The document is an installation manual for ANL brand chillers, reversible heat pumps, condensing units, and related external units that provides instructions for proper selection, installation, electrical and refrigerant connections, maintenance, and disposal of the equipment. The manual includes technical specifications, dimensions, typical hydraulic circuits, electrical data, start-up procedures, and safety and compliance information for the installer and end user.

Uploaded by

djezerac
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
927 views72 pages

Aermec Toplotna Pumpa Anl - Series

The document is an installation manual for ANL brand chillers, reversible heat pumps, condensing units, and related external units that provides instructions for proper selection, installation, electrical and refrigerant connections, maintenance, and disposal of the equipment. The manual includes technical specifications, dimensions, typical hydraulic circuits, electrical data, start-up procedures, and safety and compliance information for the installer and end user.

Uploaded by

djezerac
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 72

INSTALLATION MANUAL

ANL
CHILLERS
REVERSIBLE HEAT PUMPS
CONDENSING UNITS

• EXTERNAL UNITS
• HIGH EFFICIENCY
ANL-H
020-202
• HOT WATER PRODUCTION UP TO 50 °C

EN

Aermec
participates in the EUROVENT Programme: LCP.
The products of interest can be found on:
www.eurovent-certification.com
18.01. 6755441_03
EN
ANL-ANLH 020-202

Dear Customer,
Thank you for choosing an AERMEC product. This product is the result of many years of experience and in-
depth research, and it is built using top quality material and advanced technologies.
Moreover, the CE mark guarantees that our appliances fully comply with the requirements of the European
Machinery Directive in terms of safety. We constantly monitor the quality level of our products, and as a result
they are synonymous with Safety, Quality, and Reliability.

Product data may be subject to modifications deemed necessary for improving the product without obligation
to give prior notice.

Thank you again.


AERMEC S.p.A

Aermec reserves the right to make all modification deemed necessary for improving the product at any time with any modification of technical data.

2 18.01. 6755441_03
EN
ANL-ANLH 020-202

1. General instructions for the installer..............................................6 9. Operating characteristics.............................................................29


1.1. Conservation of documentation........................................................ 6 9.1. Cooling setpoint............................................................................... 29
1.2. Safety instructions and installation standards .................................. 6 9.2. Heating setpoint.............................................................................. 29
9.3. Compressor delay timers................................................................. 29
2. Selection and position of installation.............................................7 9.4. Circulating pumps............................................................................ 29
9.5. Anti-freeze alarm............................................................................. 29
3. Dimensions....................................................................................8 9.6. Water flow alarm............................................................................. 29
3.1. Anl 020 ÷ 025 version °|p|h|hp......................................................... 8
3.2. Anl 030 ÷ 040 version °|p|h|hp......................................................... 9 10. Routine maintenance...................................................................30
3.3. Anl 050 ÷ 090 version °|p|h|hp....................................................... 10 10.1. Hydraulic circuit............................................................................... 30
3.4. Anl 102 ÷ 202 version °|p|a|n|q / h|hp|ha|hn|hq........................ 11 10.2. Electric circuit................................................................................... 30
3.5. Anl 020 ÷ 025 version °a|ha............................................................. 12 10.3. Refrigerant circuit............................................................................ 30
3.6. Anl 030 ÷ 040 version °a|ha............................................................. 13 10.4. Mechanical checks........................................................................... 30
3.7. Anl 050 ÷ 090 version °a|°q |ha |hq................................................ 14
3.8. Anl 020 ÷ 025 version c.................................................................... 15 11. Special maintenance....................................................................30
3.9. Anl 030 ÷ 040 version c.................................................................... 16
3.10. Anl 050 ÷ 090 version c.................................................................... 17 12. Disposal.......................................................................................30
3.11. Anl 102 ÷ 202 version c.................................................................... 18
3.12. Anl 050 ÷ 090 version d|da / hd|hda.............................................. 19 13. Procedure for selection of system type........................................31
3.13. Anl 102 ÷ 202 version d|da / hd|hda.............................................. 20 13.1. How to modify a user menu parameter........................................... 31
13.2. How to modify an installer menu parameter................................... 31
4. Typical hydraulic circuits..............................................................21
4.1. Internal and external hydraulic circuit anl “°” | "h" (standard)........ 21
4.2. Internal and external hydraulic circuit anl “°p|°n” / "hp|hn".......... 22
4.3. Internal and external hydraulic circuit anl “°a|°q” / "ha|hq".......... 23
4.4. System example for dhw production with anl50h°
with accessory vmf-acs.................................................................... 24
4.5. System charging............................................................................... 25
4.6. System draining................................................................................ 25

5. Electrical connections..................................................................26

6. Electrical data..............................................................................27

7. Electrical power supply connections............................................27

8. Checks and first start-up..............................................................28


8.1. Preparing for first start-up............................................................... 28
8.2. Start-up ........................................................................................... 28
8.3. First start-up..................................................................................... 28
8.4. Change of season............................................................................. 28
8.5. Change of season from unit circuit board........................................ 28
8.6. Change of season from pr3 remote panel (accessory).................... 28

18.01. 6755441_03 3
EN
ANL-ANLH 020-202
AERMEC S.p.A.
37040 Bevilacqua (VR) Italy – Via Roma, 996
Tel. (+39) 0442 633111 – Fax (+39) 0442 93577
www.aermec.com

DICHIARAZIONE DI CONFORMITÀ UE / EU DECLARATION OF CONFORMITY / DECLARATION DE CONFORMITE UE


KONFORMITÄTSERKLÄRUNG EU / DECLARACIÓN DE CONFORMIDAD UE

ANL
NAME
MODEL* ______________

SERIAL NUMBER________

DATE_________________

Noi, firmatari della presente, dichiariamo sotto la nostra esclusiva responsabilità che l'insieme in oggetto così definito:
We, the undersigned, hereby declare under our own responsibility that the assembly in question, defined as follows:
Nous, Signataires du présent acte, déclarons sous notre responsabilité exclusive que le groupe cité à l’objet défini de la façon suivante:
Die Unterzeichner erklären unter eigener Verantwortung, dass die oben genannte Maschineneinheit, bestehend aus:
Nosotros, los abajo firmantes, declaramos bajo nuestra exclusiva responsabilidad, que el conjunto en cuestión, denominado:

Nome / Name / Nom / Name / Nombre ANL


NOME DI PROVA
Tipo / Type / Type / Typ / Tipo CHILLERS
TIPOLOGIA DI UNITÀ
Modello / Model / Modèle / Model / Modelo MODELLO (PER ESTESO)

A cui questa dichiarazione si riferisce è conforme a tutte le disposizioni pertinenti delle seguenti direttive:
To which this declaration refers, complies with all the provisions related to the following directives:
Auquel cette déclaration se réfère, est conforme à toutes les dispositions relatives des directives suivantes:
Das Gerät, auf welches sich diese Erklärung bezieht, entspricht allen Verordnungen im Zusammenhang mit den folgenden Richtlinien:
A la que esta declaración se refiere, es conforme con todas las disposiciones pertinentes de las siguientes directivas:

Direttiva LVD: 2014/35/UE


Direttiva Compatibilità Elettromagnetica EMCD: 2014/30/UE
Direttiva PED in materia di attrezzature a pressione: 2014/68/UE (modulo A)
Direttiva RoHS sulla restrizione dell’uso di determinate sostanze pericolose nelle AEE: 2011/65/UE

L’oggetto della dichiarazione di cui sopra è conforme alle pertinenti normative di armonizzazione dell’Unione:
The above-mentioned declaration complies with the harmonised European standards:
L'objet de la déclaration reportée ci-dessus est conforme aux normes d’harmonisation relatives de l'Union:
Der Gegenstand der genannten Erklärung entspricht den diesbezüglichen harmonisierten Normen der europäischen Gemeinschaft:
El objeto de la declaración de arriba es conforme con las normativas pertinentes de armonización de la Unión:

CEI EN 60335-2-40: 2005 CEI EN 61000-6-1: 2007 UNI EN 378-2: 2017


CEI EN 60335-2-40/A1: 2007 CEI EN 61000-6-3: 2007 UNI EN 12735-1: 2016
CEI EN 60335-2-40/A2: 2009 CEI EN 55014-1: 2017
CEI EN 60335-2-40/A13: 2012 CEI EN 55014-2: 2016

La presente dichiarazione di conformità è rilasciata sotto la responsabilità esclusiva del fabbricante.


This declaration of conformity has been released under the exclusive responsibility of the manufacturer.
La déclaration de conformité présente est délivrée sous la responsabilité exclusive du fabricant.
Diese Konformitätserklärung wurde unter der ausschließlichen Verantwortung des Herstellers ausgestellt.
Esta declaración de conformidad se ha otorgado bajo la responsabilidad exclusiva del fabricante.

Firmato a nome e per conto di: AERMEC S.p.A.


Signed for and on behalf of: AERMEC S.p.A.
Signé par et au nom de: AERMEC S.p.A.
Unterzeichnet für und im Namen von: AERMEC S.p.A.
Firmado en nombre de: AERMEC S.p.A.

* NOTA: La presente dichiarazione non è valida per tutte le macchine non conformi al regolamento 2016/2281 ed elencate nella Tabella 1 sotto riportata.
* NOTE: This declaration is not valid for machines not compliant with regulation 2016/2281 and listed in Table 1 below.
* REMARQUE: Cette déclaration n'est pas valable pour les machines non conformes au règlement 2016/2281 et listées dans le tableau 1 ci-dessous.
* ANMERKUNG: Diese Erklärung gilt nicht für Maschinen, die nicht der Verordnung 2016/2281 entsprechen und in der nachstehenden Tabelle 1 aufgeführt sind.
* NOTA: Esta declaración no es válida para máquinas que no cumplen con la regulación 2016/2281 y se enumeran en la Tabla 1 a continuación.

Bevilacqua (VR) Commercial Director


Luigi Zucchi

4 18.01. 6755441_03
EN
ANL-ANLH 020-202
AERMEC S.p.A.
37040 Bevilacqua (VR) Italy – Via Roma, 996
Tel. (+39) 0442 633111 – Fax (+39) 0442 93577
www.aermec.com

DICHIARAZIONE DI CONFORMITÀ CE / EC DECLARATION OF CONFORMITY / DECLARATION DE CONFORMITE CE


KONFORMITÄTSERKLÄRUNG EG / DECLARACIÓN DE CONFORMIDAD CE

NAME
ANL-H
MODEL* ______________

SERIAL NUMBER________

DATE_________________

Noi, firmatari della presente, dichiariamo sotto la nostra esclusiva responsabilità che l'insieme in oggetto così definito:
We, the undersigned, hereby declare under our own responsibility that the assembly in question, defined as follows:
Nous, Signataires du présent acte, déclarons sous notre responsabilité exclusive que le groupe cité à l’objet défini de la façon suivante:
Die Unterzeichner erklären unter eigener Verantwortung, dass die oben genannte Maschineneinheit, bestehend aus:
Nosotros, los abajo firmantes, declaramos bajo nuestra exclusiva responsabilidad, que el conjunto en cuestión, denominado:

Nome / Name / Nom / Name / Nombre ANL-HDI PROVA


NOME
Tipo / Type / Type / Typ / Tipo REVERSIBLE
TIPOLOGIA HEAT PUMPS
DI UNITÀ
Modello / Model / Modèle / Model / Modelo MODELLO (PER ESTESO)

A cui questa dichiarazione si riferisce è conforme a tutte le disposizioni pertinenti delle seguenti direttive:
To which this declaration refers, complies with all the provisions related to the following directives:
Auquel cette déclaration se réfère, est conforme à toutes les dispositions relatives des directives suivantes:
Das Gerät, auf welches sich diese Erklärung bezieht, entspricht allen Verordnungen im Zusammenhang mit den folgenden Richtlinien:
A la que esta declaración se refiere, es conforme con todas las disposiciones pertinentes de las siguientes directivas:

Direttiva Macchine: 2006/42/CE


Direttiva Compatibilità Elettromagnetica EMCD: 2014/30/UE
Direttiva PED in materia di attrezzature a pressione: 2014/68/UE
Direttiva RoHS sulla restrizione dell’uso di determinate sostanze pericolose nelle AEE: 2011/65/UE

L’oggetto della dichiarazione di cui sopra è conforme alle pertinenti normative di armonizzazione dell’Unione:
The above-mentioned declaration complies with the harmonised European standards:
L'objet de la déclaration reportée ci-dessus est conforme aux normes d’harmonisation relatives de l'Union:
Der Gegenstand der genannten Erklärung entspricht den diesbezüglichen harmonisierten Normen der europäischen Gemeinschaft:
El objeto de la declaración de arriba es conforme con las normativas pertinentes de armonización de la Unión:

CEI EN 60335-2-40: 2005 CEI EN 61000-6-1: 2007 UNI EN 378-2: 2017


CEI EN 60335-2-40/A1: 2007 CEI EN 61000-6-3: 2007 UNI EN 12735-1: 2016
CEI EN 60335-2-40/A2: 2009 CEI EN 55014-1: 2017
CEI EN 60335-2-40/A13: 2012 CEI EN 55014-2: 2016
La presente dichiarazione di conformità è rilasciata sotto la responsabilità esclusiva del fabbricante
This declaration of conformity has been released under the exclusive responsibility of the manufacturer
La déclaration de conformité présente est délivrée sous la responsabilité exclusive du fabricant
Diese Konformitätserklärung wurde unter der ausschließlichen Verantwortung des Herstellers ausgestellt
Esta declaración de conformidad se ha otorgado bajo la responsabilidad exclusiva del fabricante

La persona autorizzata a costituire il fascicolo tecnico è Luca Martin. Il prodotto, in accordo con la direttiva 2014/68/UE, soddisfa la procedura di Garanzia qualità
Totale (modulo H) con certificato n.06/270-QT3664 Rev. 10 emesso dall’organismo notificato n.1131 CEC via Pisacane 46 Legnano (MI) – Italy.
The person authorised to compile the technical file is Luca Martin. The product, in agreement with Directive 2014/68/EU, satisfies the Total quality Guarantee
procedure (form H) with certificate no. 06/270-QT3664 Rev. 10 issued by the notified body n.1131 CEC via Pisacane 46 Legnano (MI) - Italy.
La personne autorisée à constituer le dossier technique est Luca Martin. Le produit, selon la directive 2014/68/UE, respecte la procédure de Garantie de qualité
Totale (module H) par le certificat n.06/270-QT3664 Rév. 10 émis par l’organisme notifié n.1131 CEC via Pisacane 46 Legnano (MI) - Italie.
Die bevollmächtigt, die technischen Unterlagen zusammenzustellen ist Luca Martin. In Übereinstimmung mit der Richtlinie 2014/68/EU, erfüllt das Produkt die
Anforderungen des Verfahrens der umfassenden Qualitätssicherung (Modul H), Zertifikat Nr.06/270-QT3664 Rev. 10, ausgestellt durch benannte Stelle Nr. 1131
CEC Via Pisacane 46, Legnano (MI) - Italy.
La persona facultada para elaborar el expediente técnico es Luca Martin. El producto, conforme a la directiva 2014/68/UE, cumple con el procedimiento de
Garantía de calidad total (módulo H) con certificado n. 06/270-QT3664 Rev. 10 emitido por el organismo autorizado n. 1131 CEC via Pisacane 46 Legnano (MI) - Italia.

* NOTA: La presente dichiarazione non è valida per tutte le macchine non conformi al regolamento 2016/2281 ed elencate nella Tabella 1 sotto riportata.
* NOTE: This declaration is not valid for machines not compliant with regulation 2016/2281 and listed in Table 1 below.
* REMARQUE: Cette déclaration n'est pas valable pour les machines non conformes au règlement 2016/2281 et listées dans le tableau 1 ci-dessous.
* ANMERKUNG: Diese Erklärung gilt nicht für Maschinen, die nicht der Verordnung 2016/2281 entsprechen und in der nachstehenden Tabelle 1 aufgeführt sind.
* NOTA: Esta declaración no es válida para máquinas que no cumplen con la regulación 2016/2281 y se enumeran en la Tabla 1 a continuación.
Bevilacqua (VR) Commercial Director
Luigi Zucchi

18.01. 6755441_03 5
EN
ANL-ANLH 020-202
AERMEC S.p.A.
37040 Bevilacqua (VR) Italy – Via Roma, 996
Tel. (+39) 0442 633111 – Fax (+39) 0442 93577
www.aermec.com

DICHIARAZIONE DI INCORPORAZIONE CE
EC DECLARATION OF INCORPORATION / DÉCLARATION D'INCORPORATION CE
EINBAUERKLÄRUNG EG / DECLARACIÓN DE INCORPORACIÓN CE

NAME
ANL-C

Noi, firmatari della presente, dichiariamo sotto la nostra esclusiva responsabilità che l'insieme in oggetto così definito:
We, the undersigned, hereby declare under our own responsibility that the assembly in question, defined as follows:
Nous, Signataires du présent acte, déclarons sous notre responsabilité exclusive que le groupe cité à l’objet défini de la façon suivante:
Die Unterzeichner erklären unter eigener Verantwortung, dass die oben genannte Maschineneinheit, bestehend aus:
Nosotros, los abajo firmantes, declaramos bajo nuestra exclusiva responsabilidad, que el conjunto en cuestión, denominado:

Nome / Name / Nom / Name / Nombre ANL-CDI PROVA


NOME
Tipo / Type / Type / Typ / Tipo CONDENSING
TIPOLOGIA UNITS
DI UNITÀ
Modello / Model / Modèle / Model / Modelo MODELLO (PER ESTESO)

A cui questa dichiarazione si riferisce è conforme a tutte le disposizioni pertinenti delle seguenti direttive:
To which this declaration refers, complies with all the provisions related to the following directives:
Auquel cette déclaration se réfère, est conforme à toutes les dispositions relatives des directives suivantes :
Das Gerät, auf welches sich diese Erklärung bezieht, entspricht allen Verordnungen im Zusammenhang mit den folgenden Richtlinien:
A la que esta declaración se refiere, es conforme con todas las disposiciones pertinentes de las siguientes directivas:

Direttiva Macchine: 2006/42/CE

La documentazione tecnica pertinente è stata compilata in conformità alla parte B dell'allegato VII; tale documentazione, o parti di essa, sarà
trasmessa per posta o per via elettronica, in risposta ad una richiesta motivata da parte delle autorità nazionali competenti.
The relevant technical documentation is compiled in accordance with part B of Annex VII; this documentation, or part of it, will be transmitted
by mail, in response to a reasoned request by the national authorities.
La documentation technique pertinente est constituée conformément à l'annexe VII, partie B; cette documentation ou una partie de celui-ci
seront envoyés par la poste ou par voie électronique, à la suite d'une demande dûment motivée des autorités nationales.
Die dazugehoerende technische Dokumentation wurde in Uebereinstimmung mit dem Teil B der Anlage VII zusammengestellt. Diese
Dokumentation (bzw. Teile davon) wird per Post oder per Email uebermittelt, in Beantwortung einer motivierten Forderung seitens der
zustaendigen Nationalbehoerde.
La documentación técnica correspondiente, de conformidad con el anexo VII, parte B; dicha documentación o parte de ella se enviaràn por
correo o por vìa electrònica, en respuesta a un requerimiento debidamente motivado de las autoridades nacionales.

La quasi-macchina a cui fa riferimento questa dichiarazione non deve essere messa in servizio finché la macchina finale in cui deve essere
incorporata non sia stata dichiarata in conformità con le disposizioni della Direttiva Macchine 2006/42/CE.
The partly completed machinery must not be put into service until the final machinery into which it is to be incorporated has been declared in
conformity with the provisions of Directive 2006/42/EC.
La quasi-machine ne doit pas être mise en service avant que la machine finale dans laquelle elle doit être incorporée ait été déclarée conforme
aux dispositions pertinentes de la directive 2006/42/CE.
Die unvollständigen maschine, auf die sich diese Erklaerung bezieht, soll nicht im Betrieb gesetzt werden, solange die Schlussmaschine, in der
sie eingebaut werden soll, nicht in Uebereinstimmung mit den Vorschriften der Maschinevorgabe 2006/42/EC erklaert wird.
La cuasi máquina no deberá ser puesta en servicio mientras la máquina final en la cual vaya a ser incorporada no haya sido declarada conforme
a lo dispuesto en la Directiva 2006/42/CE.

Bevilacqua (VR), Commercial Director


Luigi Zucchi

6 18.01. 6755441_03
EN
ANL-ANLH 020-202

1. GENERAL INSTRUCTIONS FOR THE INSTALLER

The AERMEC ANL units are manufactured in accord- 1.2. SAFETY INSTRUCTIONS AND INSTALLA-
ance with recognised technical and safety standards. TION STANDARDS
They are designed for air conditioning and production
of domestic hot water (DHW) and must be used in a 1. The equipment must be installed by a competent
manner compatible with their performance character- and qualified technician, in compliance with the
istics. All contractual and extra-contractual liabilities applicable national legislation of the country of
causing damage to persons, animals or objects or destination. AERMEC assumes no responsibility
through errors of installation, control or maintenance for any losses incurred by not observing these
or from improper use are excluded by the Company. instructions.
Any uses not expressly indicated in this manual are not 2. Before commencing any works it is necessary
permitted. to CAREFULLY READ THE INSTRUCTIONS AND
MINIMISE ANY RISKS BY TAKING APPROPRIATE
1.1. CONSERVATION OF DOCUMENTATION SAFETY PRECAUTIONS. All relevant personnel
must be made aware of the procedures and
1. Submit the manual with all supplementary possible risks that may arise at the time of instal-
documentation to the system user who will be lation of the unit.
responsible for the conservation of documents
so that they can be available when needed.
2. Read this manual fully: all works must be carried
out by qualified personnel, in accordance with
any applicable current local regulations.
3. The unit must be installed in a manner to render
possible maintenance and/or repair operations.
4. The equipment warranty does not cover any
costs associated with lifting or access equipment
necessary for warranty procedures.
5. Do not modify or tamper with the equipment
as this could result in accidents for which the
manufacturer will not be held responsible. The
warranty will be voided if the above mentioned
warnings are not respected.

