Burkert 8630-E-C Manual
Burkert 8630-E-C Manual
CONTENTS:
1 GENERAL INFORMATION ....................................................................................... 87
1.1 Symbols ................................................................................................................................................. 87
TopControl Continuous 85
6 OPERATION ............................................................................................................ 117
6.1 Control and display elements ............................................................................................................ 117
1.1 Symbols
ATTENTION!
Indicates information, which if not observed can result in harmful effects on the health or the serviceability of
the unit.
Please observe the information in these operating instructions, as well as the operating conditions and permissible data specified
in the date sheets of the TopControl and of the relevant pneumatically actuated valve, to ensure satisfactory operation of the unit
and a long service life:
• Follow general technical rules when planning the application and operation of the unit!
• Installation and maintenance may only be performed by technical personnel provided with suitable tools!
• Note the accident prevention and safety precautions applicable for electrical units during operation and maintenance of the
unit!
• Always switch off the power supply before working on the system!
• Ensure a defined and controlled re-start of the process following an interruption of the electrical or pneumatic supply!
• We cannot accept any liability if these instructions are ignored or impermissible interventions are made in the unit and the
warranty also becomes invalid on units and accessories!
ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING !
ELECTROSTATIC
SENSITIVE
DEVICES
TopControl Continuous 87
1.4 Scope of delivery
Check the contents of the delivery for damage and agreement with the details specified on the delivery note immediately
following receipt. This normally comprises:
• pneumatically actuated valve of types 2652, 2655, 2672, 2700, 2712, 2730, 2731 or 2731K with the TopControl Continuous
Suitable cable plugs for the multipole connection are available as accessories.
This document contains no warranty promises. We refer in this connection to our General Conditions of Sale and Business. The
condition for the warranty is use of the unit for the intended purpose under the specified application conditions.
ATTENTION!
The guarantee only covers faults in the TopControl Continuous, and in the integrated pneumatically-driven
valve. No liability will, however, be accepted for subsequent damage of any kind that may arise as a result of
the failure or incorrect functioning of the device.
Operation of the device can be locked via a freely selectable user code. Independent of this, there is an unalterable master
code with which you can carry out all operations on the device. This 4-digit master code is printed on the last page of these
operating instructions.
If needed you can cut out this code and store it separately from these operating instructions.
The function ranges of the Bürkert pneumatic control valves are greatly increased when in combination with the TopControl
Continuous. These valves can be fitted with the TopControl Continuous in order to obtain continuous control with variable
functions.
The figure 2.1 below shows various combination capabilities of the TopControl Continuous combined with various pneumatic
control valves. A vast range of connections and valve diameters is available, although not displayed in the figure below. All
technical informations about these products are described in the relevant data sheets. The product range will be continuously
increased.
TopControl
Type 8630
with flat seat valve Type 2712 with slanted seat with diaphragm valve
(here with flange connection) valve Type 2700 Type 2730
Top Control
Type 8630
Fig. 2.1: Overview of mounting options for the Top Control Continuous with various valve types
TopControl Continuous 89
Various control valves from the Bürkert range may be used in connection with the Top Control Continuous depending on the installation
conditions. Angle valves, diaphragm valves, including ball valves fitted with a control cone are suitable, as well as piston or rotary driven
pneumatic actuators.
Pneumatic piston actuators or rotary actuators may be used as actuators. Single acting and double acting actuators may be used in
combination with the TopControl.
Within a single action actuator a single chamber is filled and exhausted. The resulting pressure acts on a spring, which forces the piston
to move until the pressure difference between the piston and spring are equal.
Double chamber actuators posses 2 chambers, which supply the pressure to the piston. The filling of one chamber induces the emptying
of the other, as there is no spring within this design.
Valves characteristics:
• 2731K
Characte- • flow over under the seat • fluid tightly isolated from the actuator and environtment • possibility of internal scraping
ristics
• protected against water hammer • no dead volume, self purging design • reduced dead volume
• straight flow direction • direction of flow as required with minimal turbulence of • low retention of deposits
flow
• high tightness through selfpositioning • replaceable seat and seals through 3 parts ball
packing box • steam sterilizable valve design
• CIP
Typical • water, steam and gas • neutral fluid and gas • neutral fluid and gas
medium
• alcohol, oil, fuel, hydraulic fluids • charged or aggressive fluids • pure water
• brine, organic fluids, base • high purity or sterilised fluid • low aggressive fluids
The type 8630 TopControl Continuous is an electropneumatic position controller for pneumatically actuated continuous valves.
The TopControl Continuous and pneumatic actuator are joined together to build one functional unit.
3.1 Construction
The design of the type 8630 TopControl Continuous (Fig. 3.1) is based on a modular concept.
Wide ranges of pneumatic and electrical connections are available as options.
Pressure supply
connection
(Marked: 1)
TopControl Continuous 91
CONSTRUCTION FEATURES:
• Design:
• Control unit:
The positioning system is composed and requires 2 solenoid valves for single-acting actuators (air inlet; exhaust air), or 4
solenoid valves for double-acting actuators (2 for air inlet; 2 for exhaust air).
The controller with a PWM-voltage powers the valves according to the rocker principle which allows fast positioning volumes
to be reached as required.
A large flexibility concerning the volumes of the chambers and the positioning speed is reached in that way. For use of
actuators with larger volumes, the positioning valves are fitted with membrane amplifiers in order to increase the maximal flow
and optimise the dynamic of the system.
