0% found this document useful (0 votes)
266 views

Output Ratings Ratings and Performance Data: 65.0 kVA 52.0 KW 72.0 kVA 57.6 KW

This document provides information about an FG Wilson FD4-4.6A1 generator set including its: 1) Ratings of 65.0 kVA/52.0 kW prime and 72.0 kVA/57.6 kW standby at 400V and 50Hz. 2) Engine details including a 4.6L, 4-cylinder turbocharged diesel engine. 3) Dimensions of 1870mm x 840mm x 1482mm and dry weight of 968kg.

Uploaded by

Akash Chandra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
266 views

Output Ratings Ratings and Performance Data: 65.0 kVA 52.0 KW 72.0 kVA 57.6 KW

This document provides information about an FG Wilson FD4-4.6A1 generator set including its: 1) Ratings of 65.0 kVA/52.0 kW prime and 72.0 kVA/57.6 kW standby at 400V and 50Hz. 2) Engine details including a 4.6L, 4-cylinder turbocharged diesel engine. 3) Dimensions of 1870mm x 840mm x 1482mm and dry weight of 968kg.

Uploaded by

Akash Chandra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

www.FGWilson.

com

F72-1
Image for illustration purposes only.

Output Ratings Ratings and Performance Data

Voltage, Frequency Prime Standby Engine Make & Model: FG Wilson FD4-4.6A1
400V, 50 Hz 65.0 kVA / 52.0 kW 72.0 kVA / 57.6 kW Alternator manufactured for
Marelli
FG Wilson by:
- / - - / -
Alternator Model: MJB 200 MB4
Ratings at 0.8 power factor. Control Panel: DCP-10

Please refer to the output ratings technical data section for Base Frame: Heavy Duty Fabricated Steel
specific generator set outputs per voltage. Circuit Breaker Type: 3 Pole MCB
Frequency: 50 Hz 60 Hz
Engine Speed: rpm 1500 -
Prime Rating
These ratings are applicable for supplying continuous electrical power Fuel Tank Capacity:
(at variable load) in lieu of commercially purchased power. There is no 180 (47.6)
litres (US gal)
limitation to the annual hours of operation and this model can supply 10%
Fuel Consumption: l/hr (US gal/hr)
overload power for 1 hour in 12 hours.
(100% Load) - Prime 13.9 (3.7) -
Standby Rating
These ratings are applicable for supplying continuous electrical power (at - Standby 15.1 (4.0) -
variable load) in the event of a utility power failure. No overload is
permitted on these ratings. The alternator on this model is peak
continuous rated (as defined in ISO 8528-3).

Standard Reference Conditions Available Options


Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m
(328 ft) A.S.L. 30% relative humidity. FG Wilson offer a range of optional features to tailor our generator
sets to meet your power needs. Options include:
Fuel consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2.  Upgrade to CE Certification
 A wide range of Sound Attenuated Enclosures
 Additional alarms and shutdowns
 Industrial silencer
For further information on all of the standard and optional features
accompanying this product please contact your local Dealer or visit:
www.FGWilson.com

Dimensions and Weights

Length (L) Width (W) Height (H) Dry Wet


mm (in) mm (in) mm (in) kg (lb) kg (lb)

1870 (73.6) 840 (33.1) 1482 (58.3) 968 (2134) 981 (2163)

Dry = With Lube Oil Wet = With Lube Oil and Coolant

Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22.
Generator set pictured may include optional accessories.
Engine Technical Data Air Systems 50 Hz 60 Hz

No. of Cylinders / Alignment: 4 / In Line Air Filter Type: Replaceable Element


Cycle: 4 Stroke Combustion Air Flow: m³/min (cfm)

Bore / Stroke: mm (in) 108.0 (4.3) / 125.0 (4.9) - Prime - -


- Standby 5.5 (195) -
Induction: Turbocharged
Max. Combustion Air Intake
Restriction: kPa (in H2O) 5.0 (20.1) -
Cooling Method: Water
Governing Type: Electronic
Governing Class: ISO 8528 G2
Compression Ratio: 17:1
Cooling System 50 Hz 60 Hz
Displacement: l (cu. in) 4.6 (279.5)
Cooling System Capacity: l (US gal) 13.0 (3.4) -
Moment of Inertia: kg m² (lb/in²) -
Water Pump Type: Centrifugal
Engine Electrical System:
Heat Rejected to Water & Lube Oil:
- Voltage / Ground 12/Negative
kW (Btu/min) - Prime - -
- Battery Charger Amps 65
- Standby - -
Weight: kg (lb) - Dry 490 (1080)
Heat Radiation to Room: Heat radiated from engine and alternator
- Wet 510 (1124) kW (Btu/min) - Prime - -
- Standby - -