18.01. 6755441_03 7
EN
ANL-ANLH 020-202

2. SELECTION AND POSITION OF INSTALLATION

Before proceeding with the installation of the equip- connections.


ment agree the location with the client, taking into ac- In the case of installation where gusts of wind may oc-
count the following points: cur adequately secure the unit using appropriate ties.
1. The base must be able to support the weight of the Ensure the installation of the condensate drain tray on
unit. units that require it (as ACCESSORY).
2. The safe distances between the unit and other
150
equipment or structures must be strictly respected
to ensure the intake and outlet air is free to circu- 200
late.
3. The equipment must be installed by a competent
and qualified technician, in compliance with the
applicable national legislation of the country of
destination, respecting the required minimum
maintenance access spaces.

2.2.1. POSITIONING

Before lifting the unit verify the lifting capability of Free


the equipment being used, taking into account the disc
harg 500
information provided with the packaging. e
To move units (ANL 020-090) over horizontal planes
use forklifts or similar in the most appropriate manner
taking into account the weight distribution of the unit.
ANL 020 - 025 - 030 - 040
When lifting (ANL 102-202) insert through the unit's
base holes lifting bars (NOT PROVIDED) of sufficient
length to locate the lifting chains and safety lugs.
Position the unit in the place indicated by the client, 200
inserting between the unit's base and the base support
a rubber pad (minimum 10 mm thick) or feet anti- 300
vibration mounts (ACCESSORY). For further information
refer to the dimensional tables.
Secure the unit and ensure it is level; check that suf-
ficient access is provided for hydraulic and electrical

500

Free
disc
800 harg
e
ANL 050 - 080 - 090

800

800
1100
ANL 102 - 152 - 202

8 18.01. 6755441_03
EN
ANL-ANLH 020-202

3. DIMENSIONS
3.1. ANL 020 ÷ 025 version °|P|H|HP

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
020 °/H ° 75 174 325 32,1% 31,8% 18,2% 18,0% 9
020 °/H P 77 177 326 31,6% 32,2% 17,9% 18,3% 9
025 °/H ° 75 174 325 32,1% 31,8% 18,2% 18,0% 9
025 °/H P 77 177 326 31,6% 32,2% 17,9% 18,3% 9

310 900
868

OUT 1”¼
OUT 1”¼
194
97

IN1”¼
IN 1”¼
354 69
113
895
D B
122,50 650 122,50
D
C
330

Gy

Ø9

C A A

Gx
Mod. A B C D
VT9 40 30 23 M8

18.01. 6755441_03 9
EN
ANL-ANLH 020-202

3.2. ANL 030 ÷ 040 version °|P|H|HP

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
030 °/H ° 86 183 336 30% 33% 18% 19% 9
030 °/H P 91 180 327 31% 33% 18% 19% 9
040 °/H ° 86 183 336 30% 33% 18% 19% 9
040 °/H P 91 180 327 31% 33% 18% 19% 9

310 900
1000

OUT 1”¼
OUT 1”¼
194
97

IN1”¼
IN 1”¼
354 69
113

D 895 B
122,50 650 122,50
D
C
330

Gy
B

Ø9
C A A

Gx
Mod. A B C D
VT9 40 30 23 M8

10 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.3. ANL 050 ÷ 090 version °|P|H|HP

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
50 °/H ° 120 213 447 30,3% 29,8% 20,1% 19,8% 9
50 °/H P 127 212 436 31,0% 30,1% 19,8% 19,2% 9
70 °/H ° 120 213 447 30,3% 29,8% 20,1% 19,8% 9
70 °/H P 127 212 436 31,0% 30,1% 19,8% 19,2% 9
80 °/H ° 156 217 453 30,3% 29,8% 20,1% 19,8% 9
80 °/H P 163 216 444 31,0% 30,1% 19,8% 19,2% 9
90 °/H ° 156 217 453 29,5% 30,1% 20,0% 20,4% 9
90 °/H P 163 216 444 30,0% 30,3% 19,8% 19,9% 9

384 1124

1252

OUT 1”¼ OUT 1”¼

IN1”¼
100
190

428
IN1”¼
67

1118
D B
229 660 229

D
403

Gy
C

C Ø 11 A
B

Gx
A

Mod. A B C D
VT9 40 30 23 M8

18.01. 6755441_03 11
EN
ANL-ANLH 020-202

3.4. ANL 102 ÷ 202 version °|P|A|N|Q / H|HP|HA|HN|HQ

ANL VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
ANL102 ° 270 381 620 31,7% 32,8% 17,4% 18,0% 15
P 288 382 659 30,6% 31,7% 18,5% 19,1% 15
A 338 382 659 29,5% 30,4% 19,8% 20,4% 15
ANL102H ° 295 381 604 32,2% 33,3% 17,0% 17,5% 15
P 313 381 640 31,2% 32,2% 18,0% 18,6% 15
A 363 381 640 30,1% 30,9% 19,2% 19,8% 15
ANL152 ° 293 383 650 30,8% 32,1% 18,2% 18,9% 15
P 314 383 693 29,6% 30,8% 19,4% 20,2% 15
A 364 383 693 28,7% 29,7% 20,4% 21,2% 15
ANL152H ° 322 382 630 31,4% 32,6% 17,7% 18,3% 15
P 343 382 671 30,3% 31,4% 18,8% 19,5% 15
A 393 382 671 29,3% 30,3% 19,9% 20,5% 15
ANL 202 ° 329 383 600 32,1% 33,6% 16,8% 17,5% 15
P 350 383 641 31,0% 32,4% 17,9% 18,7% 15
A 400 383 641 30,0% 31,2% 19,1% 19,8% 15
ANL 202H ° 358 383 586 32,6% 33,9% 16,4% 17,1% 15
P 379 383 626 31,5% 32,8% 17,5% 18,2% 15
A 429 383 626 30,5% 31,6% 18,6% 19,3% 15
1450

IN
ø 1” ¼

518
1750 OUT
1754 ø 1” ¼
750 750
117

POSITION ANTI-VIBRATION
D 80 1590 80
D
40

20

B
C
750

B
Gy

Ø9 A

A
C Gx Mod. A B C D
VT15 50 30 28,5 M10

12 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.5. ANL 020 ÷ 025 version °A|HA

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
020 °/H A 99 177 326 35,6% 31,5% 17,4% 15,5% 9
025 °/H A 77 177 326 31,6% 32,2% 17,9% 18,3% 9

384 1124
868

OUT 1”¼
OUT 1”¼

IN1”¼
100
190

428 IN1”¼
67
1118
229 660 229

D B
408

Gy
D

A
C Ø 11
C

Gx
B

Mod. A B C D
VT9 40 30 23 M8

18.01. 6755441_03 13
EN
ANL-ANLH 020-202

3.6. ANL 030 ÷ 040 version °A|HA

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
030 °/H A 103 180 327 39% 32% 16% 13% 9
040 °/H A 103 180 327 39% 32% 16% 13% 9

384 1124

1015

OUT 1”¼
OUT 1”¼

IN1”¼
100
190

428 IN1”¼
67

1118
229 660 229

D B
408

Gy

A
C Ø 11
C

Gx
B

Mod. A B C D
VT9 40 30 23 M8

14 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.7. ANL 050 ÷ 090 version °A|°Q |HA |HQ

ANL MOD. VERS. WEIGHTS C. OF G. A B C D KIT


Gy Gx % % % % VT
50 °/H A 147 212 436 32,2% 31,3% 18,5% 18,0% 15
70 °/H A 147 212 436 32,2% 31,3% 18,5% 18,0% 15
80 °/H A 147 212 436 32,2% 31,3% 18,5% 18,0% 15
90 °/H A 183 216 444 31,1% 31,3% 18,8% 18,9% 15

550 1165

1281

IN1”¼
340
210

OUT 1”¼
40 Ø 34 480 214

1162 48,5
70 4,3
70
25,3

D B
9

D
550

C
Gy

A
B

C
Ø9
A

Gx
Mod. A B C D
VT15 50 30 28,5 M10

18.01. 6755441_03 15
EN
ANL-ANLH 020-202

3.8. ANL 020 ÷ 025 version C

WARNING
For the weight distribution refer to
versions "° | H"

310 900

Ø 15.88 gas
G
868

Ø 9.52 liquid
L
196

holes for electrical


354 cables
83
143
895
122,50 650 122,50

D B
330

D
Gy

C Ø9
A
C

Gx
B

Mod. A B C D
VT9 40 30 23 M8

16 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.9. ANL 030 ÷ 040 version C

WARNING
For the weight distribution refer to
versions "° | H"

310 900

Ø 15.88 G gas
1000

Ø 12.70 Lliquid
194.5

holes for electrical


354 cables
70
130
895
122,50 650 122,50
D B

D
330
Gy

C A
C

Ø9

Gx
B

Mod. A B C D
VT9 40 30 23 M8

18.01. 6755441_03 17
EN
ANL-ANLH 020-202

3.10. ANL 050 ÷ 090 version C

WARNING
For the weight distribution refer to
versions "° | H"

384 1124
1252

Ø 22 G
Ø 15,88 L
100
190

194,50

428
1118 70,5
130,5
229 660 229
D B
D
403

C
Gy

C A
B

Ø 11
Gx A

Mod. A B C D
VT9 40 30 23 M8

18 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.11. ANL 102 ÷ 202 version C

WARNING
For the weight distribution refer to
versions "° | H"
1450

750 Ø 28 G Ø 34
515

Ø 15.88 L
102

138

D B
80 1590 80
40

20

D
C
750

B
Gy

A
Ø9

A
C Mod. A B C D
Gx VT15 50 30 28,5 M10

18.01. 6755441_03 19
EN
ANL-ANLH 020-202

3.12. ANL 050 ÷ 090 version D|DA / HD|HDA

550 1165 326 OUT 1”

74
540
IN1”
1281

IN1”¼
340
210

OUT 1”¼
40 Ø 34 480 214

1162 48,5
70 4,3
70
25,3

D B D
9
550

C
Gy

C A
B

Ø9
A

Gx

Mod. A B C D
VT9 D|HD 40 30 23 M8
VT15 DA|HDA 50 30 28,5 M10

20 18.01. 6755441_03
EN
ANL-ANLH 020-202

3.13. ANL 102 ÷ 202 version D|DA / HD|HDA

1800
1750

OUT 1”
1450
1158
692

IN1”

249 750 Ø 34

DESUPERHEATER CONNECTIONS IN1”¼

SYSTEM SIDE CONNECTIONS


515

OUT 1”¼
102

D
138

80 1590 80
40

20

B
D
750

C
Gy

Ø9

C Gx A
A

Mod. A B C D
VT15 50 30 28,5 M10

18.01. 6755441_03 21
EN
ANL-ANLH 020-202

4. TYPICAL HYDRAULIC CIRCUITS


4.1. INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT ANL “°” | "H" (standard)

HYDRAULIC HYDRAULIC COMPONENTS


COMPONENTS ANL RECOMMENDED EXTERNAL TO UNIT WARNING
The selection and installation of
components external to the ANL
°|H unit are the responsibility of
the installer and must be carried
out in accordance with good
13 working practices and applica-
4 8 ble standards of the country of
1 5 11 12 11
destination.

