0% found this document useful (0 votes)
73 views

Enginewise Consumers (W16V32) : Consumer List

This document provides a list of consumers for a W32EAM+EFB HFO power plant with their descriptions, fuse/base ratings, power consumption, current draw, and notes. It includes consumers for the engine control panel, prelube pump, water preheaters, fuel booster heaters, lube oil separator, radiator fans, and other auxiliary systems. The largest consumers are the lube oil separator electrical heater drawing 56kW and the radiator frequency converter drawing 86kW.

Uploaded by

Charlie Mendoza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views

Enginewise Consumers (W16V32) : Consumer List

This document provides a list of consumers for a W32EAM+EFB HFO power plant with their descriptions, fuse/base ratings, power consumption, current draw, and notes. It includes consumers for the engine control panel, prelube pump, water preheaters, fuel booster heaters, lube oil separator, radiator fans, and other auxiliary systems. The largest consumers are the lube oil separator electrical heater drawing 56kW and the radiator frequency converter drawing 86kW.

Uploaded by

Charlie Mendoza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
ENGINEWISE CONSUMERS (W16V32)

1 BJA 0_1 W32 EAM & EFB CONTROL PANEL 350 / 130.9 216.6 0.0 53.5 73.5 121.35 3 MCCB -
SCA 0_1 M201 Prelube Pump Motor 15.0 31 15.0 15 3 DOL -
SCA 0_1 M782 Turning Gear Motor 2.2 5 2.2 3 F/R -
BAG 0_1 B001 Generator Anticondensation Heaters 1.6 2.5 1.6 2 FH Heater connected L1-L2 -
VDA 0_1 M001 Preheating Circulation Pump Motor 0.65 1.75 0.7 0.65 3 DOL -
VDA 0_1 B001.1 Water Preheater step 1 27 39 27.0 27 3 FH -
VDA 0_1 B001.2 Water Preheater step 2 27 39 27 27 3 FH -
BLU 0_1 Charge Air Filter Control Panel 0.18 0.7 0.18 3 MCB -
BLS 0_1 Oil mist separator 10A 1 2.4 1 3 MCB -
MOD 0_1 B017 Electrical trace heating for EAM fuel & sludge lines 16A 1.1 4.8 1 RCB Two heating circuits -
MOD 0_1 M002 Clean leak fuel pump motor 1.1 2.4 1.1 1.1 3 DOL -
PCC 0_1 B024 Electrical trace heating for EFB fuel & sludge lines 16A 2.8 12.1 1 RCB Two heating circuits -
PCC 0_1 M001 Booster Pump Motor 4 7.1 4 4 3 DOL -
PCC 0_1 M004 Fuel cooling pump 0.65 1.6 0.65 3 DOL -
BJA 0_2 B007.1 Fuel Booster Heater, Step 1 13.3 19.2 13.3 13.3 3 FH -
BJA 0_2 B007.2 Fuel Booster Heater, Step 2 13.3 19.2 13.3 13.3 3 FH -
BJA 0_2 B007.3 Fuel Booster Heater, Step 3 10 14.4 10 10 3 FH -
BJA 0_2 B007.4 Fuel Booster Heater, Step 4 10 14.4 10 10 3 FH -
BJA 0_1 E001 Outlet Socket 16A 3 RCB -
PCC 0_1 Q001 Fuel mass flow meter 0.01 0.5 0.01 1 MCB 110 VAC -

1 BJN 0_1 LUBE OIL SEPARATOR 150 / 65.0 91.2 0.0 65.0 0.0 0 3 MCCB -
QBB 0_1 M001 Feeder Pump Motor 1.5 3.2 1.5 0 3 DOL -
QBB 0_1 M002 Separator Motor 7.5 14 7.5 0 3 DOL -
QBB 0_1 B103 Electrical heater 56.0 74 56 0 3 MCCB Check heater size! -

