Multicalor 700.1 MD Multicalor 800.1 MD Multicalor 1000.1 MD Multicalor 1200.1 MD
Multicalor 700.1 MD Multicalor 800.1 MD Multicalor 1000.1 MD Multicalor 1200.1 MD
MODELS
GASTEC
Multicalor 700.1 MD
Multicalor 800.1 MD
Multicalor 1000.1 MD
Multicalor 1200.1 MD
Light oil / Natural Gas 300 mbar
LB1360
27.05.2004
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
WORKING FIELDS
mbar 36
34
32
30
M
28
ul
Backpressure in combustion chamber
tic
26
al
or
24
12
M
ul
00
22
tic
.1
al
20
M
or
D
M
10
18
ul
00
tic
16
.1
al
M
or
14
D
80
12
0.
Multicalor 700.1 MD
1
M
10
D
8
6
4
2
0
-2
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 kW
Burner output
OVERALL DIMENSIONS
A
E D - D1 B C
L
I
F
SUNTEC
M
O
G
D = Short head
D1= Long head
H
MODELS A B C D D1 E F G H I L M N O
Multicalor 700.1 1215 585 630 570 - 1420 420 800 480 460 460 M20 195 232
Multicalor 800.1 1285 655 630 570 - 1420 420 800 480 460 460 M20 195 232
Multicalor 1000.1 1315 685 630 570 - 1420 420 800 480 460 460 M20 195 232
Multicalor 1200.1 1425 795 630 570 - 1420 450 800 480 460 460 M20 195 232
pag.2
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
ELECTRICAL CONNECTIONS
All burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral for
auxiliary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors on
burner as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtai-
ning in the country in question.
the air servocontrol in approximately 30 seconds time. When the servocontrol is fully open, 0 - STOP
LIGHT-OIL
a signal to the electronic control unit starts the 66 seconds pre-purge cycle. At the end of 12 -- GASOLIO
GAS 0
the prepurging time, the air servocontrol gets to the Low Flame position so that burner
ignition is ensured at min. output. Simultaneously the ignition transformer receives voltage
and after 3 seconds (pre-ignition) opens the pilot gas valve. Fuel flows to the combustion head and ignites. Two
seconds after pilot gas valves have opened, the ignition transformer is excluded from the circuit. In case of no igni-
tion the burner goes to lock-out within two seconds. After 6 sec. open the working gas valve, governed by the gas
firing butterfly valve.Now the burner is operating at the min. firing rate (about 30% of the max. firing rate). The air
servocontrol runs at the Low Flame position and in case the temperature control has to be set at the max. output it
goes to a fully open position of air damper and butterfly valve. During the burner-off periods the air damper closes
up fully.
NOTE:
ALL SAFETY DEVICES (AIR PRESSURE SWITCH, MINIMUM GAS PRESSURE SWITCH, GAS SOLE-
NOID VALVES AND GAS GOVERNOR) SHALL BE DULY SEALED AFTER CALIBRATION AND BUR-
NER START UP BY ECOFLAM’S TECHNICIANS.
pag.3
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
Gas valve
Valvola gas
The control box starts the burner t5 t6
Consenso
fan, to carry out the prepurging of min./max.
Min/max capacity
potenza
enabling device
the combustion chamber, and 100%
Serranda aria min
cheks the vent air pressure through Air damper 0
the air pressure switch. At the end Gas damper
Serranda gas
of prepurging, the ignition tran-
Rivelazione
Flame detector
sformer cuts-in and generates a di fiamma
pag.4
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
AIR ADJUSTMENT
--
+
Part. 1
Part. 3
--
SELECTOR
COMMUTATORE
AUTO +
Part. 2
0
0 = operating
bloccaggio elements locked
degli apparati per ilin an intermediate
position
funzionamento in una posizione intermadia
= operation on maximum
funzionamento capacity
alla massima potenza
= operation
funzionamento alla minima
on minimum potenza
capacity
AUTO =automatic
funzionamento automatico
operation
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas
flow, as established by analyzing the combustion process.