7 8
6 WARNING
The hydraulic piping to the unit
3 PD must be adequately sized for the
8
42
13 required flow rate. The water flow
5
9
rate through the heat exchanger
must always be constant.

11

10

WARNING
Carefully clean the system prior to
connection to the unit. This clean-
COMPONENTS PROVIDED AS STANDARD ing eliminates welding slag, dirt,
1 Water filter rust or any other impurities from
2 Differential pressure switch the piping. These impurities may
3 Plate heat exchanger otherwise be deposited within
4 Water temperature sensor (IN/OUT) the unit and cause a malfunction
8 Air vent The connecting piping must be
adequately supported so as not to
impose any weight onto the unit.
COMPONENTS NOT PROVIDED AND RESPONSIBILITY OF THE INSTALLER
5 Anti-vibration joints
6 Safety valve
7 Expansion tank
9 System buffer tank
10 Drain valve
11 Isolating valve
12 Pump
13 Gauge

22 18.01. 6755441_03
EN
ANL-ANLH 020-202

4.2. INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT ANL “°P|°N” / "HP|HN"

HYDRAULIC HYDRAULIC COMPONENTS


COMPONENTS ANL RECOMMENDED EXTERNAL TO UNIT WARNING
The selection and installation
of components external to the
ANL°P|N /ANLHP|HN unit are the
responsibility of the installer and
must be carried out in accord-
13 ance with good working practices
4 7 6 8
12 1 5 11 and applicable standards of the
country of destination.
7 8
WARNING
3 PD The hydraulic piping to the unit
8 must be adequately sized for the
4
13
5 11 required flow rate. The water flow
9
rate through the heat exchanger
must always be constant.

10

WARNING
Carefully clean the system prior to
connection to the unit. This clean-
COMPONENTS PROVIDED AS STANDARD ing eliminates welding slag, dirt,
1 Water filter rust or any other impurities from
2 Differential pressure switch the piping. These impurities may
3 Plate heat exchanger otherwise be deposited within
4 Water temperature sensor (IN/OUT) the unit and cause a malfunction
6 Safety valve The connecting piping must be
adequately supported so as not to
7 Expansion tank
impose any weight onto the unit.
8 Air vent
12 Pump

COMPONENTS NOT PROVIDED AND RESPONSIBILITY OF THE INSTALLER


5 Anti-vibration joints
7 Additional expansion tank (if necessary)
9 System buffer tank
10 Drain valve
11 Isolating valve
13 Gauge

18.01. 6755441_03 23
EN
ANL-ANLH 020-202

4.3. INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT ANL “°A|°Q” / "HA|HQ"

HYDRAULIC HYDRAULIC COMPONENTS


COMPONENTS ANL RECOMMENDED EXTERNAL TO UNIT WARNING
The selection and installation
of components external to the
ANL°A|Q /ANLHA|HQ unit are the
responsibility of the installer and
must be carried out in accord-
13 ance with good working practices
4 7 8
12 1 5 11 and applicable standards of the
country of destination.
8
2 WARNING
3 PD The hydraulic piping to the unit
4 must be adequately sized for the
13
6 7 required flow rate. The water flow
9
5 rate through the heat exchanger
must always be constant.
11

10

WARNING
Carefully clean the system prior to
connection to the unit. This clean-
COMPONENTS PROVIDED AS STANDARD ANL STANDARD ing eliminates welding slag, dirt,
1 Water filter rust or any other impurities from
2 Differential pressure switch / Flow switch (ANL°A|HA 020…040) the piping. These impurities may
3 Plate heat exchanger otherwise be deposited within
4 Water temperature sensor (IN/OUT) the unit and cause a malfunction
6 Safety valve The connecting piping must be
adequately supported so as not to
7 Expansion tank
impose any weight onto the unit.
8 Air vent
9 System buffer tank
12 Pump

COMPONENTS NOT PROVIDED AND RESPONSIBILITY OF THE INSTALLER


5 Anti-vibration joints
7 Additional expansion tank (if necessary)
10 Drain valve
11 Isolating valve
13 Gauge

24 18.01. 6755441_03
EN
ANL-ANLH 020-202

4.4. SYSTEM EXAMPLE FOR DHW PRODUCTION WITH ANL50H° WITH ACCESSORY VMF-ACS

2 1

3
8

6
5

ANL050H°
VMF SYSTEM for the CONTROL AND PRODUCTIONS OF DHW (ACCESSORIES) 9
1 E5 (white or black)
VMF-ACS3KTN | 6KTN |8KTN
Control of:
2 - 3 way valve
- Sensor DHW storage tank
- Immersion heater DHW storage tank (for integration and anti-legionella cycle)
3 3 way valve (not supplied)
Immersion heater DHW storage tank (not supplied) (for integration and anti-legionella
4
cycle)
5 Interface board RS485 (ACCESSORY MODU-485A) 10

6 DHW storage tank (not supplied)


8 System buffer tank (not supplied)

9 For further information refer to the specific


VMF system documentation available on the
website:
www.aermec.com

10 Accessory required for the unit to communi-


cate with the VMF system

18.01. 6755441_03 25
EN
ANL-ANLH 020-202

4.5. SYSTEM CHARGING


WARNING
Confirm the hydraulic integrity of the Before commencing the charging procedure position charging valve external to the unit
joints. the main isolator of the unit in the OFF position. 5. W
hen water exits the terminal units air vents
1. Ensure that the system drain valve is closed close them and continue charging until the
WARNING 2. Open all the system air vents and of the terminal required system operating pressure is reached.
It is recommended to repeat this pro- units
cedure after the unit has operated for 3. Open the system isolating valves
a few hours and to periodically check 4. Start filling slowly opening the system water
the system pressure. Charging to be
done with unit off (pump OFF).

4.6. SYSTEM DRAINING


1. Before commencing draining the draining proce-
dure position the main isolator of the unit in the
OFF position
2. Ensure the system water charging valve is closed
3. Open the system drain valve external to the unit
and all the system air vents and of the terminal
units.

26 18.01. 6755441_03
EN
ANL-ANLH 020-202

5. ELECTRICAL CONNECTIONS
The ANL units are fully factory wired and only require
All electrical works must be carried out by PERSONNEL WITH THE APPROPRIATE LEGAL
connection to the power supply network, downstream
QUALIFICATIONS, trained and aware of the risks relating to such works.
of an isolator, in accordance with the applicable wiring
The design of the cabling and related components must be carried out by PERSONNEL WITH
standards of the country of installation.
It is recommended to check the following items:
APPROPRIATE QUALIFICATIONS TO DESIGN ELECTRICAL INSTALLATIONS, following interna-
1. The electrical network is capable of meeting the
tional and national standards of the location the unit is installed, in accordance with current
electrical input data shown in the table below.
legal requirements.
2. The unit is only powered up on completion of
any hydraulic and electrical works.
3. Comply with the indicated phasing and earth
For installation details refer to the electrical wiring schematics supplied with the unit. The
requirements.
electrical wiring schematic together with the manuals must be conserved with care and
4. The power supply cable must have the appropri-
MADE AVAILABLE FOR FUTURE REFERENCE.
ate protection against short circuits, residual
current and earth leakage with suitable isolation
The weatherproof seals of the equipment must be checked before making electrical connec-
from other devices.
tions and the unit most only be powered on completion of all electrical and hydraulic works.
5. The tolerance on the power supply voltage is
±10% of the nominal voltage rating of the unit
(for three phase units a maximum imbalance of For longer cable lengths or different types of cable
3% between phases is permitted). If these values installations, the DESIGNER is responsible for correctly
are not met please contact the power supply sizing the isolator, circuit breaker, earthing protection
company. and cable sizes, based on:
6. For the electrical connections use double insu- WARNING
• Length Using the water piping to earth
lated cables in accordance with applicable wiring • Type of cable
standards. the unit is not permitted.
• Electrical input of the unit, distance and operat-
ing ambients.
MANDATORY REQUIREMENTS
1. A magneto-thermal circuit breaker conforming WARNING
to IEC-EN standards (contact aperture minimum Verify that all terminals are tight
3 mm) is required, with adequate protection in on power carrying conductors be-
accordance with the data provided in the follow- fore first start-up and 30 days after
ing table, to be installed as close as possible to putting into service. Afterwards
the unit. check twice yearly.
2. An effective earth connection is required. The Loose terminals can result in
manufacturer cannot be held responsible for overheating of cables and com-
any damages caused by lack of, or inadequate, ponents..
earthing of the unit.
3. For three phase units check the correct cable
phasing.

The cable cross sections shown in the following cable


are the recommended values based on a maximum 50
m cable length.