Page: 1(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
1 BLP 0_1 RADIATOR FREQUENCY CONVERTER 300 / 86.0 180.0 0.0 86.0 0.0 0.0 3 MCCB -
BLP 0_2 RADIATOR PANEL -
VCA 0_1 M001 Radiator 1, Fan Motor 1 8.6 18 8.6 3 MPS -
VCA 0_1 M002 Radiator 1, Fan Motor 2 8.6 18 8.6 3 MPS -
VCA 0_1 M003 Radiator 1, Fan Motor 3 8.6 18 8.6 3 MPS -
VCA 0_1 M004 Radiator 1, Fan Motor 4 8.6 18 8.6 3 MPS -
VCA 0_1 M005 Radiator 1, Fan Motor 5 8.6 18 8.6 3 MPS -
VCA 0_2 M001 Radiator 2, Fan Motor 1 8.6 18 8.6 3 MPS -
VCA 0_2 M002 Radiator 2, Fan Motor 2 8.6 18 8.6 3 MPS -
VCA 0_2 M003 Radiator 2, Fan Motor 3 8.6 18 8.6 3 MPS -
VCA 0_2 M004 Radiator 2, Fan Motor 4 8.6 18 8.6 3 MPS -
VCA 0_2 M005 Radiator 2, Fan Motor 5 8.6 18 8.6 3 MPS -
1 BLP 0_2 E001 RADIATOR PANEL vent fan/heater 10A 0.5 4.0 0.5 1 MCB 230VAC, supply to be linked to next radiator -

1 BLQ 0_1 INLET VENTILATION FREQUENCY CONV. 50 / 15.0 26.0 0.0 15.0 0.0 0.0 3 MCCB -
EAA 0_1 M001 Supply air fan motor 15 26 15 3 FC -

1 BLQ 0_5 AUXILIARY VENTILATION FREQUENCY CONV. 35 / 8.8 18.6 0.0 8.8 0.0 0.0 3 MCCB -
BLQ 0_5 E002 DISTRIBUTION BOX -
EAA 0_2 M001 Auxiliary air fan motor 1 4.4 9.3 4.4 3 MPS -
EAA 0_2 M002 Auxiliary air fan motor 2 4.4 9.3 4.4 3 MPS -

1 CFE 0_1 ENGINEVISE CONTROL PANEL 10 / 1.0 3.0 1 1 1 MCB supply to be linked to next panel in same engine hall
-

P/kW I/A P/kW P/kW P/kW P/kW For


Enginewise Total: 613.4 1070.7 0.0 458.7 146.9 244.7 2 engine(s)

Page: 2(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
ENGINEWISE CONSUMERS (W6L32)

1 BJA 0_1 W32 EAU 200 / 38.3 52.9 14.4 0.0 36.0 38.3 3 3 MCCB -
SCA 0_1 M201 Prelube Pump Motor 7.5 11.3 7.5 7.5 3 DOL -
SCA 0_1 M782 Turning Gear Motor 2.2 3.3 2.2 2.2 3 F/R -
BAG 0_1 B001 Generator Anticondensation Heaters 1.6 2.5 1.6 1.6 2 FH Heater connected L1-L2 -
VDA 0_1 M001 Preheating Circulation Pump Motor 0.65 1.8 0.65 0.65 3 DOL -
VDA 0_1 B001.1 Water Preheater step 1 12 14.4 12 12 3 FH -
VDA 0_1 B001.2 Water Preheater step 2 12 14.4 12 12 12 3 FH -
BLU 0_1 E001 Charge Air Filter A Control Panel 0.2 0.3 0.2 0.2 3 MCB -
BJA 0_1 E1 Outlet Socket 16 1.8 3.5 1.8 1.8 3 FF for mobile lube oil pump (1,75kW and 3,5A)
MOD 0_1 B017 Trace heating, EAM fuel & sludge lines 6A 0.4 1.4 0.4 0.4 1 RCB One heating circuit -

1 BJB 0_1 FUEL OIL UNIT 25 / 4.1 6.4 0.0 3.8 0.0 3.8 3 MCCB -
PFC 0_1 M001 Fuel Oil Pump Motor 3.0 4.1 2.5 2.5 3 DOL -
QBB 0_1 M002 Return Fuel Pump Motor 1.1 2.3 1.3 1.3 3 DOL -

