Standard Method Load Calculation For One-Family Dwellings
Standard Method Load Calculation For One-Family Dwellings
4 Add lines 1, 2, and 3 4 Lines 5 through 8 utilize the demand factors found in Table 220.42.
5 – 3000 = 5 6 – 117,000 = 6
(line 4) (if 117,000 or less, skip to line 8) (line 5, if more than 117,000)
7 × 25% = 7 8 × 35% = 8
(line 6) (smaller of line 5 or 117,000)
15 Total Volt-Ampere Demand Load: Add lines 9 through 14 to find the minimum required volt-amperes. 15
16 Minimum Amperes
Divide the total Minimum Size
volt-amperes by 16 17 Service or 17
÷ = Feeder 240.6(A)
the voltage. (line 15) (voltage) (minimum amperes)
18 Size the Service or Feeder Conductors.
Use 310.15(B)(7) to find the service conductors up to 400 amperes. Minimum Size
Ratings in excess of 400 amperes shall comply with Table 310.15(B)(16) Conductors
18
310.15(B)(7) also applies to feeder conductors supplying the entire load.
19 Size the Neutral Conductor. 220.61
310.15(B)(7) states that the neutral service or feeder conductor Minimum Size
can be smaller than the ungrounded ("hot") conductors,provided the Neutral 19
requirements of 215.2, 220.61, and 230.42 are met. Conductor
250.24(C)(1) states that the grounded conductor shall not be smaller
than specified in Table 250.102(C)(1).
20 Size the Grounding Electrode Conductor (for Service). 250.66
Use line 18 to find the grounding electrode conductor in Table 250.66. Minimum Size
Grounding
Size the Equipment Grounding Conductor (for Feeder). 250.122
Electrode
20
Use line 17 to find the equipment grounding conductor in Table 250.122.
Equipment grounding conductor types are listed in 250.118. Conductor