Therefore The Required Heat Transfer Area, A 303.44 m2: in Out in Out

The document provides technical specifications for an existing economizer design including flue gas temperatures, heat transfer area, and flow rates. It then evaluates three modified design options with longer tube lengths, fewer tubes, and larger diameters to increase the heat transfer area and reduce gas and water velocities. Option 3 is recommended as it achieves the required heat transfer area while keeping velocities within acceptable ranges and a lower estimated outlet gas temperature rise.

Uploaded by

Hsein Wang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
192 views

Therefore The Required Heat Transfer Area, A 303.44 m2: in Out in Out

The document provides technical specifications for an existing economizer design including flue gas temperatures, heat transfer area, and flow rates. It then evaluates three modified design options with longer tube lengths, fewer tubes, and larger diameters to increase the heat transfer area and reduce gas and water velocities. Option 3 is recommended as it achieves the required heat transfer area while keeping velocities within acceptable ranges and a lower estimated outlet gas temperature rise.

Uploaded by

Hsein Wang
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

Flue Gas Temperature @ Eco inlet, TGin = 435 Deg C

Flue Gas Temperature @ Eco outlet TGout = 245 Deg C


Feed water Temperature @ Eco inlet TWin = 105 Deg C
Feed water Temperature @ Eco outlet TWout = 175 Deg C
Flue gas volume flow rate @ 435 Deg C = 27.91 m3/sec
Existing Heat Transfer Area = 212.45 m2

Flue Gas density @ 0 Deg C = 1.2 Kg/m3


Flue Gas density @ 435 Deg C = (1.2 x 273) / (273 + 435)
Flue Gas density @ 435 Deg C = 0.46 Kg/m3

Therefore mass flow rate of flue gas = 46218.96 Kg/hr

Heat transferred in economiser, Q = m x cp x ΔT


= 46218.96 x 0.255 x (435 - 245)
= 2239308.61 Kcal/hr

LMTD = (TGin - TWout) - (TGout - TWin) / ln((TGin - TWout) -


= (435 - 175) - (245 - 105) / ln((435 - 175) - (245 - 105)
= 230.76 Deg C

Heat transferred is also given by, Q = U x A x LMTD


Heat transfer coefficient, U = 45.68 Kcal/hr/m2/DegC

"For Inline pitch Heat transfer coefficient will be 30% less efficient as compared to Stagger pitch"

Heat transfer coefficient, U = 31.98 Kcal/hr/m2/DegC

Heat transferred is also given by, Q = U x A x LMTD


2239308.612 = 31.98 x A x 230.76
Therefore the required heat transfer area, A = 303.44 m2
(435 - 245)

Gout - TWin) / ln((TGin - TWout) - (TGout - TWin)


105) / ln((435 - 175) - (245 - 105)

mpared to Stagger pitch"


EXISTING ECONOMISER DESIGN

Tube OD 50.8 mm
Straight length (Bend to Bend) 3200 mm
No of straight length segments 64 Nos
No of loop 7 Nos
Heat Transfer Area Available 228.79 m2
Required Heat transfer area 303 m2

Casing Width 1100 mm


Casing Length (Excluding baffle plate) 3277 mm
Flue gas volume flow rate at Eco I/L (435 Deg C) 27.91 m3/s
Available area for flue gas flow 2.44 m2
Flue gas velocity at Eco I/L 11.44 m/s HIGH
Recommended velocity 10 m/s

Water flow rate @ Peak load 31000 Kg/hr


Density of water 957 Kg/m3
ID of the tube 42.8 mm
Total C.S.A of tubes 0.019 m2
Water velocity inside the tubes 0.474 m/s
Double click here to view the drawing

EXISTING.jpg
MODIFIED ECONOMISER DESIGN (Option - 1)

Tube OD 38.1 mm
Straight length (Bend to Bend) 3277 mm
No of straight length segments 62 Nos
No of loop 12 Nos
Heat Transfer Area Available 291.83 m2 ACCEPTABLE
Required Heat transfer area 303 m2

Casing Width 1100 mm


Casing Length (Excluding baffle plate) 3277 mm
Flue gas volume flow rate at Eco I/L (435 Deg C) 27.91 m3/s
Available area for flue gas flow 2.11 m2
Flue gas velocity at Eco I/L 13.23 m/s HIGH
Recommended velocity 10 m/s

Water flow rate @ Peak load 31000 Kg/hr


Density of water 957 Kg/m3
ID of the tube 29.94 mm
Total C.S.A of tubes 0.008 m2
Water velocity inside the tubes 1.125 m/s HIGH

Required velocity inside the Eco tubes 0.474 m/s


Quantity of water to be bypassed to have low pressure drop 17935.8 Kg/hr
Estimated raise in flue gas temp at Eco O/L 321.67 Deg C HIGH

Double click here for drawing


MODIFIED 1.jpg
MODIFIED ECONOMISER DESIGN (Option - 2)

Tube OD 38.1 mm
Straight length (Bend to Bend) 4000 mm
No of straight length segments 60 Nos
No of loop 10 Nos
Heat Transfer Area Available 287.27 m2 ACCEPTABLE
Required Heat transfer area 303 m2

Casing Width 1100 mm


Casing Length (Excluding baffle plate) 4000 mm
Flue gas volume flow rate at Eco I/L (435 Deg C) 27.91 m3/s
Available area for flue gas flow 2.88 m2
Flue gas velocity at Eco I/L 9.69 m/s OK
Recommended velocity 10 m/s

Water flow rate @ Peak load 31000 Kg/hr


Density of water 957 Kg/m3
ID of the tube 29.94 mm
Total C.S.A of tubes 0.007 m2
Water velocity inside the tubes 1.285 m/s HIGH

Required velocity inside the Eco tubes 0.474 m/s


Quantity of water to be bypassed to have low pressure drop 19568.8 Kg/hr
Estimated raise in flue gas temp at Eco O/L 330.40 Deg C HIGH

Double click here for drawing


MODIFIED 2.jpg
MODIFIED ECONOMISER DESIGN (Option - 3)

Tube OD 50.8 mm
Straight length (Bend to Bend) 4200 mm
No of straight length segments 48 Nos
No of loop 9 Nos
Heat Transfer Area Available 289.57 m2 ACCEPTABLE
Required Heat transfer area 303 m2

Casing Width 1100 mm


Casing Length (Excluding baffle plate) 4200 mm
Flue gas volume flow rate at Eco I/L (435 Deg C) 27.91 m3/s
Available area for flue gas flow 2.7 m2
Flue gas velocity at Eco I/L 10.34 m/s ACCEPTABLE
Recommended velocity 10 m/s

Water flow rate @ Peak load 31000 Kg/hr


Density of water 957 Kg/m3
ID of the tube 42.8 mm
Total C.S.A of tubes 0.013 m2
Water velocity inside the tubes 0.692 m/s ACCEPTABLE

Required velocity inside the Eco tubes 0.474 m/s


Quantity of water to be bypassed to have low pressure drop 9770.68 Kg/hr
Estimated raise in flue gas temp at Eco O/L 278.02 Deg C ACCEPTABLE

Double click here for drawing


MODIFIED 3.jpg