1 BJN 0_1 LUBE OIL SEPARATOR 150 / 65.0 91.2 0.0 65.0 0.0 0.0 3 MCCB -
QBB 0_1 M001 Feeder Pump Motor 1.5 3.2 1.5 0.0 3 DOL -
QBB 0_1 M002 Separator Motor 7.5 14 7.5 0.0 3 DOL -
QBB 0_1 B103 Electrical heater 56.0 74 56 0.0 3 MCCB Check heater size! -

1 BLP 0_1 RADIATOR FREQUENCY CONVERTER 200 / 43.0 90.0 0.0 43.0 0.0 0.0 3 MCCB -
BLP 0_2 RADIATOR PANEL -
VCA 0_1 M001 Radiator 1, Fan Motor 1 8.6 18 8.6 3 MPS -
VCA 0_1 M002 Radiator 1, Fan Motor 2 8.6 18 8.6 3 MPS -
VCA 0_1 M003 Radiator 1, Fan Motor 3 8.6 18 8.6 3 MPS -
VCA 0_1 M004 Radiator 1, Fan Motor 4 8.6 18 8.6 3 MPS -
VCA 0_1 M005 Radiator 1, Fan Motor 5 8.6 18 8.6 3 MPS -
1 BLP 0_2 E001 RADIATOR PANEL vent fan/heater 10A 0.5 4.0 0.5 1 MCB 230VAC, supply to be linked to next radiator -

1 BLQ 0_1 INLET VENTILATION FREQUENCY CONV. 50 / 15.0 26.0 0.0 15.0 0.0 0.0 3 MCCB -
EAA 0_1 M001 Supply air fan motor 15 26 15 3 FC -

Page: 3(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
1 BLQ 0_5 AUXILIARY VENTILATION FREQUENCY CONV. 35 / 8.8 18.6 0.0 8.8 0.0 0.0 3 MCCB -
BLQ 0_5 E002 DISTRIBUTION BOX -
EAA 0_2 M001 Auxiliary air fan motor 1 4.4 9.3 4.4 3 MPS -
EAA 0_2 M002 Auxiliary air fan motor 2 4.4 9.3 4.4 3 MPS -

1 CFE 0_1 ENGINEVISE CONTROL PANEL 10 / 1.0 3.0 1 1 1 MCB supply to be linked to next panel in same engine hall
-

P/kW I/A P/kW P/kW P/kW P/kW For


Enginewise Total: 525.6 864.3 43.1 409.8 107.9 129.3 3 engine(s)

COMMON CONSUMERS

1 BJC 901 LFO UNLOADING UNIT 50 / 15.0 26.2 7.5 7.5 0.0 0.0 3 MCCB -
PAD 901 M001 LFO unloading pump motor 1 7.5 13.1 7.5 3 DOL -
PAD 901 M002 LFO unloading pump motor 2 7.5 13.1 7.5 3 DOL -

1 BJD 901 B001 HFO UNLOADING PUMP MOTOR 1 VFD 50 / 15.0 27.9 0 15.0 0.0 0 3 MCCB -
PAA 901 M001 HFO unloading pump motor 1 15.0 27.9 15.0 3 FC -

1 BJD 901 B002 HFO UNLOADING PUMP MOTOR 2 VFD 50 / 15.0 27.9 15.0 0.0 0.0 0 3 MCCB -
PAA 901 M002 HFO unloading pump motor 2 15.0 27.9 15.0 3 FC -

1 BJD 901 HFO UNLOADING PUMP CONTROL PANEL 16 / 0.5 1.0 0.0 0.5 0.0 0 3 MCB -
PAA 901 Q001 HFO mass flow meter 1 10 0.2 0.4 0.2 1 MCB -
PAA 901 Q002 HFO mass flow meter 2 10 0.2 0.4 0.2 1 MCB -

1 BJF 901 B001 HFO TRANSFER PUMP MOTOR 1 VFD 35 / 4.0 6.0 0.0 4.0 0.0 0 3 MCB -
PAC 901 M001 HFO transfer pump motor 1 4.0 6.0 4.0 3 FC -

