1. OBJECTIVE
These specifications define the technical characteristics of the SAFEPOWER-EVO-HF uninterruptible power supply
(UPS). The UPS is designed to supply a clean and stable electrical supply, irrespective of the condition of the
mains or an alternative power supply.
The SAFEPOWER-EVO-HF series of UPS is designed and manufactured by Siel UPS, a leader in this field with a range
of products from 350VA to 800kVA, and over 25 years of experience in power protection.
2. SYSTEM DESCRIPTION
The SAFEPOWER-EVO-HF UPS is available in 10-120 kVA On Line double conversion technology.
SAFEPOWER-EVO-HF meeting the VFI-SS-111 classification defined by IEC EN 62040-3.
SAFEPOWER-EVO-HF is designed protect critical industrial and Information Technology (IT) systems with the
following features:
! low input current distortion - as low as 3% and with a 0.99 input power factor;
! Power Walk-In and start-up delay to reducing generator oversizing; these features also help to guarantee
supply compatibility where available mains power is limited.
c) Inverter thermal oversizing in order to guarantee 115% overload (0.8pF) without time restrictions;
d) Capability to power loads with cos ` from 0.9 inductive to 0.9 capacitive, without active power (kW)
reduction;
e) High performance design achieving a system efficiency greater than 95% (on-line mode);
f) Backfeed protection;
! Easy operations to separate the bypass line from the rectifier input line
! Wide range of communication options
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 3 di 40 + FR
The SAFEPOWER-EVO-HF series consists of the following models:
MODEL DESCRIPTION
3. REFERENCE STANDARDS
Siel UPS operates a Quality Management System certified to ISO 9001/2000 (Certification No. CERT-04116-99-AQ-
MIL-SINCERT) covering all company functions from design and manufacture to after sales services.
In addition, the UPS meets the VFI-SS-111 classification (according to EN 62040-3) and complies with the following
specific standards for UPS:
! IEC EN62040-1: Static uninterruptible power supplies (UPS): general and safety provisions;
! IEC EN62040-1-1: Static uninterruptible power supplies (UPS): general and safety provisions for operator-
accessible areas;
! IEC EN 62040-2: Electromagnetic compatibility (EMC) requirements category C2
! EN 62040-3: Methods of specification of performances and test provisions;
The SAFEPOWEREVO-HF series also satisfies the following general standards, where applicable:
! IEC 60529: Degree of protection provided by enclosures;
! IEC 60664: Insulation for low-voltage equipment;
! IEC 60755: General Requirements for Residual Current Operated Protective Devices;
! IEC 60950: General safety provisions for "Information Technology" equipment;
! IEC 61000-2-2: Electromagnetic compatibility immunity;
! IEC 61000-4-2: Electrostatic discharge immunity test;
! IEC 61000-4-3: Radio frequencies, electromagnetic immunity test;
! IEC 61000-4-4 : Transitory overvoltage immunity test;
! IEC 61000-4-5 : Overvoltage immunity test;
! IEC 61000-4-11: Voltage dips, short interruptions and voltage variations immunity test.
! IEC 61000-3-12: Harmonic current emissions (for equipment with rated current > 16 A j 75)
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 4 di 40 + FR
European Directives:
LV 2006/95/EC
Low voltage Directive: contains provisions relating to equipment safety and imposes the EC marking obligation
from 1/1/97.
EMC 2004/108/EC
Electromagnetic compatibility directive: contains provisions relating to UPS immunity and emissions in its
installation environment and imposes the EC marking obligation from 1/1/96.
4. APPLICATIONS
SAFEPOWEREVO-HF UPS are suitable for applications requiring critical load protection including:
LAN, Server and Datacenters: the 0.9 output power factor ensures greater active power availability for efficient
UPS loading.
e-business and Telecommunications: parallel operation means that the installed UPS size can be increased (up
to 6 units) to keep pace with the growth of the organisation.
Industrial processes and electro-medical systems: the UPS is designed to protect a range of loads, from industrial
processes to electro-medical applications. This has been achieved through careful load analysis at the design
stage of the SAFEPOWEREVO-HF project, to ensure the following characteristics:
! optimum input technical characteristics with zero impact on the power supply source
! high short circuit and overload capacity
! high battery recharge capacity with the option to use a variety of battery types (sealed valve
regulated and open-vented) for long back-up times.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 5 di 40 + FR
Emergency systems: the UPS can be configured to operate in any one of four operating modes to comply with
EN 50171 (the Centralised Power Supply Systems) standard:
'
The'UPS'operates'in'the'following'mode:'
ON9LINE''
(See'chapter'6'"Ups'descriptions")'
'
'
The'UPS'operates'in'the'following'mode:'
ECO9MODE'
(See'chapter'6'"Ups'descriptions")'
'
'
The'UPS'operates'in'the'following'mode:'
STAND'BY9OFF'
(See'chapter'9.4'"Configuration'Software")'
'
'
'
The'UPS'operates'in'the'"ON'LINE"'MODE'
by'using'the'POWERSHARE'socket''
(see'the'operating'manual)'
5. CONFIGURATIONS
The UPS can be installed as a single, stand-alone UPS and this format is most commonly used for relatively straight
forward installations. This can be expanded up to 6 units in order to meet load power demands or to introduce a
level of redundancy.
Parallel configuration
Up to 6 UPSs can be connected in parallel to increase the power of the uninterruptible power system (power
parallel) or to enhance its reliability (redundant parallel).
The system is defined as “redundant parallel” when the stoppage of one or several UPSs does not determine the
loss of the power supply.
All the UPSs power the load simultaneously with automatic sharing of the current.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 6 di 40 + FR
The units exchange information on the operating status and the sync signals by means of the RS485 connections
in loop with dual redundancy. This means that even in the event of the accidental interruption of both
connections, only the UPS affected by this interruption cuts itself off, while the other one continues to operate
without any interference.
The “Hot System Expansion” feature means that a new UPS can be added to the system while the other units are
on-line and powering the load from the inverter.
The integrated UPS will configure itself automatically with the system data without any disturbance to the load.
LOAD
NOTE: for realizing a parallel configuration where is required a transformer connected downstream
each single UPS please contact the manufacturer in advance
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 7 di 40 + FR
6. UPS DESCRIPTION
The UPS can be operated in four main operating modes: ON-LINE, FREQUENCY CONVERTER, ECO MODE and
SMART ACTIVE and in their main variants described in following paragraph.
Mode: ON-LINE
Normal Operation: the rectifier, drawing power from the mains power supply, supports the Inverter and charges
the batteries; the load is powered by the Inverter which provides a clean and secure supply, synchronised to the
bypass supply.
Emergency Operation: if the mains power supply wanders outside the permitted input range (voltage and
frequency), the rectifier is shut down and the Inverter is automatically powered by the battery set for the preset
back-up time and without disruption to the load. When the mains power supply returns, the rectifier gradually
starts up, charging the batteries and eventually powers the Inverter.
Operation from By-pass: if an Inverter overload exceeds permitted limits (or is manually shutdown), the load
automatically transfers to the emergency bypass via the static switch and without disruption to the load.
The UPS can be configured as a frequency converter (with “UComGP”), therefore when the input frequency is
50Hz the output frequency can be 60Hz and vice versa. During this mode of operation the automatic by-pass is
disable. The UPS can work in frequency converter mode with or without the batteries (must be set up with
“UComGP”).
Mode: ECO
The load is normally powered from the emergency bypass supply and the rectifier maintains battery charge.
When the mains power supply wanders outside the permitted input range, the load is automatically transferred
to the output of the Inverter until the mains power supply returns within range.
This mode is useful when powering loads that do not require the regulated no-break supply from the Inverter and
allows the system to achieve an efficiency up to 99%.
When the UPS is configured to operate in SMART ACTIVE mode, it automatically selects whether to operate in
ON-LINE or ECO mode.
The decision is made based on statistical calculations performed by the UPS and based on the quality of the
mains and bypass supplies: if the latter remains suitable for a certain period, the unit selects ECO mode,
otherwise it remains in ON-LINE mode.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 8 di 40 + FR
The SAFEPOWEREVO-HF block diagram is as follows:
The PFC Converter converts the AC voltage into a DC supply to power the Inverter; if the mains or alternative
power supply fails, the Converter will raise the battery voltage to a value suitable with which to power the
Inverter. The PFC control technology using Digital Signal Processing (DSP) microprocessors and IENT power
semiconductors to achieve a low impact on the power supply source, low harmonic distortion and high input
power factor. A zero impact on the supply source is achieved due to the following characteristics:
! Negligible Input Harmonics: upstream generators and transformers (including distribution) can be reduced
due to the negligible input harmonic distortion of 3% and high input power factor > 0.99.