18.01. 6755441_03 27
EN
ANL-ANLH 020-202

6. ELECTRICAL DATA

TOTAL INPUT RECOMMENDED CABLE CROSS SECTION


Power supply
ANL° | H

Compressors
L.R.A. F.L.A. SEZ. A SEZ. B EARTH IL

Fans [n°]
Version 400V/3N/50Hz

[n°]
phases cables per Cross section Total cables
[A] [A] [mm2] [mm2] [A]
[n°] phase [n°] [mm2] [n°]
° 1 1 59,5 16,5 1 1 4 2 0,5 4 25
020 230V/1/50Hz
P 1 1 26,5 17,5 1 1 4 2 0,5 4 25
° 1 1 62,5 16,5 1 1 4 2 0,5 4 25 PE
025 230V/1/50Hz
P 1 1 63,5 17,5 1 1 4 2 0,5 4 25
° 1 1 83,7 19,7 1 1 6 2 0,5 6 25 L1 L2 L3 N
030 230V/1/50Hz
P 1 1 84,7 20,7 1 1 6 2 0,5 6 25
° 1 1 98,7 23,7 1 1 6 2 0,5 6 32
040 230V/1/50Hz
P 1 1 99,7 24,7 1 1 6 2 0,5 6 32
° 1 1 26,5 6,0 3+N 1 2,5 4 0,5 2,5 16
020 400V/3N/50Hz
P 1 1 27,5 7,0 3+N 1 2,5 4 0,5 2,5 16
° 1 1 32,5 6,0 3+N 1 2,5 4 0,5 2,5 16
025 400V/3N/50Hz
P 1 1 33,5 7,0 3+N 1 2,5 4 0,5 2,5 16
° 1 1 35,7 6,7 3+N 1 2,5 4 0,5 2,5 16 230/1/50Hz
030 400V/3N/50Hz
P 1 1 36,7 7,7 3+N 1 2,5 4 0,5 2,5 16
° 1 1 48,7 8,7 3+N 1 2,5 4 0,5 2,5 16
040 400V/3N/50Hz
P 1 1 49,7 9,7 3+N 1 2,5 4 0,5 2,5 16
° 1 2 65,3 11,3 3+N 1 4 4 0,5 4 16
050 400V/3N/50Hz P 1 2 67,3 13,3 3+N 1 4 4 0,5 4 16 PE
N|Q 1 2 68,0 14,0 3+N 1 4 4 0,5 4 16
° 1 2 75,3 13,5 3+N 1 4 4 0,5 4 16 L1 N
070 400V/3N/50Hz P 1 2 77,3 15,5 3+N 1 4 4 0,5 4 16
N|Q 1 2 78,0 16,2 3+N 1 4 4 0,5 4 16
° 1 2 102,3 16,3 3+N 1 6 4 0,5 6 25
080 400V/3N/50Hz P 1 2 104,3 18,3 3+N 1 6 4 0,5 6 25
N|Q 1 2 105,0 19,0 3+N 1 6 4 0,5 6 25
° 1 2 96,3 17,3 3+N 1 6 4 0,5 6 25
090 400V/3N/50Hz P 1 2 98,3 19,3 3+N 1 6 4 0,5 6 25
N|Q 1 2 99,0 20,0 3+N 1 6 4 0,5 6 25
° 2 2 76,0 22,0 3+N 1 10 4 0,5 10 25
100 400V/3N/50Hz P 2 2 77,4 23,4 3+N 1 10 4 0,5 10 25 LEGEND
N|Q 2 2 78,8 24,8 3+N 1 10 4 0,5 10 25 F.L.I.: Maximum power input
° 2 2 87,0 26,0 3+N 1 16 4 0,5 16 45 F.L.A.: Maximum current input
150 400V/3N/50Hz P 2 2 89,8 28,8 3+N 1 16 4 0,5 16 45 L.R.A.: Starting current
N|Q 2 2 90,5 29,5 3+N 1 16 4 0,5 16 45 Sez A: Power supply connection
° 2 2 117,0 34,0 3+N 1 16 4 0,5 16 45 3+N: 3 phase + Neutral
200 400V/3N/50Hz P 2 2 119,8 36,8 3+N 1 16 4 0,5 16 45 Sez B: Control and safeties connection
N|Q 2 2 120,5 37,5 3+N 1 16 4 0,5 16 45 EARTH: Earth connection to the unit
IL: Main isolator

7. ELECTRICAL POWER SUPPLY CONNECTIONS


WARNING
1. Before making the electrical connections ensure in the case of three phase units (400V/3N/50Hz).
CHECKS AND FIRST START-UP
that the isolator is open. 9. Replace the inspection panels.
It is reminded that for units of this
2. Open the front control panel. 10. Ensure that all protection removed for the elec-
series, if requested by the Aermec
3. Use the holes provided in the lower part of the trical connection are replaced before powering
client or the legal owner and only on
cabinet for the electrical power supply and for the unit.
ITALIAN territory, free start-up is pro-
other external wiring connections. 11. Place the main isolator (external to the unit) to
vided by the regional Aermec techni-
4. Enter cables into the control panel only through “ON”.
cal assistance service. The start-up
the apertures provided.
must be previously agreed based on
5. Avoid direct contact with un-insulated copper
the intended time of completion of
tubes and compressors.
installation. Before the start-up all
6. Identify the terminals for electrical connection
the works (electrical and hydraulic
with reference to the wiring diagram provided
connections, filling and venting of air
loose with the unit.
in the system) must be completed.
7. Take the power cable into the control panel and
connect to terminals U-N and PE with respect to
(U) phase, (N) neutral, (PE) earth in the case of
single phase units (230V/50Hz),
8. U-V-W for phases, N for neutral and PE for earth

28 18.01. 6755441_03
EN
ANL-ANLH 020-202

8. CHECKS AND FIRST START-UP

HYDRAULIC CIRCUIT
SAFETY AND CONTROL DEVICES
WARNING 1. Check that all hydraulic connections have been CHECK:
Before carrying out the following correctly installed, that the instructions on the - The manual high pressure pressostat, which stops
checks ensure the unit is discon- labels have been followed, and that a mechani- the compressor and generates and alarm when the
nected from the power supply. cal filter has been installed on the inlet to the discharge pressure exceeds the preset value. The
Ensure that the main isolator is in evaporator. (Mandatory component otherwise correct operation is checked by closing the refriger-
the OFF position and locked in that the warranty will be voided). ant isolating valve to the heat exchanger (in cooling
position with appropriate warning 2. Confirm that the pump(s) are operating and that mode) and keeping a check on the high pressure
label attached. Before starting the the flow rate is sufficient to make the contact on gauge, verify the operation corresponds to the rated
procedures check for the absence of the flow switch. value. Warning: in the event the pressostat does
voltage with a voltmeter or phase 3. Check the water flow rate by measuring the not operate at the rated value immediately stop
checker. differential pressure across the evaporator inlet the compressor and investigate the cause. Reset is
and outlet and calculating the flow from the manual but can only be done when the pressure
evaporator pressure drop diagram provided in drops below the differential setting. (For the values
the documentation. of the trip and differential setting refer to the tech-
8.1. PREPARING FOR FIRST START-UP 4. Check the correct functioning of any flow nical manual).
switch installed; close the isolating valve on the
It is reminded that for units of this series, if requested evaporator outlet and observe the result on the - Anti-freeze protection
by the Aermec client or the legal owner and only unit display panel; open the valve and reset the The electronic control of the anti-freeze protection
on ITALIAN territory, free start-up is provided by the flow trip alarm. is from the water temperature sensor leaving the
regional Aermec technical assistance service. The evaporator prevents freezing of water when the
start-up must be previously agreed based on the 8.3. FIRST START-UP temperature is too low. The operation of the anti-
intended time of completion of installation. Before the freeze protection can be checked by increasing the
start-up all the works (electrical and hydraulic connec- After having rigorously followed the above checks it is setpoint value until it is above the temperature of
tions, filling and venting of air in the system) must be possible to start the unit: leaving water and checking the water temperature
completed. 1. Close the electrical panel. with a high precision sensor. Confirm that the unit
2. Turn the main isolator to ON. stops and generates the responding alarm. After this
8.2. START-UP 3. Press the key ON for 3 seconds to start the check reset the anti-freeze setpoint to the original
unit. value.
8.2.1. PRELIMINARY CHECKS BEFORE POWER- Pressing the key ON displays the water
ING UP temperature and the operating mode of the unit. 8.4. CHANGE OF SEASON
Check the operating setpoint parameters and
Check: reset any alarms present . After a few minutes 8.5. CHANGE OF SEASON FROM UNIT CIR-
1. All safety precautions have been followed. the unit will start. CUIT BOARD
2. The unit has been appropriately fixed to the
support base. 8.3.1. CHECKS WITH THE UNIT RUNNING Access the USER SET menu with the key and
3. Minimum clearance spaces have been ob- confirm the password 000 pressing key . Using the
served. REFRIGERANT CIRCUIT arrow key display the parameter STA index 0 of the
4. Power supply cables are correctly sized and ca- CHECK: menu and select pressing the key . Using the arrow
pable of supporting the electrical requirements - That the compressor input current of the compres- keys select the value for either: VALUE 0 cooling
of the unit (see section on electrical data) and sors is less than that indicated in the table of electri- mode operation, or, VALUE 1 heating mode operation.
that the unit is correctly earthed. cal data. Confirm the selection pressing key and exit the
5. All electrical connections are correctly termi- - That in three phase models the compressor noise is menu with the key .
nated and tightened. not abnormal, indicating a reverse rotation. In this
case reverse one of the phases. 8.6. CHANGE OF SEASON FROM PR3 RE-
8.2.2. CHECKS TO BE DONE WHEN POWERED UP - That the voltage values are within the determined MOTE PANEL (ACCESSORY)
limits and that the phase imbalance (three phase
1. Apply power to the unit by turning the main iso- power) is less than 3%. If the PR3 remote panel (accessory) is installed it must
lator to the ON position. The display will power - Presence of any refrigerant leaks, in particular be enabled after making the electrical connections.
up after several seconds after applying power, from connections to gauges, pressure transducers
check that the operating status is on OFF (OFF BY and pressostats. (Vibrations during transportation 8.6.1. REMOTE PANEL ENABLING
KEYB on the lower part of the display). may have loosened connections).
2. Check with a tester that the power supply volt- - Superheat Access the INSTALLER SET menu with the key and
ages on the phases U-V-W are 400V ±10%, check Compare the compressor suction temperature with insert the menu access password: password installer
that the phase imbalance is not greater than 3%. a contact temperature sensor reading with the 030. Using the arrow keys display the parameter
3. Check that the connections made by the installer temperature of the low pressure gauge (saturated PAN index 9 of the menu and select pressing the key
comply with the documentation. suction temperature corresponding to the evaporat- . Using the arrow keys select from the desired
4. Check that the compressor crankcase heater(s) ing pressure). The difference between these two values of:
are operating by measuring the increase of oil temperatures is the superheat value. The optimal VALUE 1:
sump temperature. The heater(s) must be in values are between 4 and 8 K. • SEASON CHANGE from the unit circuit board
operation for at least 12 hours before starting - Discharge temperature • ON/OFF CONTROL from the PR3
the compressor, and in all cases the sump oil If the values of sub-cooling and superheat are VALUE 2:
temperature must be 10-15 K above ambient normal the temperature measured in the discharge • SEASON CHANGE controlled from the PR3
temperature. line from the compressor must be 30/40 K above • ON/OFF CONTROL from the unit
the condensing temperature. VALUE 3:

18.01. 6755441_03 29
EN
ANL-ANLH 020-202

• SEASON CHANGE controlled from the PR3


• ON/OFF CONTROL from the PR3

Confirm the selection pressing key and exit the


menu with the key

Once the PR3 remote panel is enabled the change of


season selection can be made directly from the switch
(fig.1). The unit will automatically switch on and off
with the selected operating mode.

For further information refer to the USER manual.

