"General" Use and Maintenance Manual
"General" Use and Maintenance Manual
MAINTENANCE MANUAL
EN
INSTRUCTIONS MANUAL
CONTENTS
Page
1. DECLARATION OF CONFORMITY – CE .........................................................................................................3
2. GENERAL INFORMATION ................................................................................................................................4
3. PICTOGRAMS AND WARNING SYMBOLS .....................................................................................................5
4. CONDITIONS OF INTENDED USE ...................................................................................................................7
5. CONDITIONS OF IMPROPER USE ..................................................................................................................7
6. RISK ANALYSIS ................................................................................................................................................8
7. TECHNICAL CHARACTERISTICS ...................................................................................................................8
8. OPERATING PRINCIPLE ..................................................................................................................................9
9. PNEUMATIC DIAGRAM ....................................................................................................................................9
10. ELECTRIC MOTORS - TECHNICAL CHARACTERISTICS .......................................................................... 10
11. HANDLING AND LIFTING .............................................................................................................................. 10
12. INSTALLATION .............................................................................................................................................. 11
13. INSTALLATION DIAGRAM ............................................................................................................................ 12
14. CONNECTION................................................................................................................................................. 13
15. WIRING DIAGRAM ......................................................................................................................................... 13
16. BELT TIGHTENING ........................................................................................................................................ 14
17. RECOMMENDATIONS ................................................................................................................................... 17
18. FIRST START-UP ........................................................................................................................................... 17
19. STARTING AFTER A LONG TIME IN STORAGE ......................................................................................... 19
20. STARTING AT LOW AMBIENT TEMPERATURES....................................................................................... 20
21. REGULATING THE WORKING PRESSURE ................................................................................................. 20
22. STOPPING THE MACHINE ............................................................................................................................ 21
23. MAINTENANCE .............................................................................................................................................. 22
24. MAINTENANCE PROGRAMME ..................................................................................................................... 22
25. RECOMMENDED OIL ..................................................................................................................................... 23
26. TANK ............................................................................................................................................................... 25
27. DISMANTLING ................................................................................................................................................ 27
28. TROUBLESHOOTING ON ELECTRIC SCREW COMPRESSORS .............................................................. 28
Pag. 2 of 32
INSTRUCTIONS MANUAL
1. DECLARATION OF CONFORMITY – CE
Pag. 3 of 32
INSTRUCTIONS MANUAL
2. GENERAL INFORMATION
a) This manual is intended principally for the user of the compressor and specifically for:
b) The instructions manual is to be considered an integral part of the compressor and must be "kept for future
reference" for the whole life of the compressor, until it is scrapped, and must accompany the compressor if
sold. As a rule it is applied on the outside of the compressor, in a protective envelope, and must always be
kept with care and be available for consultation in the vicinity of the compressor. You may apply to the
manufacturer's address for a new copy, specifying the data on the identification plate.
c) For information or to request spare parts, consult the respective manual and supply also the serial number
and the model, indicated on the identification plate.
This manual concerns only the compressor and not the other components and accessories of the system,
for which reference must be made to the respective manuals.
d) This manual reflects the state of the art at the time the compressor was placed on the market and it may be
updated on the basis of further experience, without the obligation to update the previous production and
manuals, except in cases where this is deemed necessary.
Any explanations and information or proposals for the improvement of the manual may be sent to the
manufacturer.
e) The identification data of the compressor model must be copied (by the user) onto the Data plate shown on
the last page of the "specific" instructions manual and are the same ones shown on the PLATE APPLIED
ON THE COMPRESSOR (a fundamental requirement of the EC Directive).
Other interesting data, such as noise production and weight, are shown on the page “TECHNICAL
CHARACTERISTICS” (see the “specific” instructions manual for each type of machine).
f) In this manual, the compressor model is identified by the initials and by the motor power expressed in kW,
as indicated on the page “TECHNICAL CHARACTERISTICS” (see the “specific” instructions manual
for each type of machine).