- +
pag.5
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
50
35
30
N
25
ADJUSTMENT OF THE AIR PRESSURE SWITCH M
2,5
5
20
10
15
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1. I
- Start the burner and keep in low flame running, while checking that combustion is cor-
rect. Through a small cardboard, progressively obstruct the air intake until to obtain a L
CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connected to pressure
port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the air pressure switch
adjustment value of the air pressure switch until to have the burner lockout. Remove the
2,7
2,4
3,0
2,1
1,8
obstruction from the air intake, screw on the cover C and start the burner by pressing the D
1,5
C 0,4
1,2
control box rearm button. 0,6
0,9
A
Note: The pressure measured at pressure port E must be within the limits of the pressu- H
G
re switch working range. If not, loose the locking nut of screw F and gradually turn the E
B
same: clockwise to reduce the pressure; counterclockwise to increase. At the end tighten the
locking nut. F
IONIZATION CURRENT
Microamperometer The ionization current is checked by inserting a microam-
Microamperometro LANDIS
meter with an end of scale of 50 µA (d.c.) in series with
full scale
fondo scala1000 µA
1000µA LFL 1.622
the ionization probe. A faulty position of the electrode
PHOTORESISTOR
Fotocellula 22 23 can lead to a reduction in the ionization current and cause
a safety cut-out of the burner due to a flame detection fai-
lure. In this case, check the position of the electrode, its
electric connection and the earthing of the burner. The
min 70 µA ionization current is normally > 20 µA.
pag.6
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
HYDRAULIC CIRCUIT
1 - Hose
2 - Oil filter
3 - Oil cock
A - Suction VL
R - Return
VS - Safety oil valve
VL - Working oil valve VS
VR - Return oil valve
PR - Oil pressure switch A
R
VR PR
1 2 3
pag.7
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
pag.8
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
pag.9
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
pag.10
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
5 ÷ 6 mm
B A - Reset key
G B - Operating lamps (orange=light-oil; green= gas)
C - Selector switch:
E K6
0 = Loking of devoices for operating at intermediate outputs
C OIL GAS AUTO
= Operation at max. output
PGM EXIT
MAINTENANCE
YEARLY CHECKS
The burner’s periodical check (firing head, electrodes etc.) must be carried out by authorised personnel one or two times per
year, depending on the utilisation. Before going on with the maintenance controls of the burner, it should be advisable to check
its general conditions, according to the following steps:
Unplug the burner; close the fuel cock; shut down the gas supply; remove burner’s cover and clean the fan and air intake; clean
the firing head and check the electrode’s position; reassemble all the parts; check the connection’s sealing; check the chimney;
start the burner and check the combustion flue (CO2 = 9.5 ÷ 9.8; O = lower than 75 ppm).
The electric system is duly powered and the burner is plugged in.
The gas pressure must be the suitable one and the gas cock open.
The control devices must be properly connected.
When all the above conditions are met, start the burner by pressing the lockout enable pushbutton.
Check the burner’s cycle.
THE BURNER RUNS THE PREPURGING AND SWITCHES TO LOCKOUT AT THE END OF CYCLE:
Check the fan and the air pressure.
Check the air pressure switch.
Control box faulty. Ignition transformer faulty.
Check the ignition cable. Electrodes are dirty or in wrong position.
Nozzles are clogged or worn. Filters are clogged. Light-oil pressure is too low.
Combustion air’s flow rate too high related to nozzle output.
THE BURNERS IGNITES BUT SWITCHES TO LOCKOUT AFTER THE SAFETY TIME:
Check phase and neutral for a correct connection.
Check gas solenoid valve.
Check the position of ionisation probe and its connection.
Check the control box.
Check nozzles (clogged or worn).
The photoresistor does not detect the flame.
The filters are clogged. Light-oil pressure too low.
Combustion air’s flow rate too high related to nozzle output.
pag.12
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
Reduce power
CLOSE/1st Stage Manual operation
Two-stage operation
Programming key
PROGRAMMING LEVELS
Normal display
min 2s
PGM PGM PGM
User Level
PGM
min 2s
PGM PGM Exit
Parameters level
PGM
min 2s PGM PGM
Configuration level
PGM
pag.13
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
SETTING PARAMETERS
When the burner is ignited all displays of the regulator light up. The set point display will blink for about 10 seconds. The value
in the upper field of the display (red) indicates the actual value. The value in the lower field of the display (green) indicates the set
point currently programmed.
CHANGING THE SET POINT
To change the set point, proceed as follows: - Press the PGM button to access the user level. SP1* will appear in the lower display
- Change the value of set point SP1 using the t and s keys.▼e ▲. - After a 2 second delay the value set is stored automatically – To
return to normal display press EXIT.
EXIT
* The value of SP1 depends on the value set previously in configuration level C111.
SETTING PID PARAMETERS
PID parameters are factory set to standard mean values. The operation of the regulator can be self-adapted to suit the system by
activating the “tunE” function. The regulator will set the PID parameters automatically. To activate the “tunE” function proceed
as follows: - With the burner in operation, press PGM + ▼. - the caption “tunE*” will blink in the display. – When “tunE” stops
blinking, the self-adaptation routine has been completed. - Confirm the computed parameters by pressing the ▲ key for 2 seconds.
* The “tunE” function cannot be activated in Manual mode, or when the burner is off.
The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-
ve action time dt and the integral action time rt.
To change parameters Pb1, dt and rt, proceeds as follows: - Press the PGM button to access the parameters level. - To move from
one parameter to the next, press PGM . - When Pb1 is displayed, the value can be increased or decreased using the s and t keys. -
Confirm the changed parameters by pressing PGM. PGM - If confirmation is not given within 2 seconds the value will be stored auto-
matically. - Press PGM to access the next parameter. - When dt is displayed, repeat the procedure described above. - Press PGM
to access the next parameter. - When rt is displayed, repeat the procedure above. - To return to normal display press EXIT.EXIT
DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows: - Press
the PGM key to access the parameters level. - To move from one parameter to the next, press PGM . - When HYS1 is displayed
(burner ignition differential-stage II), increase or decrease the value using the ▼ and ▲ keys. - Confirm the changed parameters by
pressing PGM.
PGM - If confirmation is not given within 2 seconds the value will be stored automatically. - Press PGM to access the
next parameter. - When HYS2 is displayed (burner shutoff differential-stage II), repeat the procedure described above. - Press
PGM to access the next parameter. - When HYS3 is displayed (upper shutoff differential) repeat the procedure described above.
- To return to normal display press EXIT.
EXIT
MANUAL/AUTOMATIC MODE
To access “MANUAL” mode, press and hold EXIT for at least 5 seconds. Manual mode can only be selected when the burner is
in operation. It is deactivated automatically when the burner shuts off. When the LED above the hand symbol is alight, the regu-
lator is in manual mode and the position of the servocontrol can be changed using the ▼ and ▲ keys. The LEDS on the front of
the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active. Pressing the ▼ key the servocon-
trol OPENS. Pressing the ▲ key the servocontrol CLOSES. To select automatic mode press and hold EXIT for at least 5 seconds.
The LED above the hand symbol goes out and the regulator reverts to automatic.
CLIMATIC COMPENSATION
The RWF 40 regulator can be set with the set point interlocked to the external probe. To select this operating mode, proceed as
follows: - Connect the required probe as in the wiring diagram. - Change the regulator settings. When using an external probe
the regulator must be set as follows: - Press the PGM key to access the configuration level. When the caption C111 (XXXX) is
displayed, use the ▲ key to access the second figure (XXXX). Use the ▼ key to select the type of probe (XX3X). - Confirm the
change of parameters by pressing PGM.
PGM If this is not done within 2 seconds, the value is stored automatically - Press PGM to
access the configuration level. When the display reads C112 (XXXX), use the ▲ key to access the second figure (XXXX). Press the
▼ key to set the type of probe (XX3X). - Confirm the changed parameters by pressing PGM.PGM - If confirmation is not given
within 2 seconds the value will be stored automatically.
- To return to normal display press EXIT.