1 BJF 901 B002 HFO TRANSFER PUMP MOTOR 2 VFD 35 / 4.0 6.0 4.0 0.0 0.0 0 3 MCB -
PAC 901 M002 HFO transfer pump motor 2 4.0 6.0 4.0 3 FC -

1 BJF 901 HFO TRANSFER PUMP CONTROL PANEL 16 / 0.5 1.0 0.0 0.5 0.0 0 3 MCB -

Page: 4(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
1 BJF 902 HEATER PANEL 200 / 72.0 104.0 0.0 72.0 0.0 0.0 3 MCCB solid state contactor control -
PAC 901 B003.1 HFO heater step 1 20.0 28.9 20.0 3 FH -
PAC 901 B003.2 HFO heater step 2 20.0 28.9 20.0 3 FH -
PAC 901 B003.3 HFO heater step 3 16.0 23.1 16.0 3 FH -
PAC 901 B003.4 HFO heater step 4 16.0 23.1 16.0 3 FH -

1 BJF 903 HEATER PANEL 200 / 72.0 104.0 72.0 0.0 0.0 0.0 3 MCCB solid state contactor control -
PAC 901 B103.1 HFO heater step 1 20.0 28.9 20.0 3 FH -
PAC 901 B103.2 HFO heater step 2 20.0 28.9 20.0 3 FH -
PAC 901 B103.3 HFO heater step 3 16.0 23.1 16.0 3 FH -
PAC 901 B103.4 HFO heater step 4 16.0 23.1 16.0 3 FH -

1 BJF 904 B001 HFO TRANSFER PUMP MOTOR 1 VFD 35 / 4.0 6.0 0.0 4.0 0.0 0 3 MCB -
PAC 901 M001 HFO transfer pump motor 1 4.0 6.0 4.0 3 FC -

1 BJF 904 B002 HFO TRANSFER PUMP MOTOR 2 VFD 35 / 4.0 6.0 4.0 0.0 0.0 0 3 MCB -
PAC 901 M002 HFO transfer pump motor 2 4.0 6.0 4.0 3 FC -

1 BJF 904 HFO TRANSFER PUMP CONTROL PANEL 16 / 0.5 1.0 0.0 0.5 0.0 0 3 MCB -

1 BJF 905 HEATER PANEL 200 / 72.0 104.0 0.0 72.0 0.0 0.0 3 MCCB solid state contactor control -
PAC 901 B003.1 HFO heater step 1 20.0 28.9 20.0 3 FH -
PAC 901 B003.2 HFO heater step 2 20.0 28.9 20.0 3 FH -
PAC 901 B003.3 HFO heater step 3 16.0 23.1 16.0 3 FH -
PAC 901 B003.4 HFO heater step 4 16.0 23.1 16.0 3 FH -

1 BJF 906 HEATER PANEL 200 / 72.0 104.0 72.0 0.0 0.0 0.0 3 MCCB solid state contactor control -
PAC 901 B103.1 HFO heater step 1 20.0 28.9 20.0 3 FH -
PAC 901 B103.2 HFO heater step 2 20.0 28.9 20.0 3 FH -
PAC 901 B103.3 HFO heater step 3 16.0 23.1 16.0 3 FH -
PAC 901 B103.4 HFO heater step 4 16.0 23.1 16.0 3 FH -

Page: 5(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
1 BJJ 901 HFO SEPARATOR UNIT 1 50 / 19.5 36.7 0.0 19.5 0.0 0.0 3 MCCB -
PBB 901 M001 Feeder Pump Motor 3.0 6.3 3.0 3 FC -
PBB 901 M002 Separator Motor 12.5 22 12.5 3 DOL -
PBB 901 B104 Sludge tank heater 3.0 4.4 3.0 3 FH -
PBB 901 B106 Trace heating 6A 1.00 4 1.0 1 RCB 230VAC -