As an option with single-acting actuators, a fast pressurizing/venting version is available with an additional pressurizing
valve and venting valve. This enables the actuator to be completely pressurized and vented more rapidly. This is used with
the tight-closing function (see chapter "CUTOFF") and on activating a safety position of 0 or 100% (see chapter "BIN-IN").
Protected against internal over-pressure, (eg. air leakage) by a pressure limit valve.
Protection against non-authorised opening of the cover by a seal or self-cutting screws.
The figure 3.4 shows the functional diagram of the TopControl Continuous in combination with a single acting piston valve.
Process value
Process
setpoint Position
Process
controller setpoint
external
position
setpoint
Position
Actuator
controler
1: Air inlet valve
Position 2: Air exhaust valve
feedback
Actuator
TopControl
Pressure air inlet
Displacement
measurement
system
Air exhaust
Pneumatic actuator
(single acting)
Control valve
(Control output)
Sensor
Process value
(Flow, pressure, level,
temperature, ...)
Fig. 3.4: Functional diagram of the TopControl Continuous in combination with a single acting piston valve
TopControl Continuous 93
Fig. 3.5: Process control example: TopControl with sensor
The actual position (POS) is measured by the displacement measuring system. This position value is compared to the normalized
position setpoint signal (CMD). In cases of difference (Xd1), a voltage pulse-width modulation signal is sent as control signal.
With single-acting actuators, a positive error exists and pulses are sent from output B1 to activate the air supply. When a negative
error exists, and pulses are sent from output E1 to activate the exhaust air. With this system, the difference between the position
of the actuator and the setpoint is reduced 0. Z1 represents a disturbance variable.
Z1
B1
CMD Xd1 PK Valve opening
E1
POS
By using the TopControl Continuous as a process controller, the previous position control function is a component of the main
control loop.
The process controller within the main control loop posseses a PID function. The process setpoint (SP) is used and compared to
the controlled process value (PV). A sensor delivers the actual value. The manipulated variable correction functions as described
in chapter 3.2.1 represents a disturbance variable.
Z1
B1
Xd1 PK Valve opening
E1
XPOS
Z2
Valve
CMD Position Process value
SP Xd2 opening
control
loop
Process setpoint Process controller soleno- Process
id valve
PV
Transmitter
TopControl Continuous 95
3.3 TopControl Continuous variants
The TopControl Continuous is available in 3 forms, varying in electrical connection and control functions.
• Terminal with PG cable glands and terminals with restricted functions (Fig. 3.9)
Output
Frequency
Pt 100 Continuous
(Multipole
Binary input connection)
supply
Power
24 V DC
Pt 100
Operating
4..20 mA Continuous
Output
Frequency
Pt 100
(as an alternative to binary
(PG and QUICKON
outputs) variants)
supply
Power
24 V DC
Operating Advice:
Choose between an analogue
position feedback and two binary
outputs by setting the jumper.
Fig. 3.9: Interfaces of the TopControl Continuous on the variants with PG screw connectors and QUICKON connectors
NOTE The TopControl Continuous posses 3-wires instruments. The 24 V DC power supply is isolated from the setpoint
signal.
Close tight function Valve tightly closed over the tightness process range
Statement of a value (in %) above which the drive is completely de-aerated
(at 0 %) or ventilated (at 100 %)
Plug travel limitation Mechanical movement of the valve piston within a specified stroke range
Characteristics curves for process The linearization of the characteristic curvecan be processed
value adjustment
Direction of command of nominal and actual Relationship between the setpoint limit values and the position of the actuator
value
Available parameters Proportional coefficient, reset time, action rate and operating point
Input scale Position of the decimal point, lower and upper scale values of the actual value
and setpoint
Configuration mode Selection of the basic functions, and if necessary additional functions within
this level
TopControl Continuous 97
3.5 Technical characteristics
electrical pneumatic
single acting up up
WW B
TopControl Continuous 99
3.5.3 Characteristics of the TopControl Continuous
Operating data
Conformity to norms
CE According to CE 89/336
Mechanical data
Electrical data
Power supply 24 V DC ± 10 %
Residual pulsation 10 %
No technical direct voltage!
Binary outputs:
Current limitation 100 mA
Pneumatic data
2)
Pressure fluctuations max. ± 10 % during service
Airflow rates Steuerventile 100 lN /min (for air supply and exhaust) 3)
(QNn-Value according to definition of the pressure loss from 7 to 6 bar absolute)
1)
The control pressure has to exceed the pressure from 0.5- 1 bar, in order to ensure the final positioning of the actuator.
2)
Higher pulsation reduces the control accuracy based on the autotune function.
3)
We reserve the right to make technical changes to optimize the function of the TopControl.
NOTE This section allows you to perform the quick commissioning of the TopControl Continuous. The not essenti-
al additional functions are not described in this section. See chapter 5 and 6 for complete explanations
about commissioning and the functions available.
➔ Connect the air supply (3..7 bar, instrument air, oil, water and duster) to port 1.
M16 M12
1 + 24 V
1
2 not connected 24 V DC ± 10 %
Residual ripple 10 %
3 GND
3
4 not connected
5 Power supply + 5
24 V DC ± 10 %
Residual ripple 10 %
6 Power supply GND
6
Once activated, the TopControl Continuous will work and the necessary configuration and self-calibration operations of the
TopControl Continuous will have to be performed (Fig. 4.4).