EXIT To establish the heating curve, proceed as follows:
- Press PGM to access the parameters level. - Press PGM to move from one parameter to the next. - When the letter H is
displayed (heating curve gradient), increase or decrease the value using the ▼ and ▲ keys. - Confirm the changed parameters by
pressing PGM.
PGM - If confirmation is not given within 2 seconds the value will be stored automatically.
- To return to normal display press EXIT.
EXIT
pag.14
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
PARAMETERIZATION
160
4
3.8
140 3.6
3.4
3.2
120 3
Boiler temperature set point (iC)
2.8
2.6
0
20 15 10 5 0 -5 -10 -15 -20
17.5 12.5 7.5 2.5 -2.5 -7.5 -12.5 -17.5
External temperature (iC)
pag.15
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
ERROR/FAULT INDICATION
NUMBERS BLINKING IN DISPLAY
- Situation - The number 1999 blinks in the display as the actual value, with the
set point value displayed normally.
- Cause - The real value is not being measured. This means that the upper or lower
limit of the measurement range on analog input 1 (real value) has been exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probe
is faulty, the regulator will not indicate the real value of the physical quantity
monitored. This will result in automatic shutdown (failsafe), deactivation of the
self-adapt function and inhibition of manual operation. The response of the
auxiliary contact will depend on the configuration of parameter C113.
- Situation - The number 1999 blinks in the display as the actual value, with tA
showing in the set point field.
- Cause - The external temperature is not being measured. This means that the
upper or lower limit of the measurement range on analog input 3 (real value) has
been exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probe
is faulty, the regulator will not indicate the real value.
- Situation - The number 1999 blinks in the display as the actual value, with SP .E
showing in the set point field.
- Cause - The external set point value is not being measured. This means that the
upper or lower limit of the measurement range on analog input 2 (real value) has
been exceeded.
- Remedy - Check the electrical connections and the external set point signal. If the
probe is faulty, the regulator will not indicate the real value of the physical quantity
monitored. This will result in automatic shutdown (failsafe), deactivation of the
self-adapt function and inhibition of manual operation.
pag.16
techniques for energy saving LB1360 MULTICALOR 700.1÷1200.1 MD
Insert the RWF 40 regulator through the relative opening in the electrical panel (A).
Insert the fixing anchors and screws into the slots, and secure the unit to the panel (B).
To open the regulator, squeeze the cover from the ends as shown, and lift out (C).
pag.17
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