1 BJJ 901 E003 HFO SEPARATOR 1 HEATER PANEL 300 / 130 157 0 223 0 3 MCCB Check heater size! -

1 BJJ 902 HFO SEPARATOR UNIT 2 50 / 19.5 36.7 19.5 0.0 0.0 0.0 3 MCCB -
PBB 902 M001 Feeder Pump Motor 3.0 6.3 3.0 3 DOL -
PBB 902 M002 Separator Motor 12.5 22 12.5 3 DOL -
PBB 902 B104 Sludge tank heater 3.0 4.4 3.0 3 FH -
PBB 902 B106 Trace heating 6A 1.00 4 1.0 1 RCB 230VAC -

1 BJJ 902 E003 HFO SEPARATOR 2 HEATER PANEL 300 / 130 157 223 0 0 0 3 MCCB Check heater size! -

1 BJL 901 B011 HFO FEEDER PUMP MOTOR 1 VFD (W16V32) 40 / 4.0 6.0 0.0 4.0 0.0 0 3 MCB -
PCA 901 M001 HFO feeder pump motor 1 4.0 6.0 4.0 3 FC -

1 BJL 901 B012 HFO FEEDER PUMP MOTOR 2 VFD (W16V32) 40 / 4.0 6.0 4.0 0.0 0.0 0 3 MCB -
PCA 901 M002 HFO feeder pump motor 2 4.0 6.0 4.0 3 FC -

1 BJL 901 B013 LFO FEEDER PUMP MOTOR VFD 1 (W16V32) 60 / 15.0 22.5 0.0 0.0 0.0 15.0 3 MCB -
PCA 901 M003 LFO feeder pump motor 15.0 22.5 15 3 FC -

1 BJL 901 HFO/LFO FEEDER PUMP CONTROL PANEL (W16V32) 16 / 0.1 0.2 0.0 0.1 0.1 0.09 3+N MCB -
PCA 901 B005 Auto filter 10 0.1 0.2 0.1 0.1 0.09 3 MCB -
PCA 901 B022 Trace heating fuel lines 16 1 RCB -

Page: 6(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type

1 BJL 902 FEEDER/BOOSTER UNIT (W6L32) 300 / 116.8 182.0 13.2 103.6 13.3 3 MCB (FC-CONTROLLED) -
PCA 901 M011 HFO Feeder Pump 1 4.6 6.9 4.6 4.6 3 DOL -
PCA 901 M021 HFO Feeder Pump 2 4.6 6.9 4.6 3 DOL -
PCA 901 M011 HFO Booster Pump 1 8.6 12.9 8.6 8.6 3 DOL -
PCA 901 M021 HFO Booster Pump 2 8.6 12.9 8.6 3 DOL -
PCA 0_1 B007.1 Fuel Booster heater, step 1 44 66 44 3 FH -
PCA 0_1 B007.2 Fuel Booster heater, step 2 44 66 44 3 FH -
PCA 901 W98 Trace heating 2.30 10 2.3 1 RCB 230V -
PCA 901 B016 Viscometer 0.05 0.05 1 MCB -
PCA 901 B014 Auto Filter 0.05 0.35 0.05 0.1 3 MCB -
PCA 901 Q001 Flow Meter 0.02 0.02 0 1 MCB -

1 BJP 901 LUBE OIL UNLOADING PUMP UNIT 25 / 3.0 5.4 0.0 3.0 0.0 0.0 3 MCB -
QAA 901 M001 Lube Oil Transfer Pump Motor 3.0 5.4 3.0 3 DOL -

1 BJP 902 LUBE OIL TRANSFER PUMP UNIT (DOUBLE) 25 / 4.4 6.8 4.4 0.0 0.0 0.0 3 MCB -
QAE 901 M001 Lube Oil Transfer Pump Motor 1 2.2 3.4 2.2 3 DOL -
QAE 901 M002 Lube Oil Transfer Pump Motor 2 2.2 3.4 2.2 3 DOL -

1 BJP 903 LUBE OIL TRANSFER PUMP UNIT (MOBILE) 25 / 3.0 5.4 0.0 3.0 0.0 0.0 3 MCB -
QAA 901 M001 Lube Oil Transfer Pump Motor 3.0 5.4 3.0 3 DOL -

1 BLA 901 STARTING AIR UNIT 200 / 40.0 72.0 20.0 20.0 0.0 20.0 3 MCCB 0% runtime at 100% load, needed at start up
TSA 901 M001 Starting Air Compressor Motor 20.0 36 20.0 20 3 DOL Possible to run both in manual mode -
TSA 901 M002 Starting Air Compressor Motor 20.0 36 20.0 3 DOL -

1 BLB 901 WORKING AIR UNIT 80 / 9.0 19.6 0.0 9.0 0.0 9.0 3 MCCB 100% runtime at 100% load
TCA 901 M001 Working Air Compressor Motor 7.5 14 7.5 7.5 3 DOL -
TCA 901 D001 Air Dryer 1.5 5.6 1.5 1.5 1 MCB 230VAC -

1 BLC 901 MAINTENANCE WATER PUMP 16 / 2.2 4.8 2.2 0.0 0.0 0.0 3 MCB
VBA 901 M001 Maintenance Water Pump 2.2 4.8 2.2 3 MPS -

Page: 7(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type
1 BEY 901 DC PANEL BEY901 63 / 1.8 9.1 1.8 1.8 3x1PH MCB 3 x 1 pole MCB
1 BEY 901 E001 110V DC Panel charger 1 16 / 1.6 9.2 1.6 1.6 1 MCB 208/240VAC -
1 BEY 901 E002 110V DC Panel charger 2 16 / 1.6 9.2 1.6 1.6 1 MCB 208/240VAC -
1 BEY 901 E003 110V DC Panel charger 3 16 / 1.6 9.2 1.6 1.6 1 MCB 208/240VAC -

1 BLK 901 OVERHEAD CRANE 16 / 2.7 2.7 3 MCB -


1 BA_ 901 MV SWITCHGEAR 10 / 1.0 1 1.0 1.0 1 MCB -
1 CFA 901 COMMON CONTROL PANEL 10 / 1.0 1 1.0 1.0 1 MCB -
1 BEU 901 UPS 16 / 2.5 2.5 2.5 2.5 1 MCB -
1 BLM 901 BLACKSTART UNIT 400 / 3+N MCCB -
1 CUSTOMER PANEL 800 / MCCB
1 BLM 901 E01 BLACKSTART UNIT 35 / 3+N MCCB -
SPARE / 350 3 MCCB -
SPARE / 300 3 MCCB -
SPARE / 200 3 MCCB -
SPARE / 200 3 MCCB -
SPARE / 125 3 MCCB -
SPARE / 125 3 MCCB -
SPARE / 125 3 MCCB -

Page: 8(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT
Doc ID: P20007-WAR-DL-0079_01

CONSUMER LIST

VOLTAGE 480 V
FREQUENCY 60 Hz

INSTALLED
Bus Plant Code Description Fuse / Base Power Current Unit Plant P / kW Feedertype Notes Rev.
Nr W32EAM+EFB HFO, EL I/A P / kW I/A St.by Run Hot St.by BSU Phase Type

P/kW I/A P/kW P/kW P/kW P/kW


Special characters, explanation: Common Total: 851.0 1243.1 460.8 561.2 0.1 57.4

DOL = Direct On Line (Contactor + MCB)


F/R = Forward/Reverse Total : 1990.0 3178.1 503.9 1429.7 254.8 431.4
Y/D = Star / Delta motor start
FC = Frequency Converter
MCB = Miniature Circuit Breaker Wartsila + Customer Scope 2801.3 4195.6 927.2 1924.5 299.5 507.6
MCCB = Mould Case Circuit Breaker
MPS =Motor Protection Switch
RCB =Residual Current Breaker
FF = Fused Feeder (Fuse only)
FH = Feeder for Heater (Contactor + Fuse)

Total Power for Station Transformer = (Connected loads - Stand by load) + 10% of Emergency loads

1904.05 KW
2380.07 KVA

Page: 9(9)
Doc no: DBAE491412
Revision: 01
BANTAYAN 25MW POWER PLANT