Pag. 4 of 32
INSTRUCTIONS MANUAL
Pag. 5 of 32
INSTRUCTIONS MANUAL
Pag. 6 of 32
INSTRUCTIONS MANUAL
b) The air produced by the compressor is not suitable for direct breathing because it is not sufficiently filtered
for the human organism.
c) The intended use of this compressor is "professional", used according to the indications given in the
technical characteristics for the specific model.
d) Compressor operation is completely automatic and does not require the presence of the operator. All that is
required is that it be supervised and maintained by an operator who is sufficiently trained and has learned
all the safety and operating procedures that concern him, contained in this manual.
f) Compressor operation is contemplated only complete with its closing panels both for cooling and for
protection and soundproofing.
g) The compressor is not suitable for installation in environments with a potentially explosive atmosphere.
Pag. 7 of 32
INSTRUCTIONS MANUAL
6. RISK ANALYSIS
Below are indicated the safety measures taken in the design stage or the recommendations for the user,
for protection in dangerous situations.
RISK REMEDY
Handling Base designed for inserting forks of a pallet truck or forklift
Electrical connection Built-in disconnecting switch under load in AC23 (where provided)
Bolted on with opening provided with door-locking disconnecting switch
Electric panel
(where provided)
Mechanical hold-down button or yellow/red disconnecting switch (where
Emergency
provided)
Short circuit Built-in line fuses (where provided)
Motor overload Thermal overload relay
Electrostatic currents Oil separating filter with metallic continuity
Compressor excess
Thermostat
temperatures
Insufficient lubrication Thermostat for "adiabatic" compression
Starting under load 10 sec. delay on restarting (only for versions with control unit)
Excess pressure Regulatory safety valve
Back pressure Check valve
Residual pressure Discharge tap and internal pressure gauge
Standard protection controlled by RSF relay (only for versions with
Incorrect direction of rotation
control unit)
Temperature:
a) Maximum ambient > Tmax a) Thermostat (see specific manual)
b) Minimum ambient < Tmin b) See recommendations for starting
Containers under pressure Built according to CE regulation in force
Hoses Use of high pressure hoses (4/6 times the working pressure)
Thermal risks Warning plate on points > 70 °C
- Machine closed by panels
Rotating parts - Guard on belt transmission;
- Transmission danger label
7. TECHNICAL CHARACTERISTICS
For the full technical characteristics see the specific instructions manual for the
compressor.
Pag. 8 of 32
INSTRUCTIONS MANUAL
8. OPERATING PRINCIPLE
This is a single-stage screw compressor. The air end is composed of 2 asymmetric screws driven by an
electric motor. The air is compressed by the rotation of the male and female rotors which are parallel and
perfectly mated with each other and contained in a cast iron casing.
The oil injected into the screw has the dual function of cooling and of creating a perfect seal during screw
rotation. The compressed air leaves the air end mixed with lubricant and enters the separating tank. In the
tank there is the first separation of the oil by centrifugal action and by gravity and a final separation through a
special high-efficiency filter, which purifies the compressed air down to 2-3 ppm traces of oil. After separation
from the compressed air the oil, controlled by a thermostatic valve, enters a cooling radiator and is injected
at low temperature into the air end.
The air cooling system is of the forced type. The air is sucked in by a fan and forced through the air/oil
radiator, removing the heat.
The compressor is soundproofed by means of a coating of fireproof sound-deadening material on all the
external panels.
9. PNEUMATIC DIAGRAM
P. NAME P. NAME
1 ELECTRIC MOTOR 11 SUCTION FILTER
2 COMPRESSOR 13 SUCTION VALVE
3 OIL DISCHARGE 14 OIL RECOVERY
4 OIL SEPARATING FILTER 15 PRESSURE GAUGE
5 SAFETY THERMOSTAT 16 DISCHARGE VALVE
6 OIL SEPARATING TANK 18 PRESSURE SWITCH/PRESSURE TRANSDUCER
7 SAFETY VALVE 19 MINIMUM PRESSURE CHECK VALVE
8 OIL FILTER 20 AIR RADIATOR (MODELS > 5.5 Kw)
9 OIL RADIATOR
10 THERMOSTATIC VALVE
Pag. 9 of 32
INSTRUCTIONS MANUAL
N.B. • When moving, avoid jolts and ensure the load is in a barycentric position.