(fig.1)

9. OPERATING CHARACTERISTICS
WARNING
9.1. COOLING SETPOINT 9.5. ANTI-FREEZE ALARM 11
The anti-freeze setpoint
(Factory default) = 7°C, ∆t = 5 K. The alarm is always active even in standby mode.
11 can only be adjusted by an
To prevent damage to the plate heat exchanger by
authorised service centre and
9.2. HEATING SETPOINT freezing of the water within the unit is stopped and
only after verifying that the
an alarm raised if the water temperature drops below
hydraulic circuit has the cor-
(Factory default) = 45°C, ∆t = 5 K. the minimum anti-freeze setpoint of 3°C. The unit can
rect % of anti-freeze solution.
only re-start after a manual reset and if the anti-freeze
In the event of a momentary power interruption the sensor reads a water temperature above 4°C 12. With
12
If this alarm occurs immediate-
selected operating mode will be retained in memory. the unit in off mode and with a water temperature
ly call the authorised technical
below 4°C the factory standard fitted electric heaters
service assistance.
9.3. COMPRESSOR DELAY TIMERS on the heat exchanger are turned on, and turned off
when the water temperature exceeds 5°C. The water
To avoid excessive compressor starts two functions are pump always remains active.
provided:
WARNING
- Minimum time from last stop 60 seconds in cooling 9.6. WATER FLOW ALARM FOR 230V/1/50Hz UNITS:
mode.
The unit is provided with a compres-
- Minimum time from last start 300 seconds in heat- The unit has a low water flow rate alarm using a fac-
sor soft starter. This device contains
ing mode. tory fitted differential pressure switch or flow switch.
capacitors that could overheat
This safety activates after the first 30 seconds of pump
through repeated quick starts. If
9.4. CIRCULATING PUMPS operation if the water flow rate is not sufficient. The
power supply is removed wait at
operation of this alarm stops the compressors and the
least 3 minutes before powering up.
The wiring schematic provides outputs to control pump.
the circulating pumps. The system side pump starts
immediately and after 30 seconds of operation, when
the water flow is stabilised, the pressure differential/
flow switch control function is enabled. If no alarms
are present the unit will start.

30 18.01. 6755441_03
EN
ANL-ANLH 020-202

10. ROUTINE MAINTENANCE 10.4. MECHANICAL CHECKS


WARNING
For 230V/1/50Hz units with soft- It is forbidden to carry out any cleaning operation CHECK:
start, if power is removed for before isolating from the power supply 1. 1. Tightness of screws, of compressors and electri-
reasons of fault or maintenance, it Confirm no voltage is present before commencing cal panel and external panelling of the unit. Poor
is required to wait 5 minutes before works. fixings cause noise and abnormal vibrations.
re-applying power to the unit to Periodic maintenance is a fundamental requirement to 2. The state of the unit structure.
ensure proper operation. ensure efficient unit operation both in terms of opera- Treat any parts showing signs of corrosion with
tion and energy efficiency. the appropriate paints to reduce or eliminate
rust.
The fundamental required annual checks are:
11. SPECIAL MAINTENANCE
WARNING
10.1. HYDRAULIC CIRCUIT
We recommend a service log book is
The ANL units are factory charged with R410A and
provided for the unit (responsibility
CHECK: tested. In normal operation they therefore do not
of the user) to keep records of any
1. Water circuit is filled. require any intervention from the technical assistance
works on the unit, which will aid
2. Water filter is clean. service in relation to the refrigerant charge. Over time
maintenance and repair works. Note
3. Operation of the differential pressure or flow some small leaks can appear, resulting in refrigerant
in the service log book date, type of
switch. discharges of the circuit and causing a malfunction of
works (routine maintenance, inspec-
4. Absence of air in the system (vent). the unit. In this case the leaks have to be found and
tion or repair), describing the event
5. Water flow rate is always constant through the repaired and the unit recharged in accordance, and as
and the measures taken.
evaporator. required, under current legislation and good working
6. Condition of the hydraulic piping insulation. practices.
7. The percentage of anti-freeze liquid, as may be
required. 12. DISPOSAL
10.2. ELECTRIC CIRCUIT Ensure that the disposal of the unit is carried out in
WARNING accordance with the current legal requirements.
It is FORBIDDEN to charge with CHECK:
refrigerant circuit with a refrigerant 1. Operation of safeties.
type different to that indicated. Us- 2. Power supply voltage.
ing a different refrigerant can cause 3. Electrical power input.
serious damage to the unit. 4. Tightness of connections and terminals.
5. Operation of the compressor crankcase heater.

10.3. REFRIGERANT CIRCUIT

CHECK:
1. State of compressors.
2. Efficiency of the plate heat exchanger.
3. Operating pressures.
4. Leaks to confirm the correct operating refriger-
ant charge.
5. Operation of the high and low pressure pres-
sostats
6. Efficient operation of the filter drier.

18.01. 6755441_03 31
EN
ANL-ANLH 020-202

13. PROCEDURE FOR SELECTION OF SYSTEM TYPE

Several parameters of the MODU CONTROL board 13.1. HOW TO MODIFY A USER MENU 13.2. HOW TO MODIFY AN INSTALLER MENU
have to be set, based on the type of system the unit is PARAMETER PARAMETER
installed.
These changes of parameters are summarised in the To access the USER setting press the key and To enter and modify the INSTALLER menu follow the
table below to permit the installer to make the appro- confirm the password 000 pressing the key . The same procedure as the USER menu above.
priate selections of the unit's electronic circuit board. display will show the parameters of the USER index
as three identifying characters; the index remains dis- Password INSTALLER menu: 030
played for a second and then is replaced by the value
of the parameter it relates to.
To move to the following parameter use the arrow keys
. To modify a parameter press the key , modify the
value using the arrow keys and confirm the modifica-
tion pressing the key . To exit the menu press the
key .

QUESTION ANSWER WHAT TO DO


• The unit is a cooling only model • Go to question 2

• Radiant panels • Enter in parameter StC (index 3 menu USER) with the value of 35 °C
(1) What type of terminals are
installed in the heating circuit?
• F an coil units or low temperature • Enter in parameter StC (index 3 menu USER) with the value of 45 °C (default value)
radiators
• Other applications • Enter in parameter StC (index 3 menu USER) with the value of 55 °C
• Not installed • Go to question 3
• Installed • Enter in parameter PAN (index 9 menu INSTALLER) with the appropriate value:
Value (1):
• Season selection controlled from the unit circuit board
• ON/OFF control from the PR3
(2) Is the remote control accessory
Value (2):
panel installed (PR3)?
• Season selection controlled from the PR3
• ON/OFF control from the unit circuit board
Value (3):
• Season selection controlled from the PR3
• ON/OFF control from the PR3
(3) Is domestic hot water produc- • Not present • Go to question 5
tion present? • Present • Enter in parameter ASA (menu INSTALLER) with the value (1)
• Not present • Go to question 5
(4) In the domestic hot water circuit
• Present • Enter in parameter AAS (index C menu INSTALLER) with the appropriate value (in seconds):
is a three way diverting valve
this parameter shows the reversing time for the three way diverting valve in the circuit for the
present?
production of domestic hot water
• Not present • No function
• Present • This parameter enables a digital contact ID (shown on the electrical schematic with the
reference TRA) onto which to connect an ambient thermostat with which to disable the
compressors and electric heaters. Enter in parameter trA (index D menu INSTALLER), with the
appropriate value selecting from:
(5) Is an ambient thermostat
1. Value (1 or 2): ENABLED
present?
2. Value (0 or 3): DISABLED
3. It is reminded that the OPEN state of the contact represents:
• stops compressors and heaters if the parameter value is set to 1
• stops compressors, pump and heaters if the parameter value is set to 2
• pump alarm (as in the previous software version), if the parameter value is set to 3

WARNING
For more information refer to the USER manual provided with the unit and available on the website
www.aermec.com

32 18.01. 6755441_03
34
ANL020 ANL020M ANL020A ANL020AM ANL020P

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 0 0

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 0 0

Outdoor sound power dB(A) 61 61 61 61 61 61 61 61 61 61

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL020PM ANL020H ANL020HM ANL020H ANL020HM

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW 0 0 ­ 6 ­ 6 ­ 6 ­ 6

Seasonal energy efficiency % 0 0 ­ 130 ­ 130 ­ 130 ­ 130

Annual energy consumption kWh 0 0 ­ 9535 ­ 9535 ­ 9535 ­ 9535

Indoor sound power dB(A) 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) 61 61 ­ 61 ­ 61 ­ 61 ­ 61

Colder climate conditions

Rated heat output kW 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 ­ 8 ­ 8 ­ 8 ­ 8

Seasonal energy efficiency % 0 0 ­ 158 ­ 158 ­ 158 ­ 158

Annual energy consumption kWh 0 0 ­ 6765 ­ 6765 ­ 6765 ­ 6765

* = This model isn't suitable for average temperature applications.
EN

35
36
ANL020HA ANL020HAM ANL020HA ANL020HAM ANL020HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 6 ­ 6 ­ 6 ­ 6 ­ 6

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 ­ 133 ­ 133

Annual energy consumption kWh ­ 9320 ­ 9320 ­ 9320 ­ 9320 ­ 9320

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 61 ­ 61 ­ 61 ­ 61 ­ 61

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 8 ­ 8 ­ 8 ­ 8 ­ 8

Seasonal energy efficiency % ­ 165 ­ 165 ­ 165 ­ 165 ­ 165

Annual energy consumption kWh ­ 6478 ­ 6478 ­ 6478 ­ 6478 ­ 6478

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL020HPM ANL020HP ANL020HPM ANL025 ANL025M

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 6 ­ 6 ­ 6 0 0 0 0

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 0 0 0 0

Annual energy consumption kWh ­ 9320 ­ 9320 ­ 9320 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 61 ­ 61 ­ 61 61 61 61 61

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 8 ­ 8 ­ 8 0 0 0 0

Seasonal energy efficiency % ­ 165 ­ 165 ­ 165 0 0 0 0

Annual energy consumption kWh ­ 6478 ­ 6478 ­ 6478 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

37
38
ANL025A ANL025AM ANL025P ANL025PM ANL025H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 ­ A+

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 7

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 132

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 10956

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 ­ 0

Outdoor sound power dB(A) 61 61 61 61 61 61 61 61 ­ 61

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 9

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 162

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 7422

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL025HM ANL025H ANL025HM ANL025HA ANL025HAM

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 7 ­ 7 ­ 7 ­ 6 ­ 6

Seasonal energy efficiency % ­ 132 ­ 132 ­ 132 ­ 136 ­ 136

Annual energy consumption kWh ­ 10956 ­ 10956 ­ 10956 ­ 9115 ­ 9115

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 61 ­ 61 ­ 61 ­ 61 ­ 61

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 9 ­ 9 ­ 9 ­ 9 ­ 9

Seasonal energy efficiency % ­ 162 ­ 162 ­ 162 ­ 169 ­ 169

Annual energy consumption kWh ­ 7422 ­ 7422 ­ 7422 ­ 7115 ­ 7115

* = This model isn't suitable for average temperature applications.
EN

39
40
ANL025HA ANL025HAM ANL025HAS ANL025HAMS ANL025HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 6 ­ 6 ­ 6 ­ 6 ­ 6

