MV Panel Hipot Testing

The document summarizes the results of hipot and IR testing performed on 11kV switchgears. The test voltage was 18kV and measurements were taken for 60 seconds. Hipot test results showed very low currents, ranging from 2.4 to 20 microamps, flowing between different phases and earth grounds of each incomer. Resistance values were in the gigohm and teraohm range, indicating satisfactory insulation levels. Both the Siemens and client representatives signed off on the results.

Uploaded by

Fareh Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views1 page

MV Panel Hipot Testing

The document summarizes the results of hipot and IR testing performed on 11kV switchgears. The test voltage was 18kV and measurements were taken for 60 seconds. Hipot test results showed very low currents, ranging from 2.4 to 20 microamps, flowing between different phases and earth grounds of each incomer. Resistance values were in the gigohm and teraohm range, indicating satisfactory insulation levels. Both the Siemens and client representatives signed off on the results.

Uploaded by

Fareh Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

MV PANEL HIPOT AND IR TESTING

Customer: Karachi Export Processing Zone Test performed on: 30 May


2021

Plant section / Identification: 11kV Switchgears

Test Voltage : 18kV


System Voltage : 11kV
Test Time per Measurement : 60sec

HI POT TEST

R-Y Y-B R-B R-E Y-E B-E

Incomer 1 4uA / 7uA / 770 6uA / 1.02 6uA / 7uA / 1.78 10uA /
1.14TΩ GΩ TΩ 2.01TΩ TΩ 1.01TΩ

Incomer 2 5uA / 9uA / 19uA / 7uA / 10uA / 7uA /


1.01TΩ 1.11TΩ 650GΩ 700GΩ 530GΩ 1.00TΩ

Incomer 3 7.2uA / 20uA / 2.4uA / 2.4uA / 3.6uA / 9.6uA /


780 GΩ 330 GΩ 800 GΩ 1.14TΩ 1.13TΩ 800 GΩ

Incomer 4 10uA / 10uA / 4.6uA / 3.8uA / 80uA / 10uA /


905 GΩ 889 GΩ 1.16TΩ 1.26TΩ 200 GΩ 670 GΩ

Remarks

1- All incomers were tested in “Close Position” with Busbar included of outgoing panel.

2- Results found satisfactory.

______________________ ______________________
Siemens Representative Client’s Representative
Name: Name: