TRANSFORMER
Comprehensive solutions
from design to delivery
Transformers 2
Mechanical design 6
Connection systems 7
2
ELECTRICAL DESIGN
For cast resin transformers, natural air cooling (AN) is standard. Forced air cooling (AF) is also applicable.
3
ELECTRICAL DESIGN
Distribution Power
Transformers Transformers
The transformers listed in this guide are primarily Generator transformers and large power transform-
three-phase transformers with one set of windings ers are usually connected in Yd.
connected in star (wye) and the other one in delta, For star/star-connected transformers and autotrans-
whereby the neutral of the star-connected winding formers normally a tertiary winding in delta, whose
is fully rated and brought to the outside. rating is a third of that of the transformer, has to be
The primary winding (HV) is normally connected in added. This stabilizes the phase-to phase voltages in
delta, the secondary winding (LV) in wye. The the case of an unbalanced load and prevents the
electrical offset of the windings in respect to each displacement of the neutral point.
other is either 30, 150 or 330 degrees standard Single-phase transformers and autotransformers are
(Dy1, Dy5, Dy11). Single-phase transformers are used when the transportation possibilities are
also available and included in this catalogue. limited. They will be connected at site to three-phase
Details of autotransformers can be provided on transformer banks.
request.
I
Dy1 1 Yd1 I
1
iii i
iii i
ii
III II III II
ii
Dy5 I Yd5 I
ii iii iii
i ii
III II III i II
5 5
11 I
Dy11 Yd11 I
i 11
ii i
iii ii
III II
III iii II
4
ELECTRICAL DESIGN
group
withstand voltage
powerfrequency
5
MECHANICAL DESIGN
General mechanical design for oil-immersed transformers:
Iron core made of grain-oriented electrical sheet steel insulated on both sides, core-type.
Tank design
6
CONNECTION SYSTEMS
Distribution transformers
HV LV
Flange Flange/throat
7
ACCESSORIES AND PROTECTIVE DEVICES
Buchholz relay
This is installed at a small angle (sloping from conservator to cover) between the
conservator and the cover plate. Generally, isolating valves are provided on
either side of the relay. A separate gas relay is provided for the conservator or
partition for the on-load tap changer. The isolating valves help in opening or
removal of the gas relay for inspection or maintenance purposes, without having
to drain the oil from the conservator. The gas relay has alarm and trip contacts.
The relay can be provided with a gas-sampling valve, which can be located at a
convenient height for ease of use.
All bushing current transformers provided are manufactured by Energypac unless otherwise requested by the customer.
8
ACCESSORIES AND PROTECTIVE DEVICES
Dehydrating breather
This is to prevent ingress of moisture in to the conservation system, where air
circulation is controlled by liquid seal and special re-chargeable moisture
absorbing material. The volume of charge in the breather is a function of the oil
quantity in the transformer. The breathers are located at convenient height for
inspection and recharging. Separate breathers are provided for the conservator
(or partition) of the on-load tap changer. The charge is placed in a visible
container so that the changes in the colour of the charge are easily visible.
Self dehydrating breathers are also available on request. Fig.: Dehydrating breather
Other accessories
5. Tap changer control 6. Remote measurement 7. Valves for oil filling, draining, filtering and
panels systems for temperature sampling, with locking facility.
monitoring
Marshalling box
As the name implies, this is the master control panel for the protection devices.
This is a panel with a door, part of which is with glass, allowing easy visibility of
the instruments and their readings. This houses the indicating instruments. In
addition, all the secondary wiring of the transformer from current transformers,
relays, oil level gauges etc., are terminated on to terminal blocks, from which
cables can be taken to the supply and control connections. The necessary control
switches, contactors etc., are housed in this cabinet. The cabinet may be
provided with heating and anti-condensation facility. The cabinet has a ventilation
facility, which is protected against insect entry. The fixing is carried out with Fig.: Marshalling box
anti-vibration pads.
9
POLE MOUNTED
SINGLE PHASE TRANSFORMER
• Paint system meeting or exceeding the • Dual voltage primary complete with
performance of the IEEE C57.12.28
externally operated voltage switch
Standard including the salt spray test
• Extra creep bushing
• Cover or sidewall mounted high voltage
bushing(s) as required • Surge arrester bracket
• Low voltage spade or clamp type (basket) • Internal Fault Detector (IFD)
terminals as required
• Nonconductive transformer
• Provision for surge arrester bracket,
bracket available as an option • Stainless steel tank and cover
10
TECHNICAL DATA
POLE MOUNTED SINGLE PHASE TRANSFORMERS
UP TO 36kV, 75kVA
Design Standard ANSI C57.12.00 & C57.12.20
Type Single-phase wound core
Winding Type Material High Conductivity Cu
Core Type and material Wound Core, CRGO Silicon Steel
HT = 6350 V
Nominal Voltage
LT = 240 V
HT Winding = 95 KV
BIL
LT Winding = 30 KV
a) For 5-37.5 KVA 2.5+10% max
Max % Impedance at rated KVA
b) For 50-75 KVA 3.00+10 % max
Polarity Additive
Cooling Method Class- OA (Self-cooled)
a. Winding Shall not exceed 65°C (Resistance Method)
b. Insulation Liquid Shall not exceed 65°C
Bushing
a) Type & Material Outdoor type, Porcelain
b) Connectors Bolted ring type
c) Quantity HT = 1, LT = 2
d) Mounting Position HT – on tank top cover, LT- on the tank side
Tank
a) Design Sealed type complete with cover & gasket
b) Ground provision With bolted ring type connector
c) LV ground provision With removable Cu strap
d) Lifting facilities Facilities for lifting the core & coil
e) Support Lug Shall have support lugs
f) Pressure relief device Self sealing relief device
g) Painting Light Gray, ANSI Color #70
Insulating oil New, Unused mineral oil as per ASTM standard
Rating Rated Frequency Impedance Full Load Current
Dimensions Weight (KG)
(KVA) Voltage (V) (HZ) (Max) % (Amps) No Load Full Load
Loss (W) Loss (W)
High Low High Low Diameter Height Total Oil
11
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
H1
9
HV side:
LV rating: 400–720 V (special designs
En e r g ypac
7
for up to 12 kV can be built)
Connection: HV winding: delta
2 8 LV winding: star
E
(up to 100 kVA: zigzag)
Impedance 4% (only up to HV
voltage at rated rating 24 kV and
3 2N 2U 2V 2W current: £ 630 kVA) or 6% (with
rated power ³ 630 kVA or
B1
1U 2U 1W
with HV rating > 24 kV)
Cooling: ONAN
Protection class: IP00
6 Final coating: RAL 7033 (other
A1
colors are available)
Losses
The standard IS-1180
(= DIN 42500 Part 1) applies to three-phase oil-immersed distribution transformers 50 Hz, from 50kVA to 2500 kVA, up to 36kV.