• Use lifting equipment suitable for the weight of the machine and with fork
length (A) (C) suitable for the width.
• Avoid lifting the compressor by exerting force on the panelling.
• Respect the distance of the forks (B) (D) according to the indicated lifting
points.
Pag. 10 of 32
INSTRUCTIONS MANUAL
12. INSTALLATION
b) Consult the compressor overall dimensions drawing to establish the minimum distance necessary from
walls and from other machinery.
c) Ensure that the place where the compressor is located is adequately ventilated. The temperature of the
cooling air must not be higher than +45°C or lower than 0°C. Do not allow the cooling air to recirculate. If the
compressor is provided with air ducts, respect the requested air volume and the maximum load loss in the
ducts. Also consider the possibility of cleaning the radiators (refer to the technical specifications).
d) The condensate discharge contains water and traces of oil which must be properly disposed of, as required
by the law.
f) The compressor must not be installed in environments with presence of cement dust, silica or other types of
dust without any particular measures for prefiltering the air taken in.
If you have any doubts, contact the GARDNER DENVER assistance service.
0°C
12.2 Recommendations
a) The air sucked in by the compressor must be absolutely free from inflammable vapours and toxic fumes of
solvents or paints which could cause fires or explosions and pollute the air in the working environments.
b) The absence of a storage tank is prejudicial to the safety of operation of the compressor, because it may
overload the electric regulating components and cause an excessive number of starts per hour, which are
harmful for the electric motor.
c) Do not remove or tamper with the safety devices, guards or insulations applied on the compressor.
d) Absolutely do not tamper with the pressure regulator and the pressure switch beyond the value allowed by
the compressor model and by the tank pressure. In any case the allowed working pressure is always lower
than the opening pressure of the safety valve of the tank constructed according to the regulations in force.
Pag. 11 of 32
INSTRUCTIONS MANUAL
THREE-PHASELINE
REF. NAME
1 COMPRESSOR
2 TANK
3 DRYER
4 HOSE
5 WATER-OIL SEPARATOR
6 CONDENSATE SEPARATOR
7 AUT. CONDENSATE DISCHARGE
8 CERAMIC FILTER
9 COALESCING FILTER 0.1m
10 COALESCING FILTER 0.01m
11 ACTIVATED CARBON FILTER
12 DIFFERENTIAL PRESSURE GAUGE
COMPRESSED AIR OUTLET
Pag. 12 of 32
INSTRUCTIONS MANUAL
14. CONNECTION
b) Ensure that the correct working voltage is used. The rated voltage indicated must be used, ± 5 %. Check
that the same voltage is used in each phase.
c) The installer must protect the power supply cable against short circuiting. For the types of fuses used, refer
to the "specific" manual for each type of machine.
d) If the compressor has a built-in dryer, the electric panel must be connected to a separate 230V supply unit
(refer to the wiring diagrams and the technical data).
f) The power supply connections must be made exclusively by qualified electricians. Do not install
computers in the vicinity of the compressor.
Ensure that any computers are connected to a different electric circuit from that of the compressor.
Pag. 13 of 32
INSTRUCTIONS MANUAL
If the value of f>7.2 mm, it means that the belt tension is too low, so you must adjust the tightening screw pos.1
to restore the correct value of the belt tension.
If the value of f<6.8mm, it means that the belt tension is too high, so you must adjust the tightening screw pos.1
to restore the correct value of the belt tension.
NOTE 1 : After having restored the correct belt tension, run the compressor for 20-30 minutes. Then
check the belt tension again, measuring the value of "f", and if the tension is not correct restore it
following the procedure described above.
