation covering the Ci = 99.1%
conductor. During cable manufacturing the equal spacing
between the inner armor wires is carefully controlled and the
inner armor wires are partially embedded in the plastic
insulation to preserve this equal spacing. This equal spacing is
important to spread the coverage equally between each wire
thus minimizing the gap at any one location.
06/2006
Technical Bulletin Number – 018
Wireline Torque
Electromechanical Wireline Cables are designed and If a cable has been run into a well bore with any condition
manufactured to minimize the inherent torque in the cable, that may prevent free rotation or cause torque imbalance,
see Technical Bulletin “Minimizing Cable Torque during the cable will need attention to keep it from failing. The
Design". However, all cables inherently have some torque standard approach is to normalize the cable to be sure the
and will develop a need to rotate relative to the tension outer armor is tight. If you feel or see your cable trying to
applied during operations. This is generally not a problem curl up while laying on the ground during rig ups it has
as long as the cable is allowed to rotate freely. In today’s excessive torque. Running the cable in this condition will
complex oilfield there are a lot of variables that affect and risk breaking, or getting a strand cross-over which can cause
restrict cable rotation. If the cable is not allowed to rotate the cable to strand at deeper depths. Remember every bird
in proportion to tension, torque build up will begin to occur cage you see is caused by getting too much slack in one
in certain areas of the cable depending on what is location of the cable. It is a good idea to rehead, when
restricting it from rotating properly. For example, the pack- possible, with inner armor strands on the cables that are
off will restrict the cable from rotating and the cable will using grease heads because they are lubricated and can
accumulate torque as the cable passes through pack-off. torque up relatively easily.
This results in torque build up and loose outer armor.
Lack of tension means low rotation is required, and high
Cable rotation can be restricted and torque imbalance may tensions means a lot of rotations required to prevent torque
occur from the following operations: build up. If you come out of a well with very high tension
• Deviated or crooked well bores. and torque in the cable, the next time you go into a well
• Going in and out too fast and not observing the 80/120 with very little tension, there will be a lot of torque in the
tension rule, (see Technical Bulletin #9). cable wanting to be released. Armor separation, high
• Pulling out of a well at high speeds that result in strands, or bird caging are not the only issues to worry
excessive tension. about with torque build up, you may also experience early
• Centralized and decentralizing tools. pullouts, cable breaks, and excessive compression on the
• Heavy and viscous drilling mud and completion fluids conductor which can short out the cable. The more you
affect the tension of the cable. understand the affects of torque the better off you are in
• Grease heads or pack-offs used to wipe or preventing cable failures and/or well site disasters.
control pressure.
• Pulling out of a rope socket under high load conditions. The torque generated at maximum working load for
• Low fluid bypass conditions. standard cables has been calculated as follows:
Field experience has shown that almost always loose outer TYPE Z-224 R-224 R-288 R-322 R-380 R-425
armor is caused from the torque imbalance resulting from LOAD
improper running conditions. During the seasoning or (pounds) 3360 3360 6000 6720 8600 11700
breaking in period for new cables there will generally be TORQUE
some areas in the cable that become loose. These areas do (Inch-pounds) 55.5 40.7 93.5 116.7 176.5 268.3
not cause problems under everyday use; however, it would
be good insurance to normalize (tighten loose areas) a
standard GIPS cable after 20 to 30 runs. This would tighten
any loose outer armor that may have occurred due to the
core embedment of a new cable.
06/2006
Technical Bulletin Number – 020
Cable Rotation
By design, wireline cables develop torque when subjected to increase with cable speed coming out of the hole resulting in
load, see Technical Bulletin “Minimizing Cable Torque During additional unwinding revolutions.