PARAMETERS
Parameter Display Ecoflam setting Ecoflam setting Ecoflam setting
(passive probe) (passive probe) (active probe)
QAE22 FT-TP/1000 QBE620-P...
Limit value of limit comparator AL 0 0 0
Switching differential for limit comparator HYSt 0 0 0
Proportional band Pb.1 8 8 1
Derivative time dt 20 20 3
Integral action time rt 80 80 15
Dead band (neutral zone) db 0.5 0.5 0.5
Actuator running time (sec.) tt 25 25 25
Switch-on threshold burner / stage II HYS1 -2 -2 -0.2
Switch-off level stage II HYS2 0 0 0
Upper switch-off threshold HYS3 5 5 0.5
Response threshold q 0 0 0
Heating curve slope H 2 2 2
Parallel displacement P 0 0 0
CONFIGURATION
pag.18
00 01 02 03 04 05 06 07 08 09
PAGINA DI
1/2
N 11 1 21 12 2 22 13 3 23 14 4 24 15 5 25 16 6 26 17 7 27
B B
KTavv
KMV1 KMV2 HLBT HLB
GASOLIO (1) SA
SAMA sblocco UV
-
97 SAgG GAS (2) 95 SPA YVGP KA1
T
KMV3 FMV P TV
KMV1 FMV
0 3 0 3 +
1 2 98 1 2 96
95
pag.19
FMV FMP FU
N
L1 T1 T2 S3 B4
SAL KA2
W1 V1 U1
R S T N R1 S1 T1 N 5 6 7 8 9 10 11 12 13 14
MV U V W
M MP
3
M
3
V2 U2 W2
SPGmin
YVGS YVG1 T
BROWN
BLUE
YELLOW-GREEN
BLACK
50 Hz 400V
PE
13 14 1 3
R
DUNGS VDK 200-A
S
T
E N STC
E
T
P
Q
50 Hz 400V HLB
SA COMMUTATORE ALTA-BASSA FIAMMA
PE STS SAMA
GL M U1
T SWITCH HIGH-LOW FLAME
R P
QBE620-P
S
INTERRRUPTEUR 2me-1re ALLURE
CONMUTADOR ALTA-BAJA LLAMA 0
T 3
DENOMINAZIONE MOTORIDUTTORE
DATA
DATA
UFF.TECNICO-SETTORE ELETTRICO
FIRMA
FIRMA
SOST.DA CONTROLLATO 20-05-2004 LANDIS LFL 1.622 DUNGS VDK 200-A UV BEM43141
00 01 02 03 04 05 06 07 08 09
LB1360 MULTICALOR 700.1÷1200.1 MD
00 01 02 03 04 05 06 07 08 09
PAGINA DI
MOTOR VENTILADOR TERMOSTATO DE SEGURIDAD (15°) III: CAMMA DI REGOLAZIONE ARIA PER FIAMMA DI ACCENSIONE GAS
TV TRASFORMATORE SAgG COMMUTATORE GASOLIO-GAS
IGNITION TRANSFORMER SWITCH (OIL-GAS) (15°) IV: CAMMA DI REGOLAZIONE ARIA PER FIAMMA DI ACCENSIONE GASOLIO
TRANSFORMATEUR D'ALLUMAGE INTERRUPTEUR MAZOUT-GAS (25°) V: CAMMA DI REGOLAZIONE ARIA PER BASSA FIAMMA GAS
TRANSFORMADOR CONMUTADOR GASOLEO-GAS
C UV FOTOCELLULA SAMA COMMUTATORE MANUALE-AUTOMATICO
(25°) VI: CAMMA DI REGOLAZIONE ARIA PER BASSA FIAMMA GASOLIO C
UV CELL SWITCH (MANUAL-AUTOMATIC)) (0°) VII: CAMMA NON UTILIZZATA
CELLULE UV INTERRUPTEUR MANUEL-AUTOMATIQUE
FOTOCELULA CONMUTADOR MANUAL-AUTOMATICO (0° ) VIII: CAMMA NON UTILIZZATA
FMP RELE' TERMICO MOTORE POMPA YVG1 ELETTROVALVOLA GAS DI PRIMA FIAMMA
MOTOR PUMP THERMAL RELAY FIRST STAGE GAS SOLENOID VALVE
RELAIS THERMIQUE MOTEUR POMPE ELECTROVANNE GAZ PETITE ALLURE
RELE' TERMICO MOTOR BOMBA ELECTROVALVULA GAS DE 1^ LLAMA
pag.20
FMV RELE' TERMICO MOTORE VENTILATORE YVGS ELETTROVALVOLA GAS DI SICUREZZA
MOTOR THERMAL RELAY (FAN MOTOR) EXTRA SAFETY GAS SOLENOID VALVE
RELAIS THERMIQUE MOTEUR VENTILATEUR ELECTROVANNE GAZ DE SECURITE
DATA
DATA
UFF.TECNICO-SETTORE ELETTRICO
FIRMA
FIRMA
SOST.DA CONTROLLATO LANDIS LFL 1.622 DUNGS VDK 200-A UV BEM43141
