Output Ratings Ratings and Performance Data: 65.0 kVA 52.0 KW 72.0 kVA 57.6 KW
Output Ratings Ratings and Performance Data: 65.0 kVA 52.0 KW 72.0 kVA 57.6 KW
com
F72-1
Image for illustration purposes only.
Voltage, Frequency Prime Standby Engine Make & Model: FG Wilson FD4-4.6A1
400V, 50 Hz 65.0 kVA / 52.0 kW 72.0 kVA / 57.6 kW Alternator manufactured for
Marelli
FG Wilson by:
- / - - / -
Alternator Model: MJB 200 MB4
Ratings at 0.8 power factor. Control Panel: DCP-10
Please refer to the output ratings technical data section for Base Frame: Heavy Duty Fabricated Steel
specific generator set outputs per voltage. Circuit Breaker Type: 3 Pole MCB
Frequency: 50 Hz 60 Hz
Engine Speed: rpm 1500 -
Prime Rating
These ratings are applicable for supplying continuous electrical power Fuel Tank Capacity:
(at variable load) in lieu of commercially purchased power. There is no 180 (47.6)
litres (US gal)
limitation to the annual hours of operation and this model can supply 10%
Fuel Consumption: l/hr (US gal/hr)
overload power for 1 hour in 12 hours.
(100% Load) - Prime 13.9 (3.7) -
Standby Rating
These ratings are applicable for supplying continuous electrical power (at - Standby 15.1 (4.0) -
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).
1870 (73.6) 840 (33.1) 1482 (58.3) 968 (2134) 981 (2163)
Dry = With Lube Oil Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22.
Generator set pictured may include optional accessories.
Engine Technical Data Air Systems 50 Hz 60 Hz
60 Hz - - -
(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869,
Class A2)
Alternator Physical Data Alternator Operating Data
Alternator
50 Hz 60 Hz
Performance Data:
Motor Starting
104 97 87
Capability* kVA
Short Circuit
- - -
Capacity %
Documentation
A full set of operation and maintenance manuals and circuit wiring diagrams.
The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.
Warranty
All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's
warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.