Fig. 4.3:
QUICKON connectors on QUICKON Pg11, 4-pole
TopControl
4 Set-point +
3 GND
Key assignment:
MANUAL
Mode
5s
END xx Return to the AUTOMATIC mode. The message EEPROM is displayed until the new
parameters are stored.
Message on display:
Manual opening and closing of the valve within the MANUAL mode
Message on display: The previous display within the AUTOMATIC mode remains active.
NOTE Advice Select the POS_xxx display, to ensure that the actual position of the actuator is displayed.
Please refer to the data sheets for dimensions of the TopControl Continuous and complete instrument variants of the
TopControl, pneumatic actuators and valves.
For dimensions and thread types, see data sheet of process valve.
If after installation of the continuous valve, the display of the TopControl Continuous is poorly visible or the cables or hoses
are difficult to connect, the TopControl Continuous can be turned relative to the pneumatic actuator.
Loosen the fluidic connection between the TopControl Continuous and the pneumatic actuator.
Loosen the grub screw sunk in the side of the housing (hex socket SW3).
Turn the TopControl Continuous clockwise, without lifting, into the desired position.
Remake the fluidic connection between theTopControl Continuous and the pneumatic actuator.
If necessary, use longer hoses.
ATTENTION!
If the TopControl Continuous is lifted on turning (displaced axially), the mechanically coupling of the
distance measuring system may be damaged. By turning in the wrong direction (anticlockwise), there is a
risk of unhooking the distance measuring system. It can only be hooked in again with a special tool!
➔ Connect the air supply (3..7 bar, instrument air, oil, water and duster) to port 1 (Fig. 5.1).
➔ Mount the exhaust air pipe or noise reducer on port 3 (Fig. 5.1).
Supply pressure
connector (inscription: 1)
NOTE The pressure supply must exceed the pressure required by the pneumatic actuator and must exceed at
least 0.5 to 1 bar.
This is to ensure that the control process in the upper ranges of the actuator will not become negative due
to a lower pressure difference.
Keep the pressure supply variations within the most restricted limits (max. ±10 %).
Higher variations reduce the reliability of the measured parameters within the AUTOTUNE procedure.
• Multipole connection
• QUICKON connection
ATTENTION!
A screw with a nut is available in the connecting module for connection of the technical earth (TE). In
order to comply with the EMC requirements connect this screw to a good earthing point with a short
length cable (max. 30 cm).
The figure 5.2 indicates the functions of the multipole connectors and assignment of the pins.
Power supply
Signal to SPS
M16 M12
M8 M8
Initiators
Process value
E Binary output 1 E 24 V / 0 V
F 24 V / 0 V
F Binary output 2
K not connected
L not connected
M not connected
1 + 24 V
2 not connected 24 V DC ± 10 %
Residual ripple 10 %
3 GND
4 not connected
Remove the 4 self-cutting screws to open the cover of the terminal box.
The disposal of the terminal is shown on figure 5.3.
Straps
Terminals
5 Power supply + 5
24 V DC ± 10 %
Residual ripple 10 %
6 Power supply GND
6
7 Digital output 1 7 24 V / 0V
8 Digital output 1
8 GND
9 Digital output 2 9 24 V / 0V
10 Digital output 2
10 GND
Set the type of entry signal within the configuration menu (see 6.3.2).
9 GND
9
10 GND
10
GND
10 Pulse -
8 Process 1 9
Pt-100
9 Process 2
8
10 Process 3
TE
QUICKON Pg11, (Technical QUICKON Pg11,
Fig. 5.4: QUICKON connectors on 4-pole Earth) 4-pole
TopControl
4 Set-point + 3 GND
or
b) Process actual value input (see pin assignment on choice of process actual value input)
1 24 V / 0V
1 Binary output 1+
3 Binary output 2+ 24 V / 0V
3
4 Binary output 2-
4 GND
The input type is set via the configuration menu (see 6.3.2).
3 GND
3
4 GND
4
GND
2 Process actual 1 3
4 Process actual 3 2
Aderisolationsmaterial PVC / PE
ATTENTION!
It is necessary to open the TopControl housing to install the inductive proximity switch.
Disconnect the power supply before opening open the TopControl.
➔ Remove the screws and possible seals between the cover and the housing.
➔ Mount each inductive proximity switch at the top over the fixing screws. (Fig. 5.4):
Bild 5.5: Setting of the inductive proximity switch with the setscrews
LED
(in the MANUAL/
AUTOMATIC key)
2 operating levels are provided for operation of the TopControl Continuous (fig. 6.2):
• Configuration level:
Specify the basic functions on initial commissioning and select further additional functions within the configuration level.
➔ Follow the pneumatic and electrical connection instructions before commissioning (chapter 5).
• Enter the unit of the selected input signal (4..20 mA, 0..20 mA, 0..10 V or 0..5 V).
• Start the self-calibration of the TopControl Continuous to the selected operating conditions(Autotune).
AUTOMATIC
Mode 5s
MANUAL
Mode
5s
After switching the power on, the TopControl Continuous is in the process operation level in the AUTOMATIC mode. To enter the
basic configuration, within the configuration level, press the MANUAL/AUTOMATIC key for a duration of 5 seconds. The submenu
ACTFUNC will then be displayed as the first step of the main menu.
To enter the sub-menu ACTFUNC quickly press the MANUAL/AUTOMATIC key. One of the functions of the sub-menu will be
displayed. To move between the different functions, press the arrow keys, additionally enter any desired settings. Press the MA-
NUAL/AUTOMATIC key to validate the wished settings after selection.
NOTE The selected function is displayed on 3 or 4 digits right of the 8-characters LCD. These digits will blink on
the display.
Actfunc
Functions of the actuator
➔ Enter in this sub-menu the configuration of the pneumatical actuator used with the TopControl. See the instrument label for
function valve description.
- single acting
- double acting
Input
Selected input signal
➔ In this sub-menu enter the unit used for the setpoint value.
- Current 4..20 mA
- Current 0..20 mA
- Voltage 0..10 V
- Voltage 0..5 V
Addfunct
Configuration of the additional functions (see Fig. 6.4)
➔ With the X.TUNE sub-menu, you start a program that performs an automatic parametring of the TopControl Continuous.
• Matching the sensor signal to the (physical) stroke of the control valve
• Determining the parameters of PWM signals controlling the internal solenoid valves
• Optimum adjustment of the control parameters of the position controller (target function: quickest possible movement to
set the position without hunting)
➔ To start the autotune function, call the X.TUNE option within the main menu, then leave it by pressing the MANUAL-AUTOMATIC
key for 5 seconds.
Start of the automatic adjustment of the TopControl Continuous to the operating conditions
Display Description
Advice: The basic configuration of the TopControl is pre-set by the factory. On commissioning, however, execution of
”Autotune” is absolutely necessary. The TopControl then determines autonomously the optimum settings for
the current operating conditions.
ATTENTION!
Avoid incorrect adaptation of the controller by executing an Autotune in each case at the supply pressure
available in later operation (= pneumatic auxiliary energy).
If substantial interfering forces are to be expected from the flow through the valve (e.g. from large
pressure fluctuations), Autotune should be executed without medium pressure.
END
Quit the main menu and display the version of the software
➔ In order to quit the main menu, select the submenu END with the arrow key, then validate. On the right hand side of the screen,
the software version is displayed (End xx).Press the MANUAL/AUTOMATIC key for 3-5 seconds, and the message EEPROM
appears on the display during the storage of the changes. The instrument is then in the previous mode (MANUAL-
AUTOMATIC), before the main menu is entered.
NOTE The operating concept of the TopControl Continuous is based on a separate basic and additional functions.
Only the basic functions of the unit are activated on delivery. This enables the basic settings such as specific
units to be set during the initial setting up of the unit (Chapter 4). These are sufficient for the normal
operations.
For more demanding tasks of position and process control, additional functions can be selected and
configurated.
Validation of the selected value Selection of the selected submenu (marked with a star) in
order to suppress it from the main menu.
➔ 5s Within process mode, press the MANUAL/AUTOMATIC key and hold down for 5 sec to activate the
configuration mode.
The configuration menu is constituted of the main menu and the additional menu. The main menu will contain the functions as
specified during the initial commissioning (Chapter 4). The additional menu contains complementary functions and is available
through the ADDFUNCT menu within the main menu. If necessary, you may complete the main menu with functions from the
additional sub-menu, which you can then specify.
➔ By pressing the MANUAL/AUTOMATIC key, validate the additional function within the main menu. The function is marked with
a star (*).
➔ All functions are activated within the main menu after validation through ENDFUNCT.
➔ Enter the parameters of the additional functions within the main menu.
➔ By pressing the MANUAL/AUTOMATIC key, withdraw the additional function from the main menu (the marking star (*) is
removed).
➔ The function is deactivated from the main menu after validation through ENDFUNCT.
Enter the numeric values in the previous functions by pressing one or several times the arrow up key (to increase the value) or
the arrow down key (to decrease the value). If the value is displayed with 4 digits, only the blinking one can be changed with the
arrow key. Pressing the MANUAL/AUTOMATIC key moves to the next position.
Main menu
Validation of the Additional menu
ACTFUNC selected function
Selection of I N P U T
the ADDFUNCT *CHARACT
ADDFUNCT X . T U N E C U T O F F
sub-menu DIRECTN
E N D
S P LT R N G
X . L I M I T
Return to the exten- *X.CONTRL
ded main menu * P. C O N T R L
ENDFUNCT
Fig. 6.6: Principle of the selection of an additional function to the main menu
Output configuration
User calibration
With this function you select a transmission characteristic curve in relation to the position set value (position setpoint) and to the
valve stroke to correct the flow rate respectively the operating characteristic curve.
The operating curve Q = f(s) represents the relationship between the rate of flow Q which flows through a valve fitted in the system
and the stroke s. This curve is also affected by the properties of the pipelines, pumps and consumers. It therefore has a form,
which deviates from the flow characteristic curve.
Specific requirements are usually laid down for the operating characteristic curve (e.g. linearity) in the case of correcting tasks for
closed loop control systems. Therefore it is sometimes necessary for this reason to correct the pattern of the operating curve in a
suitable manner. A transmission element, which implements various characteristic curves that can be used to correct the
operating curve, is provided in the TopControl Continuous for this purpose.
The equipercentile curves 1:25, 1:33, 1:50, 25:1, 33:1 and 50:1 and a linear characteristic may be set. Furthermore, it is possible
to programme any characteristic via reference points or have it calibrated automatically.
The characteristic curve is defined by means of 21 restart points distributed uniformly over the set positioning range of 0 ... 100%.
These are spaced at 5%. A freely selectable stroke (range 0 ... 100%) can be assigned to each restart (Fig. 6.8). The difference
between the values of the stroke of two adjacent restart points shall not exceed 20%.
To input the characteristic curve points (function values), the CHA FREE menu item is first set.