! Delayed switching of UPS –t0-T1 (Power Walk in-start Delay): when the mains power supply returns, the UPS
delays switching of the input stage for a period of time that can be set between 0 and 255 seconds (5
seconds standard). This function is particularly useful when the mains power supply returns after an
interruption (or when the generator set is started) and the source must supply various UPS or, more
typically, multiple users.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 9 di 40 + FR
! Progressive rectifier start-up –T1-t2 (Power Walk-in duration): when the mains power supply returns,
absorption of the mains power supply progressively reaches the nominal value within a time period that
can be set from 5 to 30 seconds. This function is normally disabled.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 10 di 40 + FR
6.2 BATTERY CHARGER (Battery Care System)
The "Battery Care System" is a set of functions arranged to help extend the working life the battery set and
optimise its performance.
a) Battery recharging: the UPS can be used with sealed lead batteries (VRLA), AGM, open-vented
and NiCd batteries. According to the type of battery used two recharge methods are available:
Recharging modes (selectable by “UComGP”) SAFEPOWEREVO-HF configurations
Floating (standard configuration): the
V charge state of the battery is
continuously monitored; when the mains
272.6 power supply is present, the batteries are
charged at a preset voltage level and
limited current relative to the recharge
time required and the capacity of the
battery itself.
t
Two-level recharge (configurable): this
V recharge is at limited current with two
I 286
levels of voltage. In the first instance, the
272.6 process uses a quick charge voltage,
whilst in the second stage a float charge.
This type of charging is mainly used with
open-vented batteries or other types
when an accelerated recharge time is
required.
I<50mA/Ah t
max 3h
Cyclical recharge: this recharge is
V sometimes recommended by battery
I 286 286
manufacturers to prolong the battery life.
272.6 It consists of battery charge and
262 discharge cycles as indicated in the
diagram.
battery
test
12h
I<50mA/Ah 48h 14gg t
max 3h max
“Commissioning charge”: this charge
V method is useful every time new
batteries are installed in the UPS. By
290
272.6 272.6 increasing the voltage to 290 volts for a
maximum of 24 hours, perfect
equalisation of the battery charge is
assured, thus guaranteeing a uniform
discharge and wear of the battery
monoblocks.
max 24h t
!"#$%&''()*+,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 11 di 40 + FR
The various recharge methods and the preset voltage values are defined using UComGP.
The presence of the external temperature sensor option will activate compensation of the voltage depending on
the temperature with the battery backup voltage (272V for 20 battery blocks)
b) Battery test: during normal operation the battery is automatically tested at regular intervals. The
battery test can also be manually activated. The test is performed to ensure a limited battery
discharge and impact on overall life expectancy. If the test returns a negative result a warning is
displayed on the UPS panel (or remote panel, if installed).
c) Protection against slow discharges: for long runtimes and low load discharges, the end of
discharge voltage is raised to approximately 1.8V/el as recommended by the battery
manufacturers to avoid a deep discharge state.
d) Ripple current: recharge ripple current (residual AC component) is one of the most important
causes of poor battery reliability and reduced operating life. The UPS battery charger is a high-
frequency design with a negligible level of ripple current,
e) Battery recharge limit current: The battery recharge current is limited to a prefixed value of
Cnom/8 (i.e. 12.5% Cnom)
f) Cold-Start: This feature allows the Inverter to be switched on and the load to be powered by the
battery, when the mains power supply is not present.
g) UPS without batteries: the UPS must always be operated with the batteries connected; if they are
not connected alarms will be generated and the UPS will not be able to perform to specification.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 12 di 40 + FR
6.3 INVERTER
The DC/AC Converter (Inverter) converts the direct current into a stabilised sinusoidal alternating current to
power the load. When the UPS is in ON-LINE mode, the load is always powered by the Inverter.