NOTE 2 : Check that the pulleys are perfectly aligned and correct the alignment if necessary to obtain
a maximum misalignment of 1.5 mm. ( fig. 1 )
Fig. 1
LINE FOR
CHECKING
ALIGNMENT
Pag. 14 of 32
INSTRUCTIONS MANUAL
BELT TENSION
VISUAL INDICATOR
red
GREEN
red
Loose
Correct
Too tight
INDICATOR
Pag. 15 of 32
INSTRUCTIONS MANUAL
1
4
5 Red loose
3
Green correct
6
Red too tight
2° MAX DESCRIPTION
SYSTEM FOR CHECKING
PULLEY ALIGNMENT 1 Compressor
2 Line for checking alignment
3 Motor pulley
4 Belts
5 Compressor pulley
6 Spring and tie rod
7 Tightening nut
Grease nipples(grease every 1600 hours using
8
lithium grease: SKF LGHQ3, about 30 grams)
2
8 2 mm MAX
Sag f (mm) 8 6 8 10 6 7 7 8 10 13
Pag. 16 of 32
INSTRUCTIONS MANUAL
17. RECOMMENDATIONS
a When starting the compressor for the first time, ensure that:
- the hoses are well connected and efficient and have no abrasions or cracks
- the direction of rotation is correct, if it is incorrect invert two phases of the
electric power cable.
- It is forbidden to run the compressor with the door open.
- all the guards are in their place, well secured
- all the cables that make up the electric system are in good conditions and
the earth wire is connected
- there are no leaks of oil and air
b Before opening the gate valves and sending compressed air into the connecting hose, ensure that the end
is secured so as to avoid whiplash which would cause injuries.
c At the end of each shift, turn off the power by means of the motor protector or "OFF" button on the control
unit.
d The air produced by the compressor is not suitable for human breathing because it contains oil
vapours.
18.1 For versions with direct start for powers 2.2-5.5 kW without control unit
Airbasic 2 (operation with pressure switch)
To start the compressor press the “ON-1” button (BLACK) on the front panel.
The machine operation is automatically controlled by the pressure switch, which stops the machine when the air
pressure in the tank reaches the MAXIMUM value and restarts it when the pressure falls below the MINIMUM
value, according to the work cycle shown in the figure.
This pressure range is set at MIN. 8 bar / MAX. 10 bar
If necessary, to stop the compressor press the “OFF-0” button (RED) on the front panel.
Minutes
PAUSE 6 6 6 6 6
N.B.: The compressor must operate with WORK cycles of at least 4 minutes, before switching
off the machine, to avoid the formation of condensate in the oil.
Pag. 17 of 32
INSTRUCTIONS MANUAL
When the “ON” / “RUN” button is pressed the compressor is started in "star delta" sequence.
Once the "star delta" transition is complete, a timer counts a delay of 1 second at the end of which the
compressor passes to operation under load.
When the pressure reaches the Pmax value the control unit intervenes, making the compressor run idle for a
maximum of 3 minutes.
If the pressure falls to Pmin value during idling, the control unit starts the compressor under load.
Instead, if the pressure remains at values higher than Pmin, the motor is stopped at the end of the idling time.
As soon as the pressure falls to Pmin value, the motor is restarted in "star delta" sequence.
Pag. 18 of 32
INSTRUCTIONS MANUAL
Pag. 19 of 32
INSTRUCTIONS MANUAL
Procedure recommended for the first start-up (with ambient temperatures below 0 °C )
a Start the motor for 4/5 seconds and switch it off quickly before the pressure rises.
b Repeat point a once more.
c Start the compressor provisionally, checking that the pressure increases almost up to the maximum working
pressure of the compressor .
example: 7 BAR for 8 BAR versions
9 BAR for 10 BAR versions
12 BAR for 13 BAR versions
d Switch the compressor off promptly at the higher pressures indicated in point c
e Repeat points c - d once again
f Finally start the compressor, checking that the pressure is not exceeded due to the formation of ice in the
pipes or blocking of the check valve.
When supplied the compressor is correctly regulated with a differential of 2 bar between Pmax-Pmin.
Should it be necessary to modify the regulation of the pressure switch, contact the authorised Gardner Denver
assistance service.
It is strictly forbidden to set the pressure switch at values higher than 10 bar.
When supplied the compressor is correctly regulated with a differential of 1 bar between Pmax-Pmin.
Should it be necessary to modify the regulation of the Pmax and Pmin values, contact the authorised Gardner
Denver assistance service.
N.B.: It is strictly forbidden to set the pressure at values higher than the pressure Max Press on the compressor
data plate.
Pag. 20 of 32
INSTRUCTIONS MANUAL
N.B.: In the event of a power cut, the compressor will stop and then restart automatically, without any delay,
when the mains power returns.
WARNING: Check that automatic restarting cannot produce dangerous situations of any kind.
WARNING: the compressor continues to operate for another 15 seconds (soft-stop function)
FOR IMMEDIATE STOP: press the mechanical hold-down button or, if not present, turn the yellow/red
disconnecting switch to "OFF" position (that is counter clockwise).
N.B.:
After a power cut, the compressor will not restart automatically
(parameter P26=0 default).
To activate the automatic restart function you must change the settings in the control unit (parameter P26=1).
WARNING: this particular situation must be carefully evaluated, considering the air reserve in the
storage tank downstream from the compressor, so as to avoid any injuries to persons or damage to
property or materials due to the fall in pressure in the network.
Pag. 21 of 32
INSTRUCTIONS MANUAL
23. MAINTENANCE
NOTE:
- Maintenance activities indicated in detail with this symbol in this manual must be performed by
authorised Gardner Denver service personnel.
- Always wear protective clothing and gloves during maintenance jobs.
- Always compile a log book.
For the detailed maintenance programme, see the specific instructions manual for the
compressor.
Pag. 22 of 32
INSTRUCTIONS MANUAL
- Garden Denver AEON 3000 (type F 2105). Oil, for the first filling.
- Gardner Denver AEON 6000 FG (USDA compatible for uses in the food industry)
- Gardner Denver AEON 9000 SP (SYNTHETIC)
10 litres 03389141
20 litres 250531 89795109 89756089
209 litres 03389143 89795239 89767689
Pag. 23 of 32
INSTRUCTIONS MANUAL
kW 2.2-7.5 kW 11-15
Pag. 24 of 32
INSTRUCTIONS MANUAL
Total machine
Compressor power (kW)
capacity (lt.)
2.2 ÷ 5.5 3
7.5 3
11 - 15 5,5
18.5 - 22 10,5
30 13
37 - 45 - 55 25
75 43
90 45
26. TANK
Pag. 25 of 32
INSTRUCTIONS MANUAL
ON OFF
OPEN S
5
m
2 10 30
10
1
15 5
40
20
CLOSED
Pag. 26 of 32
INSTRUCTIONS MANUAL
27. DISMANTLING
IMPORTANT INFORMATION: more than 90% of the parts of this compressor are
made of recyclable material.
When taking the compressor out of service and demolishing it, its components must be considered in
order to dispose of them in an environment-friendly way:
Pag. 27 of 32
INSTRUCTIONS MANUAL
N.B.:
a) each job must be performed only by suitably trained technical personnel or
by a service centre!
b) before each job, take all the necessary safety precautions, as indicated in the
paragraph "MAINTENANCE”.
Pag. 28 of 32
INSTRUCTIONS MANUAL
Pag. 29 of 32
INSTRUCTIONS MANUAL
N.B.: see also the error messages listed in the manual of the electric control unit (if provided).
Pag. 30 of 32
INSTRUCTIONS MANUAL
Pag. 31 of 32
INSTRUCTIONS MANUAL
Pag. 32 of 32