After operation of the MANUAL/ AUTOMATIC key the first restart point is input with the display 0 (%). After this the next function
value is 0 (%).
A function value from 0 to 100% can be set using the arrow keys. After confirmation using the MANUAL/AUTOMATIC key the next
restart point is shown on the display etc. If finally the MANUAL/AUTOMATIC key is pressed to confirm the function value for the
last restart point (100%), the program switches back to the CHARACT menu item.
Valve
stroke
[%]
Input signal
[%]
NOTE A table for noting the reference points entered is to be found in the Annex
Note: .
Cutoff
Close tight function
The closed tight function ensures that the valve is tightly closed outside the control range. Specification of a value (%) from which
the actuator air is completely exhausted or supplied with air. With the fast pressurizing/venting version, two valves are driven
in each case in order to completely vent and pressurize more rapidly. The opening or resumption of the control operation
takes place with a hysteresis of 1% (refer to Fig. 6.9).
Setpoint [%]
Dir.cmd
Direction of command of the setpoint of the actuator
With this additional function, the direction of action according to setpoint of the actuator and the input signal (Fig. 6.10).
Rise direction
(i.e. 4 mA bzw. 0 V → 0%
20 mA bzw. 5/10 V → 100%)
Fall direction
(i.e. 4 mA bzw. 0 V → 100%
20 mA bzw. 5/10 V → 0%)
RISE
FALL
Input signal
Dir.act
Relationship or direction of the actuator
This function determines the direction of action between the air supply state and the actual value indication of the actuator
(Fig. 6.11).
Direct command
(exhausted → 0% supplied → 100%)
Inverse command
(exhausted → 100% supplied → 0%)
Set position
RISE
FALL
This additional function enables the set value range of a TopControl Continuous to be restricted by stipulating a minimum and
maximum value. This makes it possible to divide the used unit signal range (4..20 mA, 0..20 mA, 0..10 V oder 0..5 V) over several
TopControl Continuous (without or with an overlap). In this way, several valves can be partially used either simultaneously or in
sequence as a final controlling element (Fig. 6.12).
Setpoint
[mA]
Fig. 6.12: Splitting a unit signal range into Setpoint range Setpoint range
two set value ranges Top Control Top Control
Continuous 1 Continuous 2
This additional function enables the (physical) stroke to be limited to a given MIN and MAX percentage value (Fig. 6.13).
There, the stroke range of the limited stroke is set to equal 100%.
If during servicing the selected plug travel is overpassed, then the display of POS value may be greater than 100 % or lower
than 0%.
Unlimited plug
travel
Control range in automatic mode
Control range in manual mode
Limited plug
travel
Setpoint [mA]
X.time
Setting speed limitation
On execution of the function X.TUNE, the minimum opening and closing times for the entire stroke are entered in T.OPN and
T.CLS automatically. In this way, operation at maximum speed is selected.
If the control speed is to be limited, values for T.OPN and T.CLS may be entered that lie between the minimum values
determined by X.TUNE and 60 s.
Opening speed
Entry in s
Closing speed
Set-point
value
Actual
value
t
T.OPN
Fig. 6.14: Effect of limiting the opening speed for a jump in the set-point value
X.contrl
Parameters setting for the TopControl Continuous
This function ensures that the TopControl Continuous acts only then a selected control difference is measured (Fig. 6.14).
This function protects the servovalve and pneumatic actuator by controlling the start-up frequency.
The setting is optimized automatically with X.TUNE.
Proportional factor for the TopControl Continuous (to close the valve)
Proportional factor for the TopControl Continuous (to open the valve)
Control
Position setpoint difference to the controller
Xd1 Xd1'
Xd1
Actual DBND
position
P.control
Parameters setting of the process controller
P.co - dbnd
Deadband of the process controller Factory setting: 1% (relative to the range of the selected
process set-point input
This function ensures that the postioner acts only then a selected control difference is measured (Fig. 6.15). This function
protects the servovalve and pneumatic actuator by controlling the start-up frequency.
4..20 mA 4 .. 20 mA 16 mA 0,16 mA
Xd2'
Control
Position setpoint difference to the controller
Xd2 Xd2'
Xd2
Actual DBND
position
P.co - para
Controller PID parameters
Reset time
0.5...999.9 (factory setting 999.9)
See Appendix
NOTE A table for noting the reference points entered is to be found in the Annex
P.co - inp
Analogue input type
Enter the analogue input signal type according to the transmitter signal.
P.co - filt
Filtering of the process actual values. Valid for all process actual value types.
FILT xx
Setting in 10 steps: 0..9
Setting in 10 steps
1 5
2 3
3 2
4 1
5 0,7
6 0,5
7 0,3
8 0,2
Scale limit selection example for the 4..20 mA input (Fig. 6.16):
PV 0 0 0
PV 1.0 10.0 100.0
Process SP 0 0 0
setpoint SP 0.8 8.0 80.0
Input signal
[mA] Fig 6.16: Example of scale limit for controller input
NOTE On entry of small scaling values, to increase the display accuracy, places after the decimal point are
automatically added, so that the maximum possible digit range is obtained between the lower and upper
scaling value in each case.
The amplification (KP) of the process controller relates to scale values set.
With P.CO SETP / SETP INT (desired value pre-set via the arrow key), no scaling of the desired value SP and
SP not possible. It can be entered directly in correspondence with the scaled process variable (PV , PV ).
NOTE The valve is closed as this menu is activated. Then, the Teach-In is performed with a defined output
conditions.
