Module 6
Module 6
is called an impedance or
distance relay and, in the
complex impedance plane, has
the operating characteristic
shown.
By selecting IZ’I to be equal
IZrI, the relay characteristic
can be made to pass through
the origin, as illustrated in the
figure. Such a relay is
obviously directional and is
called a mho relay.
The operation of a differential
relay may be understood by
referring to the given figure.
Under normal conditions we
have I1 – I2 = 0. Under fault
conditions, I1 – I2 = IF, where IF
is the fault current referred to
the secondary of the CTs.
If a current IIPI < IIFI is chosen to
cause relay operation, then the
relay’s operating constraints are
Assuming again unity transformation ratio, if the fault current on the secondary
side is 3I, only 2I current will be supplied by the primary (isolated star point).
This type of connection of secondary is known as zero sequence current
generator.
Transformer star-star grounded CT delta connected
protection.
It is seen from the figure that when CTs are delta connected,
for an external fault, the relays do not operate.
Star-star grounded, internal fault.
https://www.servonics.com/PowerTransducerCatalog.pdf
https://www.elprocus.com/different-types-of-relays-used-
in-protection-system-and-their-workings