Seasonal energy efficiency % ­ 136 ­ 136 ­ 136 ­ 136 ­ 136

Annual energy consumption kWh ­ 9115 ­ 9115 ­ 9115 ­ 9115 ­ 9115

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 61 ­ 61 ­ 61 ­ 61 ­ 61

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 9 ­ 9 ­ 9 ­ 9 ­ 9

Seasonal energy efficiency % ­ 169 ­ 169 ­ 169 ­ 169 ­ 169

Annual energy consumption kWh ­ 7115 ­ 7115 ­ 7115 ­ 7115 ­ 7115

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL025HPM ANL025HP ANL025HPM ANL030 ANL030M

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 6 ­ 6 ­ 6 0 0 0 0

Seasonal energy efficiency % ­ 136 ­ 136 ­ 136 0 0 0 0

Annual energy consumption kWh ­ 9115 ­ 9115 ­ 9115 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 61 ­ 61 ­ 61 68 68 68 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 9 ­ 9 ­ 9 0 0 0 0

Seasonal energy efficiency % ­ 169 ­ 169 ­ 169 0 0 0 0

Annual energy consumption kWh ­ 7115 ­ 7115 ­ 7115 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

41
42
ANL030A ANL030AM ANL030P ANL030PM ANL030H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 ­ A+

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 8

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 129

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 12812

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 ­ 0

Outdoor sound power dB(A) 68 68 68 68 68 68 68 68 ­ 68

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 11

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 159

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 9243

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL030HM ANL030H ANL030HM ANL030HA ANL030HAM

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 8 ­ 8 ­ 8 ­ 8 ­ 8

Seasonal energy efficiency % ­ 129 ­ 129 ­ 129 ­ 133 ­ 133

Annual energy consumption kWh ­ 12812 ­ 12812 ­ 12812 ­ 12427 ­ 12427

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 ­ 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 11 ­ 11 ­ 11 ­ 11 ­ 11

Seasonal energy efficiency % ­ 159 ­ 159 ­ 159 ­ 166 ­ 166

Annual energy consumption kWh ­ 9243 ­ 9243 ­ 9243 ­ 8853 ­ 8853

* = This model isn't suitable for average temperature applications.
EN

43
44
ANL030HA ANL030HAM ANL030HAS ANL030HAMS ANL030HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 8 ­ 8 ­ 8 ­ 8 ­ 8

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 ­ 133 ­ 133

Annual energy consumption kWh ­ 12427 ­ 12427 ­ 12427 ­ 12427 ­ 12427

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 ­ 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 11 ­ 11 ­ 11 ­ 11 ­ 11

Seasonal energy efficiency % ­ 166 ­ 166 ­ 166 ­ 166 ­ 166

Annual energy consumption kWh ­ 8853 ­ 8853 ­ 8853 ­ 8853 ­ 8853

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL030HPM ANL030HP ANL030HPM ANL040 ANL040M

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 8 ­ 8 ­ 8 0 0 0 0

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 0 0 0 0

Annual energy consumption kWh ­ 12427 ­ 12427 ­ 12427 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 68 68 68 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 11 ­ 11 ­ 11 0 0 0 0

Seasonal energy efficiency % ­ 166 ­ 166 ­ 166 0 0 0 0

Annual energy consumption kWh ­ 8853 ­ 8853 ­ 8853 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

45
46
ANL040A ANL040AM ANL040P ANL040PM ANL040H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 ­ A+

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 10

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 130

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 15892

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 ­ 0

Outdoor sound power dB(A) 68 68 68 68 68 68 68 68 ­ 68

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 14

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 161

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 11617

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL040HM ANL040H ANL040HM ANL040HA ANL040HAM

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 10 ­ 10 ­ 10 ­ 10 ­ 10

Seasonal energy efficiency % ­ 130 ­ 130 ­ 130 ­ 133 ­ 133

Annual energy consumption kWh ­ 15892 ­ 15892 ­ 15892 ­ 15534 ­ 15534

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 ­ 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 14 ­ 14 ­ 14 ­ 13 ­ 13

Seasonal energy efficiency % ­ 161 ­ 161 ­ 161 ­ 168 ­ 168

Annual energy consumption kWh ­ 11617 ­ 11617 ­ 11617 ­ 10338 ­ 10338

* = This model isn't suitable for average temperature applications.
EN

47
48
ANL040HA ANL040HAM ANL040HAS ANL040HAMS ANL040HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 10 ­ 10 ­ 10 ­ 10 ­ 10

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 ­ 133 ­ 133

Annual energy consumption kWh ­ 15534 ­ 15534 ­ 15534 ­ 15534 ­ 15534

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 ­ 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 13 ­ 13 ­ 13 ­ 13 ­ 13

Seasonal energy efficiency % ­ 168 ­ 168 ­ 168 ­ 168 ­ 168

Annual energy consumption kWh ­ 10338 ­ 10338 ­ 10338 ­ 10338 ­ 10338

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL040HPM ANL040HP ANL040HPM ANL050 ANL050A

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 10 ­ 10 ­ 10 0 0 0 0

Seasonal energy efficiency % ­ 133 ­ 133 ­ 133 0 0 0 0

Annual energy consumption kWh ­ 15534 ­ 15534 ­ 15534 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 69 69 69 69

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 13 ­ 13 ­ 13 0 0 0 0

Seasonal energy efficiency % ­ 168 ­ 168 ­ 168 0 0 0 0

Annual energy consumption kWh ­ 10338 ­ 10338 ­ 10338 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

49
50
ANL050N ANL050P ANL050Q ANL050H ANL050H3

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 ­ A+ ­ A+

Rated heat output kW 0 0 0 0 0 0 ­ 13 ­ 13

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 134 ­ 134

Annual energy consumption kWh 0 0 0 0 0 0 ­ 20043 ­ 20043

Indoor sound power dB(A) 0 0 0 0 0 0 ­ 0 ­ 0

Outdoor sound power dB(A) 69 69 69 69 69 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 ­ 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 ­ 18 ­ 18

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 167 ­ 167

Annual energy consumption kWh 0 0 0 0 0 0 ­ 14400 ­ 14400

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL050H ANL050HA ANL050HA3 ANL050HA ANL050HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 13 ­ 13 ­ 13 ­ 13 ­ 13

Seasonal energy efficiency % ­ 134 ­ 136 ­ 136 ­ 136 ­ 136

Annual energy consumption kWh ­ 20043 ­ 19749 ­ 19749 ­ 19749 ­ 19749

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 69 ­ 69 ­ 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 18 ­ 18 ­ 18 ­ 18 ­ 18

Seasonal energy efficiency % ­ 167 ­ 173 ­ 173 ­ 173 ­ 173

Annual energy consumption kWh ­ 14400 ­ 13901 ­ 13901 ­ 13901 ­ 13901

* = This model isn't suitable for average temperature applications.
EN

51
52
ANL050HP ANL050HQ ANL050HQ ANL070 ANL070A

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 13 ­ 13 ­ 13 0 0 0 0

Seasonal energy efficiency % ­ 136 ­ 128 ­ 128 0 0 0 0

Annual energy consumption kWh ­ 19749 ­ 20983 ­ 20983 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 69 ­ 69 ­ 69 69 69 69 69

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 18 ­ 17 ­ 17 0 0 0 0

Seasonal energy efficiency % ­ 173 ­ 163 ­ 163 0 0 0 0

Annual energy consumption kWh ­ 13901 ­ 13934 ­ 13934 0 0 0 0

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL070N ANL070P ANL070Q ANL070H ANL070H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 ­ A+ ­ A+

Rated heat output kW 0 0 0 0 0 0 ­ 16 ­ 16

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 139 ­ 139

Annual energy consumption kWh 0 0 0 0 0 0 ­ 23781 ­ 23781

Indoor sound power dB(A) 0 0 0 0 0 0 ­ 0 ­ 0

Outdoor sound power dB(A) 69 69 69 69 69 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 ­ 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 ­ 22 ­ 22

Seasonal energy efficiency % 0 0 0 0 0 0 ­ 173 ­ 173

Annual energy consumption kWh 0 0 0 0 0 0 ­ 16990 ­ 16990

* = This model isn't suitable for average temperature applications.
EN

53
54
ANL070HA ANL070HA ANL070HP ANL070HP ANL070HQ

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 16 ­ 16 ­ 16 ­ 16 ­ 16

Seasonal energy efficiency % ­ 142 ­ 142 ­ 142 ­ 142 ­ 135

Annual energy consumption kWh ­ 23279 ­ 23279 ­ 23279 ­ 23279 ­ 24486

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 69 ­ 69 ­ 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 22 ­ 22 ­ 22 ­ 22 ­ 21

Seasonal energy efficiency % ­ 180 ­ 180 ­ 180 ­ 180 ­ 172

Annual energy consumption kWh ­ 16329 ­ 16329 ­ 16329 ­ 16329 ­ 16312

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL070HQ ANL080 ANL080A ANL080N ANL080P

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ 0 0 0 0 0 0 0 0

Rated heat output kW ­ 16 0 0 0 0 0 0 0 0

Seasonal energy efficiency % ­ 135 0 0 0 0 0 0 0 0

Annual energy consumption kWh ­ 24486 0 0 0 0 0 0 0 0

Indoor sound power dB(A) ­ 0 0 0 0 0 0 0 0 0

Outdoor sound power dB(A) ­ 69 69 69 69 69 69 69 69 69

Colder climate conditions

Rated heat output kW ­ 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % ­ 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh ­ 0 0 0 0 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 21 0 0 0 0 0 0 0 0

Seasonal energy efficiency % ­ 172 0 0 0 0 0 0 0 0

Annual energy consumption kWh ­ 16312 0 0 0 0 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

55
56
ANL080Q ANL080H ANL080H ANL080HA ANL080HA3

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW 0 0 ­ 21 ­ 21 ­ 21 ­ 21

Seasonal energy efficiency % 0 0 ­ 139 ­ 139 ­ 142 ­ 142

Annual energy consumption kWh 0 0 ­ 31213 ­ 31213 ­ 30554 ­ 30554

Indoor sound power dB(A) 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) 69 69 ­ 69 ­ 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh 0 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 ­ 28 ­ 28 ­ 28 ­ 28

Seasonal energy efficiency % 0 0 ­ 173 ­ 173 ­ 180 ­ 180

Annual energy consumption kWh 0 0 ­ 21623 ­ 21623 ­ 20782 ­ 20782

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL080HA ANL080HP ANL080HP ANL080HQ ANL080HQ

