0% found this document useful (0 votes)
205 views13 pages

Siemens S7 1200 S7 1500 Absolute Addressing Ethernet

This document provides a guide for connecting Siemens S7-1200/S7-1500 PLCs to EasyBuilder Pro using an Ethernet connection. It includes settings for the HMI, data type mappings, address formats, and instructions for importing tags from the PLC using TIA Portal project files or direct communication with the PLC. Methods like exporting tags from TIA Portal as an Excel file or .SCL file and using those files or a TIA Portal project file (.AP12/13/14/15/16) to import tags into EasyBuilder Pro are described.

Uploaded by

claudiomecatron
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
205 views13 pages

Siemens S7 1200 S7 1500 Absolute Addressing Ethernet

This document provides a guide for connecting Siemens S7-1200/S7-1500 PLCs to EasyBuilder Pro using an Ethernet connection. It includes settings for the HMI, data type mappings, address formats, and instructions for importing tags from the PLC using TIA Portal project files or direct communication with the PLC. Methods like exporting tags from TIA Portal as an Excel file or .SCL file and using those files or a TIA Portal project file (.AP12/13/14/15/16) to import tags into EasyBuilder Pro are described.

Uploaded by

claudiomecatron
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

PLC Connection Guide

Siemens S7-1200/S7-1500 (Absolute Addressing)


(Ethernet)
Supported Series: Siemens S7-300/1200/1500 series, ET200SP series
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters Recommended Options Notes
PLC type Siemens S7-1200/S7-1500 (Absolute Addressing) (Ethernet)
PLC I/F Ethernet
Port no. 102
Rack 0
CPU slot 1

On-line simulator Yes Multi-HMI connect Yes (Max:3 HMI)

*Connect S7-300 settings


PLC Connection Guide

Support Device Type:


S7-1200 data type EasyBuilder data format Memo
Bool bit
Byte 16-bit BCD, Hex, Binary, Unsigned 8-bit
SInt 16-bit BCD, Hex, Binary, Signed 8-bit
USInt 16-bit BCD, Hex, Binary, Unsigned 8-bit
Word 16-bit BCD, Hex, Binary, Unsigned 16-bit
Int 16-bit BCD, Hex, Binary, Signed 16-bit
UInt 16-bit BCD, Hex, Binary, Unsigned 16-bit
DWord 32-bit BCD, Hex, Binary, Unsigned 32-bit
DInt 32-bit BCD, Hex, Binary, Signed 32-bit
Real 32-bit Float 32-bit
UDInt 32-bit BCD, Hex, Binary, Unsigned 32-bit
LInt 64-bit Signed
ULInt 64-bit Unsigned
LReal 64-bit Double
Array
Note: EasyBuilder Pro V6.03.02 or later supports 64 bits data type, but please note that
the address limit range is 48 bits in maximum.
PLC Connection Guide

User define type


1. User define type can be established in PLC data type

2. User define type can be used in DB. User-defined types mapping address fuction are
not supported. When using a user-defined type, please add it to the end of DB, to avoid
influencing import and communication (address offset calculation).

3. User define type cannot be imported automatically, you need to manually create an
address in EasyBuilder Pro to communicate.
PLC Connection Guide

Device Address:
Bit/Word Device type Format Range Memo
B I DDDDDo 0 ~ 655357 Input (I)
B Q DDDDDo 0 ~ 655357 Output (O)
B M DDDDDo 0 ~ 655357 Bit Memory
B DBnBit FFFFFDDDDo 0 ~ 6553599997
B DBxBit FFFFFDDDDDo 0 ~ 10700655327
B DB1Bit-DB99Bit DDDDDo 0 ~ 655357 Data Register Bit
BYTE IB DDDDD 0 ~ 65535 Input (I)
W IW DDDDD 0 ~ 65533 Input (I)
DW ID DDDDD 0 ~ 65535 Input (I)
BYTE QB DDDDD 0 ~ 65535 Output (O)
W QW DDDDD 0 ~ 65533 Output (O)
DW QD DDDDD 0 ~ 65535 Output (O)
BYTE MB DDDDD 0 ~ 65535 Bit Memory
W MW DDDDD 0 ~ 65533 Bit Memory
DW MD DDDDD 0 ~ 65535 Bit Memory
BYTE DBBn FFFFFDDDD 0 ~ 655359999 Data Register
BYTE DBBx FFFFFDDDDD 0 ~ 1070065535 Data Register
W DBn FFFFFDDDD 0 ~ 655359999 Data Register
W DBx FFFFFDDDDD 0 ~ 1070065535 Data Register
DW DBDn FFFFFDDDD 0 ~ 655359999 Data Register
DW DBDx FFFFFDDDDD 0 ~ 1070065535 Data Register
W DBn_String FFFFFDDDD 0 ~ 655359999 Char Array
W DBx_String FFFFFDDDDD 0 ~ 1070065535 Char Array
W DBn_String1 FFFFFDDDD 0 ~ 655359999 String
W DBx_String1 FFFFFDDDDD 0 ~ 1070065535 String
DW DBDn_String FFFFFDDDD 0 ~ 655359999 Char Array
DW DBDx_String FFFFFDDDDD 0 ~ 1070065535 Char Array
W DB1 ~ DB99 DDDDD 0 ~ 65535 Data Register
DW S5TIME_10Ms FFFFFDDDD 0 ~ 655359999 10MS ~ 9S990MS
DW S5TIME_100Ms FFFFFDDDD 0 ~ 655359999 100MS ~ 1M39S900MS
DW S5TIME_1S FFFFFDDDD 0 ~ 655359999 1S ~ 16M39S
DW S5TIME_10S FFFFFDDDD 0 ~ 655359999 10S ~ 2H46M30S
 Double word and floating point value must use DBDn device type.
 When using DBn, DBDn, DBLn, DBx, DBDx, DBLx addresses, the object address
must be an even number due to the limitation of the original software protocol.
PLC Connection Guide

PLC Setting:
Note: Please follow the settings below, or the communication may fail.

1. Do not check [DB UTILITAIRES] -> [Attributes] -> [Optimized block access]

2. Check [General] -> [Protection] -> [Permit access with PUT/GET communication from
remote partner]
PLC Connection Guide

How to import address tags using TIA portal?


1. Exporting PLC Tags (.xlsx file format).
1.1 Under [PLC tags] create the address tags and then click the Export icon.




1.2 Designate the directory to save the file and click OK button.
PLC Connection Guide
2. Exporting Program Blocks (.scl file format).
2.1 Under [Program blocks] create “Data_block_1 [DB1]” as shown in the following figure.
Click the right mouse button on [DB1] and then click [Generate source from blocks].

2.2 In EasyBuilder click [New PLC…], select Siemens S7-1500 (Ethernet) PLC type, and
then click [Settings…] to set the parameters.
PLC Connection Guide

2.3 Click [Import Tag…] button.

2.4 Select file type (*.sd; *.db) or select TIA file (*.apxx) for import. Compiling the TIA file
by using TIA software before import is necessary to avoid importing incomplete data.
*Note1. Please compile your project before importing TIA files (*.ap12~16).
PLC Connection Guide

Note: CPU 1510SP-1 PN (6ES7510-1DJ01-0AB0)


Unable to import using TIA project (*.ap*), please use [Get tag info] instead.

2.4.1 Import Files (*.sd; *.db)


Select the PLC Tags and Program Blocks to be imported, click [Import] button, and
then click [OK] to leave when the tags are imported successfully.
* At least one db file must be imported. If only plc tags cannot be imported
successfully.
PLC Connection Guide
2.42 Import Files (*.ap*)
Select the tags to be imported and then click OK.
(Support multiple devices in the same project)

2.5 The following message window is shown if the import has succeeded.

Get Tag Info:


1. In S7-1200/1500 program software create PLC program and tag and then download
to PLC.
2. Select Go offline, EasyBuilder will connect to PLC and get tag data. In PLC type
select “SIEMENS S7-1200/1500 (Absolute Addressing) (Ethernet)”.
PLC Connection Guide
3. Click “Settings…”, input PLC IP address.

4. Check the PLC that is not connected to any PC. Click “Get tag info…”.

5. Added Tag Manager that allows selecting the Siemens S7-1200/1500 PLC tags to be
imported.
PLC Connection Guide
6. Create an object and click read address “Settings…”

7. In device select “S7-1200/1500” then select “user-defined tag”.

8. Select PLC tag.


PLC Connection Guide

Wiring Diagram:
Ethernet cable:

You might also like