For total load losses (Pk), three different listings, level - I, II and III are specified. Transformers of this kind with additionally reduced
losses are especially economical with energy (maximum efficiency > 99%). The higher costs of these transformers are counteracted by
the energy savings which they make.
12
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
UP TO 36kV
13
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
UP TO 36kV
Rated power Max. rated Impedance 50% Load 100% Load Material
volt. HV side voltage
14
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
UP TO 36kV
Rated power Max. rated Impedance 50% Load 100% Load Material
volt. HV side voltage
15
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
UP TO 36kV
Rated power Max. rated Impedance No-load losses Load losses Material
volt. HV side voltage
16
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, OIL FILLED
UP TO 36kV
17
DISTRIBUTION TRANSFORMERS
CAST RESIN
Energypac offers a full range of dry-type transformers up to 10MVA, with 36kV on the high voltage side and 12kV on the low
voltage side. These are built according to all major standards including IEC, IS and ANSI and when required as per the loss
directives of ECBC-2018. To minimize environmental contamination and fire hazard, customers are specifying dry-type transformers
more frequently. These transformers meet strict parameters with respect to electrical system demands and functioning in areas
with extreme climatic conditions. Energypac's cast resin transformers are virtually maintenance free and are manufactured in
accordance with industry and international standards including ISO 9001.
Features
Self extinguishing material
High voltage coil windings are
Compact footprint cast to prevent humidity
Easy installation High resistance against over
Maintenance free voltage
Environment friendly Low decibel
Apart from toxic or generated High capacity
gases, if fired High performance
Design to withstand the Low partial discharge
highest mechanical short
circuit stress that may occur
in service
Clamping
Frame
Core
HV Terminal
Delta Connections
Fan
LV Winding
Base
18
DISTRIBUTION TRANSFORMERS
CAST RESIN
Standard encloser
19
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, CAST RESIN
UP TO 36kV
Standard: IEC 60076-13 Connection: HV winding: delta
Rated power: 100–20000kVA* LV winding: star
Rated frequency: 50 Hz Insulation class: HV/LV = B, F and H Climatic class: C2
HV rating: up to 36kV Temperature rise: HV/LV = 100/100 K (F) Environmental class: E2
LV rating: up to 3.3kV; special designs HV/LV=120/120 K (H) Fire behaviour class: F1
for up to 12kV are possible Color of metal parts: RAL 9005
Tapings on HV side: ±2.5% or±2 x 2.5% (other colors are available)
(also available with on-load tap changers on request.)
20
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, CAST RESIN
UP TO 36kV
Fig.: Distribution transformers, cast resin 250 to 400kVA *Available in aluminium and copper windings on request
21
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, CAST RESIN
UP TO 36kV
Rated Rated Loss at Loss at
power voltage Impedance 50% load 100% load Material
Fig.: Distribution transformers, cast resin 500 to 800kVA *Available in aluminium and copper windings on request
22
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, CAST RESIN
UP TO 36kV
Rated Rated loss at Loss at
power voltage Impedance 50% load 100% load Material
Fig.: Distribution transformers, cast resin 1000 to 1600kVA *Available in aluminium and copper windings on request
23
TECHNICAL DATA
DISTRIBUTION TRANSFORMERS, CAST RESIN
UP TO 36kV
Rated Rated loss at Loss at
voltage Impedance 50% load 100% load Material
power
[kVA] [kV] [%] [W] [W]
Fig.: Distribution transformers, cast resin 2000 to 2500kVA *Available in aluminium and copper windings on request
24
Head Office India Office
Energy Center, 25 Tejgaon I/A, Bhakta Tower, KB-22, 4th Floor, Sector III,
Dhaka-1208, Bangladesh Salt Lake, Kolkata-700 098, India
Phone: +88028 87 93 95 Phone: +91 33 4006 5853
Fax: +88028 87 93 98 Email: [email protected]
Email: [email protected]
www.energypac-bd.com
CPRI Type Tested, ISO 9001:2015, 14001:2015 & ISO 17025: 2005
www.energypac-bd.com