Cable design”. The load on the wireline cable is a result of the
weight of the tool, the weight of the cable and any dynamic Standard Wireline Works Cable Rotation
friction due to running conditions. If the tool end of the cable is Nf– Number of Revolutions per 1000 feet per 1000 pound
free to rotate, the cable will try to rotate to reduce this torque. tension cable end free to rotate
All cables used in oil field service operations are built with the TYPE Z-224 R-224 R-288 R-322 R-380 R-425
torque of the outer armor dominant over the opposing torque Nf 83 48 22 17 10 7
of the inner armor. To balance the torque the cable will unwind
in a direction to loosen the outer armor, which will tighten the The above calculations represent the possible rotation of a
inner armor. If the cable is free to rotate, this unwinding or typical new cable. As a cable becomes “seasoned “ it will rotate
rotation will continue until the torque in the inner armor equals less with tension changes. A “seasoned” cable is one in which
the torque of the outer armor. The number of revolutions, Nf the outer armor wires have dug into the Zinc of the inner
(per 1000 ft per 1000 lb), that the end of the cable will make to armor wires and mud plus corrosion by products have collected
equalize the torque can be calculated as follows: between the armor layers add to the friction between layers
reducing the amount of cable rotation. The amount of this
Nf = 48 x 106 (cd – doa) (– cd + dia + 2 doa) initial new cable rotation has been reduced in Wireline Works
cables by including a material called TCI (Torque Compression
dia2 (cd – 2 (dia + doa)) nia pr sin3 (α ia) + dia2 (– cd + dia + 2 doa) nia cos2 (α ia) sin (α ia) + Inhibitor) Technical Bulletin #10, between the armor layers. TCI
contains materials that increase the friction between the armor
doa2 noa sin (α oa) (cd – doa) cos2 (α oa) + (2 (dia + doa) – cd) pr sin2 (α oa)
layers, reducing the rotation of new cables, so new cables will
perform more like “seasoned” cables.
dia2 doa2) nia noa π2 ym ((doa – cd) cos (α ia) sin (α oa) – (cd – dia – 2 doa) cos (α oa) sin (α ia))
06/2006
Technical Bulletin Number – 021
At their melting point temperature crystalline materials The pressure on the core , as a function of cable tension, can
continue to absorbed heat, called heat of fusion, with out be calculated. The equation is rather complicated but
changing temperature until all the material has completely evaluating it for different cables and tension will illustrate
changed state. The temperature will then again rise as heat the importance of special testing to qualify the temperature
is added. rating of a plastic.
07/2006
Technical Bulletin Number – 021ii
Core pressure is most important on the tool end of the cable point pull out tensions (POT), that would be used with
where the temperature is the highest. The maximum tension standard cables operating at a depth of 20,000 feet and a
in the cable at the tool end is the weak point pull out tool weight of 300 pounds are as follows:
tension. The calculated core pressure, cp, at typical weak
These calculations show that under normal operating wires as they are wrapped around the plastic core before the
conditions the pressure on the core from the tool weight is assembly enters the closing dye. The closing dye and
1200 psi or less. When a cable is manufactured with the following pinch rollers press the evenly spaced armor wires
correct inner armor coverage, the core plastic will not be into the plastic core to insure they will stay evenly spaced
squeezed out at these core pressures at the maximum rated during subsequent manufacturing operations (as shown in
temperature of the cable. If on the other hand the tool the picture below).
becomes stuck and it becomes necessary to pull out of the
rope socket, then the resulting 5,000 psi core pressure is likely
to squeeze the core plastic out between the inner armor
wires if the temperature is high enough. When a tool
becomes stuck in a hole at or near maximum rated cable
temperature, then after pulling out of the tool ,it can be
expected that there will be some plastic squeezed out and it
will be necessary to cut back the cable.
07/2006
Technical Bulletin Number – 022
Sheave Selection
There is probably more material available on sheave selection In addition to the two rules listed above there is a formula
than any other piece of cable equipment. By summarizing and commonly used to determine the safe minimum sheave
analyzing all this data it will give the operator greater choice in diameter for different working loads. This can be useful in
judging the proper size sheave for an operation. shallow operations where the maximum tensions, Tmax, are low
and therefore the cable can be operated on smaller diameter
There are two important characteristics of sheaves that must be sheaves without damage to the cable or reduction of cable life.
considered. These are the sheave groove and sheave diameter. This formula for minimum Sheave Diameter, SD, is:
Of these two, running a cable with an improper groove shape
can do more damage to a cable faster than running with the N= Number of outer armor wires, d = diameter of outer armor wires - inches.
wrong diameter. Correct sheave groove shape and size is more BS = Cable breaking strength - Klbs, Tmax = Maximum operating tension – Klbs
important when running multi-conductor cable, as the core is
easily deformed and the thin conductor insulation can be SD = [ 80(Tmax / BS) + 20 ][ d(N/2.8 + 1)]; - in ( Sheave Diameter )
damaged more easily.
For example: Wireline Works Cable type: 1-R-322 operating with the maximum
Sheave Groove tension, never over 3.0 Klb
• The groove of a new sheave should BS = 11.2 Klb ; Tmax = 3.0 Klbs ; d = 0.0445; N = 18
have a diameter 5% greater than the
Dc cable diameter. SD = [ 80(3.0 / 11.2) + 20 ][ 0.0445(18 / 2.8 + 1) ] = [ 41.6 ][ 0.0445(7.43) ] = 13.75 in
• Cables should not be run over sheaves if
the sheave groove diameter is 10% Operating under low tensions conditions, the minimum
Ds
greater than the cable diameter. recommended sheave diameter, using this formula, for a 1-R-322
135° to 150° • The sheave groove should be machined cable would be 14” compared to an 18” sheave diameter for
to support from 135 to 150 degrees of operating at maximum rated loads.
the cable diameter.
• Sheaves should NEVER be used on 2 When a cable, under load, is bent around a sheave the armor
different diameter cables wires experience a bending stress in addition to the stress from
the load. The smaller the sheave diameter, the higher the
Sheave Diameter bending stress. It is this combined stress that is the main factor in
There are two rules of thumb that are published in cable establishing the minimum sheave diameter. When this combined
literature that indicate the minimum sheave diameter that stress exceeds the yield strength of the wire it will result in
should be used for operating a cable up to its rated Maximum loose outer armor wires. When this combined stress exceeds the
Working Load. The first rule states that the minimum sheave tensile strength of the wire, the wire and possibly the cable will
diameter, SD, should be 60 times the cable diameter, D, and the break. Using the above recommended or larger sheave sizes will
second rule states that the minimum sheave diameter should be avoid such failures.
400 times the outer armor wire diameter, d.
Sheave Alignment
Wireline Cable Cable Outer Wire Sheave Sheave It is important that proper sheave alignment is attained during
Works Cable Diameter Diameter Diameter Diameter Diameter well site set up. When the sheaves are not properly aligned, the
Type D - inches D - inches d - inches SD= SD= cable will attempt to “crawl” up the sides of the sheave wheel
60 x D - inc. 400 x d - in grooves. This action can result not only in distorting the sheave
1-R-100 1/10 0.101 0.014 6.1 5.6 grooves but can also introduce additional torque in the cable.
1-R-125 1/8 0.125 0.0175 7.5 7.0
The materials used in the construction of sheaves has changed
1-S-185 3/16 0.185 0.0358 11.1 14.3 over the years. The most popular sheaves are now the
1-S-207 13/64 0.207 0.0390 12.4 15.6 “Composite Sheaves”. These composite sheaves have become
1-Z-224 7/32 0.224 0.0358 13.5 14.3 standard with most major service companies. These sheaves have
1-R-224 7/32 0.224 0.0310 13.5 12.4 the wheels and guards manufactured from synthetic materials,
1-R-258 1/4 0.258 0.0358 15.5 14.3 which has resulted in a 40% reduction in the weight. When
manufactured, these sheaves have the correct groove size and
1-R-288 9/32 0.288 0.0400 17.3 16.0 shape to properly support the cable. In use however the
1-R-322 5/16 0.322 0.0445 19.3 17.8 composite sheave groove can be quickly damaged from poor
1-R-380 3/8 0.380 0.0525 22.8 21.0 sheave alignment.
1-R-425 7/16 0.425 0.0585 25.5 23.4
7-Y-380 3/8 0.378 0.0525 22.7 21.0 Cable with Splices
In running cables with complete splices it is extremely important
7-Y-428 7/16 0.428 0.0585 25.7 23.4 that the sheaves have the proper groove shape to support the
7-K-464 15/32 0.464 0.0495 27.8 19.8 cable. Spliced cables should always be run using the largest
7-Y-474 Slammer 0.474 0.0655 28.5 26.2 sheave size available with the proper groove shape.
7-Y-484 Slammer 0.484 0.0670 29.0 26.8
09/2006