The Inverter is an IENT (Isolated Gate Bipolar Transistor) based three-phase design; the IENT is a transistor that
allows high commutation frequencies (> 18kHz) and, as a result, the Inverter provides a high quality output
voltage, with low noise levels and high operating efficiency. In addition, the DSP microprocessor controls,
guarantee static and dynamic performance under any operating condition:
Voltage adjustment
The output voltage can be adjusted using the independent phase control and DSP microprocessor; this enables
a better static and dynamic response. In detail:
a) static condition: the Inverter output voltage remains within ±1% for all variations of the input voltage within
the accepted limits;
b) dynamic condition: for load variations from 0 to 100%, the output voltage remains within ± 3%, (within the
values defined by class 1 of the EN 62040-3 standard).
Frequency adjustment
The Inverter output frequency is generated autonomously by an internal oscillator, in synchronisation with the
bypass supply. Frequency stability is operating condition dependent:
a) Frequency stability
a. With mains power present: the internal oscillator follows any frequency variations in the bypass supply
and in relation to the preset value - normally ± 5% (configurable from ± 0.25% to ± 10%).
b. With no supply present: the Inverter autonomously generates the frequency of the output voltage with
a stability of ± 0.01%.
b) Frequency variation speed
The maximum Inverter output frequency variation (to lock to that of the bypass supply) is 1Hz/s (adjustable
from 0.5 to 2Hz/s).
Inverter output waveform distortion with a linear load is maintained within ±1%. Within a non-linear load, as
defined by the EN 62040-3 standard, output voltage distortion does not exceed ±3%.
Overload
The inverter is sized to provide a power overload for a limited length of time (see the limits indicated in the
Technical specifications table.)
When the time period or power limits are exceeded, the load is transferred to the bypass supply.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 13 di 40 + FR
Short circuit capacity
If a short circuit occurs whilst the UPS is operating from the batteries, the Inverter will carefully analyse the output
voltage and current in order to distinguish if the short circuit is genuine or an overload.
! During battery operation (mains power supply failure) the Inverter can supply a current limited to 150% for
500ms.
! When the mains power supply is present, the Inverter will switch to bypass supplying a current limited to for
500ms.
The table below recommends the sizing of the various protection devices located downstream of the UPS in
order to guarantee their selectivity even in the event of a power failure:
Under all conditions, output voltage symmetry is maintained within ± 1%, for balanced loads and ± 2% for
unbalanced loads of 100% (e.g. one phase with nominal load, the other two with no load).
The three-phase Inverter output voltages have a guaranteed phase separation angle of 120° ± 1° for balanced
loads and 100% for unbalanced loads.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 14 di 40 + FR
6.4 STATIC SWITCH (Automatic Bypass)
A static switch is an electronic device that can automatically transfer the loads connected to the UPS to the
bypass supply in an emergency for example when:
If at the time of switchover, the inverter voltage is not synchronised with that of the auxiliary power supply, the
transfer will take place with a delay of around 20ms; in consideration of the various types of loads, this delay can
be set with “UComGP” to 10ms or the switchover can be inhibited if there is no synchronism.
Transfer to the emergency supply only takes place if the voltage and the frequency are considered 'suitable' for
the load and the limits for transfer can be set on-site by the UPS user.
Overload
The static switch has no over current protection devices to guarantee maximum continuity. Overload protection
is provided by protective devices within the overall installation to ensure UPS compatibility.
The UPS static switch is sized to support the following overload periods:
110% permanently
133% for 60 minutes
150% for 10 minute
>150% for 2 seconds
Under short circuit conditions, the UPS will prevent transfer to bypass for 0.5 seconds;
thyristors with I2t (Tj=125°C) = 80000A2s for 60-80kVA and 125000A2s for 100-120kVA.
The UPS is equipped with a redundant auxiliary power supply to allow the automatic bypass to function even if
the main power supply has failed.
If the UPS fails in addition to the main power supply, the load is powered through the automatic bypass. The multi
processor card and control panel are not powered, and for this reason, all LEDs and the display are off.
F1, F2, F3, F4= FUNCTION KEYS. The function of each key is illustrated in the lower part of the display
and varies according to the menu.
Messages are available in the following languages: Italian, English, French, German, Spanish, Polish, Chinese and
russian.