Unit l/s
Unit l/m
Unit m³/min
Unit m³/h
Unit gal(US)/s
Unit gal(US)/min
Unit gal(US)/h
Unit gal(Imperial)/s
Unit gal(Imperial)/min
Unit gal(Imperial)/h
Position of the decimal point for the process setpoint and actual value (Selectable value: 0..3).
Manual entry of the K-factor of the flow sensor (refer to the data sheet of the flow sensor)
Teach-In-Function:
Calculation of the K-Factor, by measuring a known fluid volume .
CODE
Code protection for the settings
When code protection is active, the entry code is demanded every time a blocked operation is attempted:
Searching of a security
position
normally closed
(0..5 V = 1; 10..30 V = 0)
normally open
(0..5 V = 0; 10..30 V = 1)
* If the safety position is 0 or 100%, the actuator is completely vented or pressurized, respectively, as soon as the
relevant signal is applied to the binary input.
With the fast pressurizing/venting version, two valves are driven in each case in order to completely vent and
pressurize more rapidly.
Output Option
Configuration of the output signals
Current 4..20 mA
Current 0..20 mA
Voltage 0..10 V
Voltage 0..5 V
normally closed
allowed control
range*
normally open
normally closed
lower threshold
(output 1)
normally open
normally closed
higher threshold
(output 2)
normally open
OUT DEV Choice: Alarm output for high control deviation (output 1)
* the selected control deviation Dev xxx must not be lower than the deadband.
NOTE The signal values within parenthesis are only available as a display and cannot be modified. The type of
signal as previously selected in the configuration menu is displayed:
CAL Inp: Display of the selection within the INPUT menu
CAL OUT: Display of the selection within the outPUT menu
cal inp Calibration of the position setpoint (4..20 mA; 0..20 mA; 0..5 V; 0..10 V)
Entry of the minimal input signal (0 mA; 4 mA; 0 V):
set the minimal input signal with the arrow key, then validate by pressing the MANUAL/AUTOMATIC
key
cal out Calibration of the analogue signl output (4..20 mA; 0..20 mA; 0..5 V; 0..10 V)
Cal fact Return to the factory setting within the Cal.user function:
Press the MANUAL/AUTOMATIC key until the countdown elapsed.
only activated in
case of analogue
position indication
NOTE The signal units within parenthesis are only available as a display and cannot be modified. The type of
signal as previously selected in the configuration menu is displayed:
CAL PV: Display of the selection within the P.co.inp menu
CAL Sp: Display of the selection within the P.co.setp menu
CAL OUT: Display of the selection within the outPUT menu
cal sp Calibration of the position setpoint; the type of setpoint (4..20 mA; 0..20 mA; 0..5 V; 0..10 V) was
selected in the INput menu
Set the minimal setpoint (0 mA; 4 mA; 0 V) with the arrow key, then validate the value by pressing the
MANUAL/AUTOMATIC key
Set the maximal setpoint (20 mA; 5 V; 10 V) with the arrow key, then validate the value by pressing the
MANUAL/AUTOMATIC key
cal pv Calibration of the actual process value ; the type of the actual process value (4..20 mA; Pt 100) was
selected in the PCO-inp menu
if 4..20 mA selected:
Set the minimal input then validate by pressing the MANUAL/AUTOMATIC key
Set the maximal input signal then validate by pressing the MANUAL/AUTOMATIC key
if Pt-100 selected:
Correct the displayed value with the arrow key until the display on the TopControl is in accordance with
the reference measuring instrument, then validate by pressing the MANUAL/AUTOMATIC key.
cal out Calibration of the analogue signl output (4..20 mA; 0..20 mA; 0..5 V; 0..10 V)
Cal fact Return to the factory setting within the Cal.user function:
Press the MANUAL/AUTOMATIC key until the countdown elapsed.
setfact
Return to the factory setting
This function allows the user to return to the initial factory setting. All EEPROM parameters are reset to default value. Finally a
complete hardware reset of the instrument is performed.
In order to use the TopControl Continuous as a process controller, apply the following requirements:
➔ Perform first the self-calibration procedure for the position controller (X.TUNE - see 6.3.2).
➔ Select the P.CONTRL additional function within the configuration mode in the main menu (see 6.4).
The function P.CONTRL will also be activated into the main menu.
➔ Enter the basic configuration of the process controller within the P.CONTRL function (see 6.4).
If the process control acts on a flow process control, it is possible to use the automatic linear characteristic curve of
the process:
ATTENTION!
Perform the functions in the following order, in any case! X.TUNE
P.QLIN
P.QLIN
This function is only useful for a flow process control
➔ Start the function to obtain the automatic linear characteristic curve by selecting the function P.Q’LIN within the main menu
and pressing the MANUAL/AUTOMATIC key during 5 seconds.
NOTE It is only possible to activate the function P.Q'LIN within the main menu if the functions P.CONTRL / P.COINP /
INPFREQ or P.CONTRL / P.COINP / INP4'20mA has been selected.
By activation of the function P.CONTRL the function P.QLIN is automatically copied within the main menu. Start the function to run
the program to obtain the automatic correction curve.
The program increases the valve stroke in 20 steps from 0 to 100 % and measures the associated process variable. The couple
of points of the correction characteristic curve are used within the sub-menu CHARACT/CHAFREE as a free programmable
characteristic curve, and can be checked within this sub-menu.
If the function CHARACT was not previously, transferred within the main menu by the sub-menu ADDFUNC this will be automatically
performed by the call to the P.Q'LIN function, and the function CHARACT/CHAFREE will be simultaneously activated.
