Technical Application Guide: Lighting Control
Technical Application Guide: Lighting Control
Wireless Occupancy
Sensor, Wireless Multi
Sensor
Technical
Application Guide
Easily enhance your smart lighting system with the Philips wireless occupancy
sensor and multi sensor, which are Interact Ready. They trigger automatic
responses to turn on, off or dim the lights according to occupancy detection
and daylight variation. The 2.4GHz mesh networking technology offers reliable
and secure communication within the space and further towards the Interact
IoT platform. The result? Greater energy saving, more control possibilities and
a more adaptable space!
Product Features
Installation Reliability
• Battery-powered, no mains wire required. • Reliable operation between -5°C and +45°C
• Quick and easy mounting with tapes or screws. ambient temperature.
• Walk test mode available for optimal detection. • Battery lifetime above 8 years. Minimum
• Indoor use only. maintenance. [ 2 ]
• IP42 (IEC standard 60529)
Environment
• No Mercury. [1]: For multi sensor only.
[2]: As calculated in typical conference room application.
• Low Carbon Footprint.
Application
Hospitals Offices
2
Field-of-View
• Field-of-view (FOV) for motion detection is determined at typical height (h=2.5m) for major and
minor motion with NEMA tests, respectively. Daylight FOV is for multi sensor only.
Motion FOV
Sensor
h = 2.5 - 4 m
(8.20 - 13.12 ft)
Daylight FOV
min. 0.7 x h
h = max. 4 m/13.12 ft
1.4 x h lux
1.4 x h
• Motion FOV can be reduced using the plastic shield around the lens.
3
Installation Instructions
×2 Instructions
+
1 × AA 3.6V
2 3
FOV indicator
4
• A walk test will help to determine the optimal location to place the sensor by quickly testing the
occupancy detection coverage. It's ONLY possible after sensor has been commissioned.
Walk test
• If needed, the sensitivity for motion detection can be adjusted with the dial at the back.
Three sensitivity levels are available from Low, Medium to High (High as default).
Sensitivity
L: low
M: medium
H: high
• Performing factory reset will restore sensor to un-commissioned status. Sensor will be removed
from current network (if any). To remove the device from certain system, it's sometimes also
required to delete it from app. Please refer to system guide when necessary.
Sensor will automatically enter commissioning mode after factory reset.
Factory reset
x 4 sec
5
Sensor Placement Guideline
• Sensors should not be exposed to direct sunlight, material with high reflection factor (e.g. aluminum
shade) or heating/cooling sources.
• The field of view (FOV) of the sensor shall not be obstructed, e.g. ceiling fans or luminaries.
• Multi sensor should be positioned to detect both artificial light and sunlight.
• Position the sensor to cover the majority of space for detecting all large movements, in particular near
the entry points. Small movements should be detected where occupants tend to move less. Multiple
sensors may be needed for larger spaces for full motion detection coverage.
• Motion in adjacent areas shall not be detected to avoid false triggering of the lights. The plastic shield
near the lens can be used to limit the motion FOV.
• It’s recommended to place only one multi sensor per daylight zone for optimal regulation. A daylight
zone can be created for each partitioned space where daylight condition is relatively uniform, and the
multi sensor only needs to sample the lux level within a small area. When the daylight condition varies
dramatically across the area, it’s recommended to create two or more daylight zones and consequently
more multi sensors are needed.
• Do not install the sensor on the ceiling until it has been programmed and fully tested.
• Important: Please refer to the system guide for any system related instructions.
LED indicator
LED pattern
Green LED blinks every 10s Ready for commissioning
Dimensions
ø 86.5 mm(3.41 in)
(1.18 in)
29.9 mm
(1.04 in)
26.4 mm
Temperature
6
Technical Specs and Order Information
Product Product Description Type Mounting Motion Battery RF Daylight
number height FOV at lifetime range level
10NC h=2.5m open-air
(m) ( sqm ) ( yr ) (m) ( lux )
Occupancy, 5.4 x 7.2 (major)
9290018190 OCC SENSOR IA CM WH ceiling mounted <=4 3.6 x 5.4 (minor) >8 15 --
Philips wireless occupancy sensor and multi sensor follow applicable legislation and standard.
The product complies with UL, cUL and CE.
Application Notes
• Product is battery operated. Use only the specified battery type (3.6V AA). Misuse of battery may cause
risk of fire or damage the device.
• Designed for indoor use only. DO NOT use in applications with high levels of condensation.
• Reliable operation between -5 °C to +45 °C ambient temperature.
• Modifications to the product void the limited warranty. For warranty information, please see
www.philips.com/lighting.
• You are required to read and understand the Quick Installation Guide and all warnings, cautions and
other materials related to installation before commencing installation work.
12/2020
www.philips.com/lighting