At the centre of the control panel there is a wide-area graphical display providing a detailed real-time overview
of the UPS operational state. From the control panel the user can switch the UPS on/off, read electrical
measurements - mains, output, battery, etc, and set the main operational parameters.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 16 di 40 + FR
The display is divided into four main areas, each with a specific function:
1 GENERAL INFORMATION
An area permanently showing the date and time and according to the level of display, either the UPS model or
the title of the menu active at that time.
4 EVENT LOG
An area showing chronological events recorded (supply voltage out of range, high temperature, overload,
etc.)and alarms. The log records 960 events in FIFO (First In First Out) mode and the string contains the following
information: Event Code, Event Description, Date and Time.
Data is displayed through the graphical display using the scroll keys; the log can be downloaded in TXT format
using the UPSTools configuration software.
5 KEY FUNCTIONS
An area divided into four sections, one for each of the function keys. According to the menu active at any time,
the display will show the corresponding function key in the appropriate box.
Measurements
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 17 di 40 + FR
8. ISOLATING SWITCHES
The UPS is supplied with the following isolating switches located and accessible from behind the case front door:
SWMB
Manual by pass
SWOUT
output
SWIN
input
SWBYP
by pass
9. COMMUNICATION
Communication ports
The rear panel (see UPS rear view) provides access to the following communication ports:
Behind the front terminal panel, a further expansion slot is available for a volt-free signal card (optional 250Vac,
3A, 4 programmable contacts).
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 18 di 40 + FR
RS232 and USB Connectors
4 3
1 2
Communication Slots
The UPS has two panel expansion slots for slot-in interface accessories that can be used for a variety of
communications options including:
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 19 di 40 + FR
AS400 Port
AS400 PORT
NOTE: The diagram shows the contacts present inside the UPS that can provide a maximum current of 0.5A at
42Vdc. The position of the contacts in the diagram is shown without alarms or warnings.
(1) The output can be programmed through the appropriate configuration software.
The function shown is the default (configured by the manufacturer).
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 20 di 40 + FR
9.1 EMERGENCY SHUTDOWN (R.E.P.O.)
This isolated input is used to switch off the UPS in an emergency. The UPS is supplied with the "Remote Emergency
Power Off" (R.E.P.O.) terminals short circuited. At installation, remove the short-circuit and connect to the
normally closed contact of the shutdown device , using a double-insulating cable.
When activated from a remote push-button or other device in an emergency, the R.E.P.O connection opens
and the UPS switches to stand-by mode. The UPS no longer powers the load.
The R.E.P.O circuit is supplied with SELV type circuits. No external supply voltage is required. When it is closed
(normal condition), a maximum current of 15mA flows.
After an emergency shutdown, the UPS will return to on-line operating mode only when it receives a startup
command from the mimic panel (provided that the Remote Emergency Power Off device is not still active).
This non-isolated input can be used to synchronise inverter output with a suitable signal from an external source. It
is essential when the SAFEPOWEREVO-HF is used in combination with Static Switch Transfer Systems.
At installation, it is important to:
! use an isolation transformer with isolated single-phase output (SELV), 12-24ac and power = 0.5VA
! connect the transformer secondary to the "EXTERNAL SYNC" terminal through a double-insulation
cable with cross-sectional area of 1 sq.mm.
The external synchronization must be enabled through the advanced configurration software (UComGP)
assigned to authorized personnel.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 21 di 40 + FR
9.3 MONITORING AND CONTROL SOFTWARE
The UPS is supplied with Powershield³ UPS monitoring and control software to provide the following:
User can modify some of the UPS configurations from the operating mimic panel; here below the list of
adjustable functions:
! English
! Italian
! German
Selects mimic panel ! French
Language* English
language language ! Spanish
! Polish
! Turkish
! Chinese
* Pressing the F1 and F4 keys at the same time for t > 2 sec will automatically reset English as default
language.