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 21 ­ 21 ­ 21 ­ 20 ­ 20

Seasonal energy efficiency % ­ 142 ­ 142 ­ 142 ­ 136 ­ 136

Annual energy consumption kWh ­ 30554 ­ 30554 ­ 30554 ­ 30382 ­ 30382

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 69 ­ 69 ­ 69 ­ 69 ­ 69

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 28 ­ 28 ­ 28 ­ 28 ­ 28

Seasonal energy efficiency % ­ 180 ­ 180 ­ 180 ­ 173 ­ 173

Annual energy consumption kWh ­ 20782 ­ 20782 ­ 20782 ­ 21623 ­ 21623

* = This model isn't suitable for average temperature applications.
EN

57
58
ANL090 ANL090A ANL090N ANL090P ANL090Q

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 0 0

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 0 0

Outdoor sound power dB(A) 68 68 68 68 68 68 68 68 68 68

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL090H ANL090H ANL090HA ANL090HA3 ANL090HA

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 23 ­ 23 ­ 23 ­ 23 ­ 23

Seasonal energy efficiency % ­ 138 ­ 138 ­ 141 ­ 141 ­ 141

Annual energy consumption kWh ­ 34433 ­ 34433 ­ 33701 ­ 33701 ­ 33701

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 ­ 68

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 31 ­ 31 ­ 31 ­ 31 ­ 31

Seasonal energy efficiency % ­ 171 ­ 171 ­ 178 ­ 178 ­ 178

Annual energy consumption kWh ­ 24220 ­ 24220 ­ 23267 ­ 23267 ­ 23267

* = This model isn't suitable for average temperature applications.
EN

59
60
ANL090HP ANL090HP ANL090HQ ANL090HQ ANL102

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ 0 0

Rated heat output kW ­ 23 ­ 23 ­ 22 ­ 22 0 0

Seasonal energy efficiency % ­ 141 ­ 141 ­ 136 ­ 136 0 0

Annual energy consumption kWh ­ 33701 ­ 33701 ­ 33421 ­ 33421 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 0 0

Outdoor sound power dB(A) ­ 68 ­ 68 ­ 68 ­ 68 76 76

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 0 0

Warmer climate conditions

Rated heat output kW ­ 31 ­ 31 ­ 30 ­ 30 0 0

Seasonal energy efficiency % ­ 178 ­ 178 ­ 172 ­ 172 0 0

Annual energy consumption kWh ­ 23267 ­ 23267 ­ 23302 ­ 23302 0 0

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL102A ANL102N ANL102P ANL102Q ANL102H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 ­ A+

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 28

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 143

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 40453

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 ­ 0

Outdoor sound power dB(A) 76 76 76 76 76 76 76 76 ­ 76

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 37

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 180

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 27462

* = This model isn't suitable for average temperature applications.
EN

61
62
ANL102H ANL102HA ANL102HA ANL102HN ANL102HN

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 28 ­ 27 ­ 27 ­ 26 ­ 26

Seasonal energy efficiency % ­ 143 ­ 140 ­ 140 ­ 130 ­ 130

Annual energy consumption kWh ­ 40453 ­ 39844 ­ 39844 ­ 41320 ­ 41320

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 76 ­ 76 ­ 76 ­ 76 ­ 76

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 37 ­ 36 ­ 36 ­ 36 ­ 36

Seasonal energy efficiency % ­ 180 ­ 181 ­ 181 ­ 166 ­ 166

Annual energy consumption kWh ­ 27462 ­ 26572 ­ 26572 ­ 28973 ­ 28973

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL102HP ANL102HP3 ANL102HP ANL102HQ ANL102HQ

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 27 ­ 27 ­ 27 ­ 26 ­ 26

Seasonal energy efficiency % ­ 140 ­ 140 ­ 140 ­ 130 ­ 130

Annual energy consumption kWh ­ 39844 ­ 39844 ­ 39844 ­ 41320 ­ 41320

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 76 ­ 76 ­ 76 ­ 76 ­ 76

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 36 ­ 36 ­ 36 ­ 36 ­ 36

Seasonal energy efficiency % ­ 181 ­ 181 ­ 181 ­ 166 ­ 166

Annual energy consumption kWh ­ 26572 ­ 26572 ­ 26572 ­ 28973 ­ 28973

* = This model isn't suitable for average temperature applications.
EN

63
64
ANL152 ANL152A ANL152N ANL152P ANL152Q

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 0 0

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 0 0

Outdoor sound power dB(A) 77 77 77 77 77 77 77 77 77 77

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 0 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 0 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 0 0

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL152H ANL152H3 ANL152H ANL152HA ANL152HA

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A++ ­ A++ ­ A++ ­ A+ ­ A+

Rated heat output kW ­ 33 ­ 33 ­ 33 ­ 32 ­ 32

Seasonal energy efficiency % ­ 152 ­ 152 ­ 152 ­ 140 ­ 140

Annual energy consumption kWh ­ 44854 ­ 44854 ­ 44854 ­ 47223 ­ 47223

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 77 ­ 77 ­ 77 ­ 77 ­ 77

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 45 ­ 45 ­ 45 ­ 44 ­ 44

Seasonal energy efficiency % ­ 186 ­ 186 ­ 186 ­ 181 ­ 181

Annual energy consumption kWh ­ 32323 ­ 32323 ­ 32323 ­ 32477 ­ 32477

* = This model isn't suitable for average temperature applications.
EN

65
66
ANL152HAS ANL152HN ANL152HN ANL152HNS ANL152HP

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 32 ­ 32 ­ 32 ­ 32 ­ 32

Seasonal energy efficiency % ­ 140 ­ 136 ­ 136 ­ 136 ­ 140

Annual energy consumption kWh ­ 47223 ­ 48612 ­ 48612 ­ 48612 ­ 47223

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 77 ­ 77 ­ 77 ­ 77 ­ 77

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 44 ­ 43 ­ 43 ­ 43 ­ 44

Seasonal energy efficiency % ­ 181 ­ 175 ­ 175 ­ 175 ­ 181

Annual energy consumption kWh ­ 32477 ­ 32827 ­ 32827 ­ 32827 ­ 32477

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL152HP ANL152HPS ANL152HQ ANL152HQ ANL202

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ 0 0

Rated heat output kW ­ 32 ­ 32 ­ 32 ­ 32 0 0

Seasonal energy efficiency % ­ 140 ­ 140 ­ 136 ­ 136 0 0

Annual energy consumption kWh ­ 47223 ­ 47223 ­ 48612 ­ 48612 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 0 0

Outdoor sound power dB(A) ­ 77 ­ 77 ­ 77 ­ 77 78 78

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 0 0

Warmer climate conditions

Rated heat output kW ­ 44 ­ 44 ­ 43 ­ 43 0 0

Seasonal energy efficiency % ­ 181 ­ 181 ­ 175 ­ 175 0 0

Annual energy consumption kWh ­ 32477 ­ 32477 ­ 32827 ­ 32827 0 0

* = This model isn't suitable for average temperature applications.
EN

67
68
ANL202A ANL202N ANL202P ANL202Q ANL202H

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class 0 0 0 0 0 0 0 0 ­ A++

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 43

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 150

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 59225

Indoor sound power dB(A) 0 0 0 0 0 0 0 0 ­ 0

Outdoor sound power dB(A) 78 78 78 78 78 78 78 78 ­ 78

Colder climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 0

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 0

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 0

Warmer climate conditions

Rated heat output kW 0 0 0 0 0 0 0 0 ­ 58

Seasonal energy efficiency % 0 0 0 0 0 0 0 0 ­ 185

Annual energy consumption kWh 0 0 0 0 0 0 0 0 ­ 41885

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL202H3 ANL202H ANL202HA ANL202HA ANL202HAS

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A++ ­ A++ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 43 ­ 43 ­ 42 ­ 42 ­ 42

Seasonal energy efficiency % ­ 150 ­ 150 ­ 141 ­ 141 ­ 141

Annual energy consumption kWh ­ 59225 ­ 59225 ­ 61540 ­ 61540 ­ 61540

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 78 ­ 78 ­ 78 ­ 78 ­ 78

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 58 ­ 58 ­ 57 ­ 57 ­ 57

Seasonal energy efficiency % ­ 185 ­ 185 ­ 182 ­ 182 ­ 182

Annual energy consumption kWh ­ 41885 ­ 41885 ­ 41842 ­ 41842 ­ 41842

* = This model isn't suitable for average temperature applications.
EN

69
70
ANL202HN ANL202HN ANL202HP ANL202HP ANL202HPS

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
EN

applications applications applications applications applications applications applications applications applications applications

55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ ­ A+ ­ A+

Rated heat output kW ­ 41 ­ 41 ­ 42 ­ 42 ­ 42

Seasonal energy efficiency % ­ 137 ­ 137 ­ 141 ­ 141 ­ 141

Annual energy consumption kWh ­ 61829 ­ 61829 ­ 61540 ­ 61540 ­ 61540

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Outdoor sound power dB(A) ­ 78 ­ 78 ­ 78 ­ 78 ­ 78

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 ­ 0 ­ 0

Warmer climate conditions

Rated heat output kW ­ 56 ­ 56 ­ 57 ­ 57 ­ 57

Seasonal energy efficiency % ­ 177 ­ 177 ­ 182 ­ 182 ­ 182

Annual energy consumption kWh ­ 42269 ­ 42269 ­ 41842 ­ 41842 ­ 41842

* = This model isn't suitable for average temperature applications.
ANL-ANLH 020-202

18.01. 6755441_03
ANL202HQ ANL202HQ ANL202HQS ANL290L00 ANL290L01

Average Low Average Low Average Low Average Low Average Low
Aermec S.p.A. temperature temperature temperature temperature temperature temperature temperature temperature temperature temperature
applications applications applications applications applications applications applications applications applications applications
ANL-ANLH 020-202

18.01. 6755441_03
55 °C* 35 °C 55 °C* 35 °C 55 °C* 35 °C 55 °C 35 °C 55 °C 35 °C

Average climatic conditions

Energy efficiency class ­ A+ ­ A+ ­ A+ 0 0 0 0

Rated heat output kW ­ 41 ­ 41 ­ 41 0 0 0 0

Seasonal energy efficiency % ­ 137 ­ 137 ­ 137 0 0 0 0

Annual energy consumption kWh ­ 61829 ­ 61829 ­ 61829 0 0 0 0

Indoor sound power dB(A) ­ 0 ­ 0 ­ 0 0 0 0 0

Outdoor sound power dB(A) ­ 78 ­ 78 ­ 78 72 72 72 72

Colder climate conditions

Rated heat output kW ­ 0 ­ 0 ­ 0 0 0 0 0

Seasonal energy efficiency % ­ 0 ­ 0 ­ 0 0 0 0 0

Annual energy consumption kWh ­ 0 ­ 0 ­ 0 0 0 0 0

Warmer climate conditions

Rated heat output kW ­ 56 ­ 56 ­ 56 0 0 0 0

Seasonal energy efficiency % ­ 177 ­ 177 ­ 177 0 0 0 0

Annual energy consumption kWh ­ 42269 ­ 42269 ­ 42269 0 0 0 0

* = This model isn't suitable for average temperature applications.
EN

71
AERMEC S.p.A.