Display Description
Fig. 6.17 Display during launching and performing the linearisation function
The process operating level is automatically set each time the unit is switched on. From configuration level you can change
over to the process operation level by using the MANUAL/AUTOMATIC key and after validation of the instruction END of the
menu.
The process operating level allows viewing of normal control functions (AUTOMATIC mode) and to open and close the valve
manually (MANUAL mode).
To change over between MANUAL and AUTOMATIC operating mode press the
MANUAL/AUTOMATIC key.
From MANUAL or AUTOMATIC mode you can change over to the configuration level by pressing the
5s MANUAL/AUTOMATIC key for 5 seconds.
Returning to the process operation level, the unit operates in the last selected level before changing.
MANUAL off -
In AUTOMATIC operating mode the system functions in the process control configuration.
Display switching
or
By pressing the arrow keys you activate the changing over between the 4 display possibilities (Fig. 6.19).
AUTOMATIC Configuration
operating mode
Point of Menu
END
(> 5 s)
POS__xxx
or
CMD__xxx No activity
Chance over
of the
INP__xxx of the
Leave the key operator
display
TEMP_xx.x
MANUAL
operating mode
Fig. 6.19: Display, operation structure and operating instructions in AUTOMATIC mode with inactive process controller
NOTE When the menu item BIN IN / BIN FUNC / FUNC SPOS is active and the binary input is switched, the
message SAFE xxx appears in the display.
The value XXX indicates the previously selected safety position in %.
By pressing the arrow keys you activate the changing over between the 6 display possibilities (Fig. 6.120).
AUTOMATIC Configuration
operating mode
Point of menu
END
PV___ (> 5 s)
SP___ or or
N o
SP S e t t i n g
Change over
POS__xxx a c t i v i - o f
of the t aktive
y
Leave the key Leave the key p r o c e s s
display
CMD__xxx
TEMP_xx.x
Manual
operating mode
Fig. 6.20: Display, operation structure and operating instructions in AUTOMATIC mode with active process controller
NOTE When the menu item BIN IN / BIN FUNC / FUNC SPOS is active and the binary input is switched, the
message SAFE xxx appears in the display.
The value XXX indicates the previously selected safety position in %.
Use the same procedure for the next digits. After validating of the 4 th digit, the program automatically returns to the menu.
In the MANUAL operating mode the valve can be opened or closed manually.
Continuously pressing the ”up arrow” and ”down arrow” keys simultaneous:
and Produces a quick opening action
Continuously pressing the ”down arrow” and ”up arrow” keys simultaneous:
and Produces a quick closing action
• To display the actual value of the actuator during the MANUAL operation mode,
previously selected in the AUTOMATIC mode display POS__xxx.
By continuously pressing the ”up arrow” key in the MANUAL operating mode, the valve is continuously opened.
To stop the function release the key and the valve will remain in the open position. By pressing the ”down arrow” key the valve will
be closed proportionally.
An additional pressing of the second arrow key generates a quick action of the valve (closing or opening) depending on the first
selected arrow (Fig. 6.21).
MANUAL
mode
Valve Valve
closed - END open -
high speed high speed
Configuration
The TopControl Continuous is maintenance free if used according to the recommendations of this manual.
X.ERR 2 Air pressure failure during Control the compressed air supply
Autotune
POS = 0 (by CMD > 0%) Close tight function (CUTOFF) Disactivate the close tight function
resp. is involuntary active (see 8.7.4)
POS = 100%, (by CMD < 100%)
For optional control behaviour and the reaching of the desired maximum flowrate the following criteria must be observed:
• The correct selection of the kV value, which is in fact defined by the valve size;
• The correct adjustment of the valve size to the pressure conditions, taking into account the pressure differences of the
installation.
Sizing guidelines can be given based upon the kV value. The kV value relative to the normal conditions for pressure, temperature
and fluid.
The kv value is the flowrate in m³/h though a piping port under a pressure difference of ∆p = 1 bar and T = 20°C.
For continuous valves the kVS value is used in addition. It corresponds to the kV value of a continuous valve, which is fully open.
In relation with the given data, we distinguish the two following cases for the sizing of the valves:
a) The pressures p1 and p2 must be known before and after the valve before the desired maximum flowrate Qmax can be
calculated:
(1)
∆p0 ρ
kVS = Qmax ⋅ ⋅
∆p ρ0
Where:
kVS: maximal flowrate of fully opened continuous valve [m³/h]
Qmax: maximal volumetric flowrate [m³/h]
∆p0: = 1 bar; pressure drops of the valve according to the kV value defined
ρ0 : = 1000 kg/m³; density of water (according to the kV value definition)
∆p: pressure drop of the valve [bar]
ρ: density of fluid [kg/m³]
b) The pressures p1 and p2 at the inlet and outlet of the complete installation for the desired maximum flowrate Qmax can be
calculated:
1.Step: Calculation of the kVges value for the complete installation according to rule (1).
2. Step: Determination of the flowrate through the installation without a continuous valve (possible by by-passing the pipe
where the valve is installed).
3. Step: Calculation of the kVa value of the installation without the continuous valve according to rule (1).
4. Step: Calculation of the needed k VS value of the continuous valve according to rule (2):
1
kVS =
(2)
1 1
2
− 2
kVges kVa
Important rule:
The kVS value of the valve should reach at least the value calculated by the formula (1) or (2) depending on the application. It
should also not greatly exceed this value.