** This function might be locked by configuration software.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 22 di 40 + FR
Authorized service centers can modify all UPS configurations through configuration software ( “configurator” of
UCom GP program) as below defined:
BASIC
! ON LINE
Selects one of five ! ECO
Operating mode ON LINE ! SMART ACTIVE
different operating modes
! STAND-BY OFF
! Frequency converter
Selects the rated output ! 220 ÷ 240 1 V step
Output voltage voltage 230V ! 200V with power downgrading
(Phase - Neutral) ! 208V with power downgrading
Selects the rated output
Output nominal ! 50Hz
frequency 50Hz
frequency ! 60Hz
ADVANCED
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 23 di 40 + FR
Activates the gradual
Power walk-in ! Disable (0 sec set up)
return to mains voltage Disable
duration ! Enable 1 ÷ 125 @1 sec step
mode
Selects the
Bypass ! 0.5 Hz/sec
synchronisation speed of ! 1 Hz/sec
Synchronization 1 Hz/sec
the inverter to the bypass ! 1.5 Hz/sec
speed
line ! 2 Hz/sec
Panel lock -
Disables UPS settings Settings ! Settings enabled
Enable config
from the Display Panel enabled ! Settings disabled
change
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 24 di 40 + FR
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
BYPASS
Disable (load
Bypass active in Load supply from bypass ! Disable (load not supplied)
NOT
stand-by with UPS in stand-by ! Enable (load supplied)
supplied)
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 25 di 40 + FR
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
BATTERY
Change
Internal battery Nominal Battery capacity according
! 0 – 18 Ah @1 Ah step
capacity for internal batteries with UPS
model
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 26 di 40 + FR
Battery
Recharging current
recharging 12% ! 3 ÷ 50 @ 1% step
compare to battery
current
nominal capacity (%)
Change
Nominal recharging ! 6 Amps
according ! 10 Amps
Internal charger current for internal battery
with UPS ! 20 Amps
charger
model ! 25 Amps
Nominal recharging
Additional current for external battery
0A ! 0 ÷ 100 @ 1Amp step
charger (external) charger
(not inside UPS)
EXTERNAL I-O
The main assemblies (including the power module and magnetics) are temperature monitored.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 27 di 40 + FR
11. OPTIONS
11.1 COMMUNICATION
PowerNETGuard is a centralised UPS management and control software package using the SNMP
communications protocol. It is the ideal UPS management tool for IT/EDP managers running datacenters and
medium-to-large-sized networks.
Hardware
Two slots are available in which to house one or two of the following options:
a) NetMan 102 Plus: the NetMan Plus network agent allows UPS management across a LAN
using any of the main network communication protocols - TCP/IP, HTTP and network
interface (SNMP). NetMan Plus enabled UPS integrate easily into medium and large sized
networks and provide reliable communications between the UPS and management
systems employed.
b) MultiCom 302: a Modbus/Jbus protocol converter through an RS232 or RS485 output for
monitoring the UPS, for example, from a BMS (Building Management System). It also
provides a second independent RS232 serial line that can be used by other devices such
as a NetMan Plus or PC.
c) Multicom 382: it provides a set of relay contacts to provide UPS alarm and status
indication. The contacts are connected through terminal connections. Signal contacts
include Emergency Power Off (EPO), Remote Shut Down (RSD), On Battery, On Bypass,
Alarm and Low battery. The contacts are change over or normally open.
d) Multicom 372: MultiCOM 372 provides a UPS with an additional RS232 serial interface port.
The card has Emergency Power Off (EPO) and Remote Shut Down (RSD) inputs with
terminal connections.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 28 di 40 + FR
e) Multi Panel: MultiPanel is a remote monitoring device that can provide a detailed UPS
status overview in real time. It is compatible with all SIEL UPS and can display values for UPS
specific input and output supplies, and battery set measurements. MultiPanel has a high-
definition graphical display and can report in 7 languages: English, Italian, German,
French, Spanish, Russian and Chinese. It has 3 independent serial ports, one of which
allows for UPS monitoring via the MODBUS/JBUS protocol (on either an RS485 or RS232 serial
line). The others can be used with devices such as the Netman 101 Plus or a PC running
PowerShield3 software.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 29 di 40 + FR
11.2 EXTERNAL BATTERY TEMPERATURE SENSOR
The UPS has a special entry point for measuring the temperature inside a remote Battery Box and indicating the
temperature on the UPS display.