Radiator Fan Load: kW (hp) 3.1 (4.2) -

Performance 50 Hz 60 Hz Radiator Cooling Airflow: m³/min (cfm) 156.0 (5509) -


External Restriction to
Engine Speed: rpm 1500 - 125 (0.5) -
Cooling Airflow: Pa (in H2O)
Gross Engine Power: kW (hp)
Designed to operate in ambient conditions up to 50°C (122°F).
- Prime 62.0 (83.0) - Contact your local FG Wilson Dealer for power ratings at specific site conditions.

- Standby 68.0 (91.0) -


BMEP: kPa (psi)

- Prime 1083.0 (157.1) - Lubrication System

- Standby 1188.0 (172.3) - Oil Filter Type: Spin-On, Full Flow


Total Oil Capacity: l (US gal) 14.0 (3.7)
Oil Pan: l (US gal) -
Oil Type: 15W-40 CF4

Fuel System Oil Cooling Method: Water

Fuel Filter Type: Spin On


Recommended Fuel: Class A2 Diesel or BSEN590
Fuel Consumption: l/hr (US gal/hr) Exhaust System 50 Hz 60 Hz
110% 100% 75% 50% Maximum Allowable Back Pressure: 6.0 (1.8) -
kPa (in Hg)
Prime Load Load Load Load
Exhaust Gas Flow: m³/min (cfm)
50 Hz 15.1 (4.0) 13.9 (3.7) 12.3 (3.2) 7.3 (1.9)
- Prime - -
60 Hz - - - -
- Standby 14.3 (504) -
Exhaust Gas Temperature: °C (°F)
100% 75% 50%
Standby Load Load Load - Prime - -

50 Hz 15.1 (4.0) 14.3 (3.8) 9.3 (2.5) - Standby - -

60 Hz - - -

(Based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869,
Class A2)
Alternator Physical Data Alternator Operating Data

Manufactured for FG Wilson by: Marelli Overspeed: rpm 2250


Model: MJB 200 MB4 Voltage Regulation: (Steady state) +/- 1.0%
No. of Bearings: 1 Wave Form NEMA = TIF: 50
Insulation Class: H Wave Form IEC = THF: 2.0%
Winding Pitch Code: 2/3 - M0 Total Harmonic content LL/LN: 2.0%
Suppression is in line with European
Wires: 12 Radio Interference: Standard EN55011
Ingress Protection Rating: IP23 Radiant Heat: kW (Btu/min)
Excitation System: SHUNT - 50 Hz 6.4 (364)
AVR Model: Mark V - 60 Hz -

Alternator
50 Hz 60 Hz
Performance Data:

Data Item 415/240V 400/230V 380/220V

Motor Starting
104 97 87
Capability* kVA

Short Circuit
- - -
Capacity %

Reactances: Per Unit


Xd 2.778 2.990 3.313
X'd 0.234 0.252 0.279
X"d 0.090 0.097 0.108

Reactances shown are applicable to prime ratings.


*Based on 30% voltage dip at 0.0 power factor and SHUNT excitation.

Output Ratings Technical Data 50 Hz Output Ratings Technical Data 60 Hz


Voltage Prime: Standby: Voltage Prime: Standby:
kVA kW kVA kW kVA kW kVA kW
415/240V 65.0 52.0 72.0 57.6

400/230V 65.0 52.0 72.0 57.6

380/220V 65.0 52.0 72.0 57.6


General Information

Documentation

A full set of operation and maintenance manuals and circuit wiring diagrams.

Generator Set Standards

The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22.

FG Wilson is a fully accredited ISO 9001 company.

Warranty

All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's

warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com.

Dealer contact details:

FG Wilson manufactures product in the following locations:


Northern Ireland • Brazil • China • India • USA
With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network.
To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com.
FG Wilson is a trading name of Caterpillar (NI) Limited.
In line with our policy of continuous product development, we reserve the right to change specification without notice. F72-1 /0614/GB

You might also like