The often used rule for on/off valves ‘a little bit higher cannot be wrong’ can strongly influence the control behaviour of continuous
valves!
(∆p)V 0 kVa 2
Ψ= =
(∆p) 0 kVa 2 + kVS 2
(3)
with
(∆p)V0: pressure drop with a fully open valve
(∆p)0: pressured drop over the complete installation
The control behaviour (standard choice, maximum adjustment time) is strongly dependent on the working
point when using a corrected characteristic.
A PID controller has a proportional, an integral and a differential component (P, I and D components).
P component:
Function: Y = Kp · Xd
Kp is the proportional action coefficient. It results from the ratio of the manipulating range ∆Y to the proportional range ∆Xd.
Manipulating range ∆Y
Fig. 8.1: Characteristics and step response of the P component of a PID controller
Characteristics:
Theoretically, a pure P controller operates without delay, i. e. it is fast and therefore dinamically favorable. It has a lasting system
deviation, i. e. it does not balance out the effects of disturbances completely and is therefore relatively unfavorable from the static point
of view.
I component:
Function: Y= 1 ∫ Xd dt
Ti
Ti is the integration or manipulating time. This is the time that elapses before the manipulated variable has passed through the
complete manipulating range.
Manipulating range ∆Y
Fig. 8.2: Characteristics and step response of the I component of a PID controller
A pure I controller eliminates the effects of occuring disturbances completely. Therefore, it has a favorable static response. Owing
to its finite manipulating speed, it operates more slowly than the P controller and tends to oscillate. Therefore, it is relatively unfavorable
from the dynamic point of view.
D component:
Function: Y = Kd d Xd/dt
Fig. 8.3: Characteristics and step response of the D component of a PID controller
Characteristics:
A controller with a D component reacts to changes in the controlled variable and is accordingly capable of dissipating occurring
deviations faster.
Y = Kp Xd + 1 ∫ Xd dt + d Xd/dt
Ti
Where Kp · Ti = Tn and Kd/Kp = Tv, results with regard to functioning of the PID controller:
Y = Kp (Xd + 1 ∫ Xd dt + Tv dXd/dt)
Tn
P Component
P component
Fig. 8.4: Step response and rise response of the PID controller
dY dXd
Function: T + Y = Kd
dt dt
dY 1 dXd
T + Y = Kp (Xd + ∫ Xd dt + Tv )
dt Tn dt
When using this method, controller parameters are adjusted on the basis of the control loop's response at the stability limit. In doing
so, the controller parameters are adjusted so as to ensure that the control loop begins to oscillate. A conclusion as to a favorable
adjustment of the controller parameters is reached from critical characteristic values occurring in this case. It goes without saying that,
when using this method, it must be possible to bring the control loop to oscillation.
Method:
• Set the controller as a P controller (i.e. Tn = 999, Tv = 0), initially selecting a low Kp value
• Increase Kp until the controlled variable oscillates continuously without attenuation (see following figure).
The proportional action coefficient set at the stability limit is referred as Kcrit. The resulting oscillation period is referred to as Tcrit.
Actual value
Tkrit
Time
On the basis of Kcrit and Tcrit, the controller parameters can then be calculated in accordance with the following table.
The Ziegler and Nichols adjustment rules were determined for P systems with a time delay of the first order and a dead time. However,
they apply only to controllers with a disturbance response, but not to controllers with a command response.
Adjustment rules according to Chien, Hrones and Reswick (manipulated variable methode)
When using this method, the controller parameters are adjusted on the basis of the control system's transition response. A 100%
change in the manipulated variable is output. The time Tu and Tg are derived from the progression of the actual value of the control
variable (following figure).
∆Y
t
Actual value
Ks * ∆Y
Controlled
variable
∆X
t
Tu Tg
Figure 8.8: Progression of the controlled variable after a manipulated variable change ∆Y
Method:
• Output a manipulated variable change and record the controlled variable with a recorder
• Switch off in good time if you encounter critical progressions (e. g. a risk of overheating).
NOTE Pay attention to the fact that, in thermally inert systems, the actual value of the controlled variable may
increase further switching off.
The following table lists the settings for the controller parameters depending on Tu, Tg and Ks for command and disturbance response
and for an aperiodic control operation as well as a control operation with 20% overshoot. They apply to systems with a P response,
with a dead time and with a delay of the 1st order.
Parameter settings
Controller Aperiodic control operation Control operation
type (0 % overshoot) with 20 % overshoot
Tg Tg Tg Tg
Kp = 0,35 Kp = 0,6 Kp = 0,6 Kp = 0,7
Tu*Ks Tu*Ks Tu*Ks Tu*Ks
PI control-
Tn = 1,2 Tg Tn = 4 · Tu Tn = Tg Tn = 2,3 · Tu
ler
Tg Tg Tg Tg
Kp = 0,6 Kp = 0,95 Kp = 0,95 Kp = 1,2
Tu*Ks Tu*Ks Tu*Ks Tu*Ks
PID con-
Tn = Tg Tn = 2,4 · Tu Tn = 1,35 · Tg Tn = 2 · Tu
troller
Tv = 0,5 · Tu Tv = 0,42 · Tu Tv = 0,47 · Tu Tv = 0,42 · Tu
The proportionality factor Ks of the controlled member is given according to Figure 8.8 by:
∆X
Ks =
∆Y
Process
controller
active
Process
controller
active
Analog
position
feedback
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
KP
TN
TV
X0
DBND