The specific kit supplied by the manufacturer includes a bipolar double isolated cable measuring 6 meters. The
use of a bipolar cable without isolation exposes the UPS and the user to risks resulting from a lack of isolation as
the reading refers directly to the UPS neutral earthing.
Once installed, the device is configured using the UPSTools software package assigned to authorized personnel.
An external remote maintenance bypass can be installed with the UPS, to allow, for example, UPS replacement
without disruption to the load.
If this option is chosen, it is essential to connect the “SERVICE BYPASS” terminal located inside the UPS to the
auxiliary “Normally Open “(NO) contact of the SERVICE BYPASS switch. Operation of the SERVICE BYPASS switch
closes this auxiliary contact and informs the UPS. If such a connection is not made, operation of the remote
maintenance bypass may disrupt the supply of power to the load and damage the UPS.
Note: Always check that the remote maintenance bypass installation (if selected) is compatible with any
transformer options selected for the UPS - see paragraph 11.6 Optional Transformer.
The battery cabinet can be used to provide an external battery set when.
The number of batteries housed within the cabinet varies according to UPS rating. It is therefore necessary to
carefully match that Battery Cabinet DC rating to that of the UPS.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 30 di 40 + FR
BATTERY BOX MODELS AB 1320-120B AB 1600-40B AB 1900
Dimensions
(mm)
HxWxD
The UPS can be furnished from the factory with a more powerful battery charger mounted in place of the
standard one.
An external transformer can be installed. Transformer options include: supply neutral reference, Galvanic isolation
and output voltage (step-up or down).
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 31 di 40 + FR
Note: An external transformer will modify the neutral arrangements of the installation. Therefore, if a "remote
maintenance bypass” is installed it must be sited downstream of the transformer (for an input-side transformer)
or upstream (for an output-side transformer).
UPS without variation of the neutral arrangements and with a separate bypass supply input (standard for
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 32 di 40 + FR
120kVA, option for others)
Remove the jumpers present between the SWIN and SWBY isolating switches (120 kVA)
UPS with Galvanic isolation on the input-side and separate bypass supply input (standard for 120kVA, option for
others)
Remove the jumpers present between the SWIN and SWBY isolating switches (120 kVA)
UPS with Galvanic isolation on the output-side and separate bypass supply input (standard for 120kVA, option
for others)
Remove the jumpers present between the SWIN and SWBY isolating switches (120 kVA)
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 33 di 40 + FR
inputs.
UPS without variation of the neutral arrangement and with a separate bypass supply (standard for 120kVA,
option for others) connected on the independent mains line
Remove the jumpers present between the SWIN and SWBY isolating switches (120kVA)
UPS with a separate bypass supply connected to an independent supply (standard for 120kVA, option for
others) and with galvanic isolation on the input
Remove the jumpers present between the SWIN and SWBY isolating switches (120kVA)
UPS with a separate bypass supply (standard for 120kVA, option for others) connected to an independent mains
supply and with galvanic isolation on the output
Remove the jumpers present between the SWIN and SWBY isolating switches (120kVA)
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 34 di 40 + FR
11.7 SEPARATE LINE INPUT
All the UPS versions in the range of 60-120 KVA are provided with a single feeding input. Simply removing the
parallel input jumpers it is possible to separate the bypass line from the rectifier input line directly on site.
Anyway, this operation guarantee the dissection of both the feeding lines through the two switches present on
the UPS (SWIN-SWBYP).
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 35 di 40 + FR
UPS Power (kVA)
Electrical data
60 80 100 120
INPUT
Nominal voltage 380-400-415 Vac Three-Phase plus neutral
Input Current (1) 104 138 182 215
Voltage range (without switching to 320 to 480 V at 100% of the load
battery power) 240 to 480 V at 50% of the load
Nominal frequency 50 or 60Hz
Input frequency tolerance 40 to 72Hz
Total Harmonic distortion (THDi) and power
THDi 2,5 % , 0,99 Pf THDi 3 % , 0,99 Pf
factor with full load
Rectifier progressive start-up Programmable from 5 to 125 seconds in steps of 1 second
(Power Walk-in duration) (this function is disabled by default)
Programmable from 1 to 255 seconds in steps of 1second.