00 01 02 03 04 05 06 07 08 09
techniques for energy saving
38
MULTICALOR 1000.1 MD 57
33
37
29
techniques for energy saving
4
34
36
35 32
31
28 30
39
14 27
7
6
12 5
13 54
16
15
pag.21
53
D
FIN
DER
FIN
24
25
17 11 52 41
18 1
40
8
3 9
10
58
OIL GAS
22
49 48 55 47 46 2 15° 30°
45°
K6 0°
60°
75°
90°
23
OIL GAS AUTO
PGM EXIT
0 0 RWF 40
21 44
19 I
0
20 RESET
45 42
51 53
51
50
LB1360 MULTICALOR 700.1÷1200.1 MD
LB1360 MULTICALOR 700.1÷1200.1 MD techniques for energy saving
Multicalor 1000.1 MD
N° DESCRIPTION code
1 - AIR PRESSURE SWITCH DG 10 U Q112/2
2 - AIR INTAKE SET GRPA100
3 - WIELAND PLUG 6 pin E226
4 - COVER BFC09255/038
5 - GLASS BFC02004
6 - PEED WINDOM FRAME BFC02006
7 - MOTOR 22 kW M170/61
8 - FAN RG-630 BFV10401/001
9 - AIR CONVEYOR BFC08260
10 - CONVEYOR RING BFC08258/038
11 - AIR INTAKE GRCA630
12 - CONTROL BOX BASE LANDIS A401
13 - CONTROL BOX LANDIS LFL1.622 A113
14 - IGNITION TRANSFORMER BRAHMA T8 T101
15 - REMOTE CONTROL SWITCH AEG LS15K.00 R621/5
16 - REMOTE CONTROL SWITCH (PUMP) AEG LS11K.00 R621/4
17 - MOTOR THERMAL RELAY AEG B18K-320 R521/16
18 - MOTOR THERMAL RELAY (PUMP) AEG R521/5
19 - MAIN SWITCH cod.40100I1509 R1020
20 - RESET BUTTON C5559AL R1021
21 - SELECTOR R1020/5
22 - LAMP Elettrospring EL/N-SC4 E1510
23 - FUSE SUPPORT FUSIT FH-B528 E802/2
24 - RELÉ BASE Finder 5532 R905
Finder 5534 R906
25 - RELÉ Finder 5532 R711
Finder 5534 R712
26 - TIMER AEG SDE R527
27 - UV CELL LANDIS QRA 2 A205
28 - IGNITION CABLE TC BFE01403/3
29 - IGNITION ELECTRODES SET E612/1
30 - PIPE TC
31 - ROD TC
32 - GAS FIRING HEAD
33 - FRONT DISC
34 - OIL FIRING HEAD
35 - COIL EL011 V523
36 - CONNECTOR WITH RECTIFIER V1119/07
37 - INNER ASSEMBLY TC
38 - BLAST TUBE TC BFB07022/103
39 - GASKET ISOMART BFG04059/1
40 - ANTIJAMMING FILTER S132/4
41 - AIR DAMPER MOTOR LANDIS SQM50.481A2 M212/91
42 - SILENCER BAA11001
43 - OIL PUMP SUNTEC T5C105 P1481/04
44 - COUPLING MP501/4
45 - PUMP MOTOR 4 kW ABB M147/91
46 - OIL VALVE LUCIFER 121 V1751
47 - COIL LUCIFER 3541 V522
48 - OIL VALVE PARKER PM133IV V175/9
49 - COIL PARKER ZB 14 V516/1
50 - OIL FILTER 70501/03 S107/5
51 - HOSES TN 18X1500 S902
52 - MANOMETER CEWAL R1/4 D50-40BAR S601/1
53 - PILOT GAS VALVE DUNGS SV-DLE 507 V1994/21
54 - COIL DUNGS
55 - OIL VALVE SUNTEC TV40011 P1481
56 - NOZZLE BERGONZO kg/h 650
57 - MODULATING UNIT LANDIS RWF 40 E1215
NOTE :
pag.23
ECOFLAM S.p.A. reserves the right to make any adjustments, without prior notice, which it considers necessary or useful
La ECOFLAM S.p.A si riserva il diritto di apportare ai prodotti quelle modifiche che riterrà necessarie o
toutili,
its products, without affectingletheir
senza pregiudicarne main features.principali.
caratteristiche
Ecoflam S.p.A.
via Roma, 64 - 31023 RESANA (TV) - Italy - tel. 0423/715345 r.a.
telefax 0423/715444 (Italy 480009 - Export 480873, 715538).
http://www.ecoflam.it - e-mail: [email protected]