Delayed switching
(5 seconds by default)
(1) The input current is stated for the following general conditions:
! Output load at 0,9pF
! Input voltage at 346 Volts
! Battery charging current of 25 Ampere (10 Ampere 60/80 kVA)
60 80 100 120
DC BUSBAR AND BATTERY SET
Number of battery cells 120+120
Float voltage
273+273 Vdc
(2,27 V/el. adjustable)
Boost voltage
288+288 Vdc
(2,4 V/el. adjustable)
End of discharge voltage – load
192+192 Vdc
dependent (1,6 V/el. adjustable)
• 0-100 % 10 A 25A
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 36 di 40 + FR
UPS Power (kVA)
Electrical data
60 80 100 120
INVERTER
Nominal power (kVA) 60 80 100 120
Active power pF 1 (kW) 54 72 90 108
Active power with load power factor from
54 72 90 108
0,9 inductive to 0,9 capacitive (kW).
Nominal voltage 380/400/415 Vac Three-Phase plus neutral
Derating for output voltage (Phase –
Neutral) set to:
• 208 V -5%
• 200 V - 10 %
Nominal frequency 50 / 60Hz
Static stability ± 0,5%
± 3% (1) (resistive load)
Dynamic stability
EN62040-3 class performance 1 distorting load
20ms
Recovery Time within ± 1%
In compliance with standard EN 62040-3, class 1
Crest factor
3:1
(Ipeak/Irms as per EN 62040-3)
Voltage distortion with linear and distorting j 1% with linear load j 2% with linear load
load (EN 62040-3) j 3% with distorting load j 4% with distorting load
Inverter frequency stability without by-pass
0,01%
supply synchronisation
Rtae of Frequency variation 1Hz/sec (adjustable from 0,5 to 2)
Voltage phase Dissymmetry with balanced
± 1% / ± 2%
and unbalanced loads
Voltage phase shift with balanced and
120 ± 1 °
unbalanced loads
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 37 di 40 + FR
UPS Power (kVA)
Electrical data
60 80 100 120
BY-PASS
Nominal voltage 380-400-415 Vac Three-Phase plus neutral
Output nominal current (A) 87 116 145 174
Bypass voltage range from 180V (adjustable 180-200) to 264 V (adjustable 250-264V)
Nominal frequency 50 to 60Hz
Bypass input frequency range ± 5% (adjustable from 0,25 to 10%)
Transfer time from By-pass to Inverter
2 ms typical
(UPS in "ECO mode")
Transfer delay to Inverter from By-pass 4 sec
Max current in short circuit for 20 ms
4000 A 4600 A
(Tj 25°C)
! j 110% infinite
Overload capability on bypass line ! > 110% ÷ j133% 60 min.
! > 133% ÷ j150% 10 min.
! > 150% 2 sec.
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 38 di 40 + FR
UPS Power (kVA)
Electrical data
60 80 100 120
SYSTEM
AC/AC Efficiency (On line)
Full load 95,4 95,2 93,6 93,5
75% Load 95,5 95,6 94,0 94,0
50% Load 95,5 95,6 93,7 93,8
25% Load 94,6 94,9 92,3 92,5
Auto-consumption (W) 455 455 1160 1280
Efficiency with UPS in STAND BY mode w 99,1 % w 98,6 %
Audible noise at 1mt (from 0 to full load) -
j 56 dB (A) j 70 dB (A)
(dBA)
Operating temperature 0 ± 40 ºC
Max. relative humidity during operation 90% (without condensation)
1000 m at nominal power
Max. installation altitude (- 1% reduction in power for every 100m over 1000m)
Max 4000m
2,61 kW 3,65 kW 6,9 kW 7,2 kW
Power dissipated with resistive nominal
2245 kcal/h 3140 kcal/h 5933 kcal/h 6191 kcal/h
load (pf=0,8) and backup battery*
8910 B.T.U./h 12460 B.T.U./h 23550 B.T.U./h 24578 B.T.U./h
UPS fan capacity 2100 mc/h 2100 mc/h 2600 mc/h 2600 mc/h
Max current leaked to earth ** j 100 mA
!"#$%&''()*+,,,'!-&.'!+/+0+'
123245')6577589):';,#;<,@<,A'''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''''Pag. 39 di 40 + FR
mail: [email protected]
www.sielups.com