SD3U ON Error: DI120 150 DI180 420 Run CPU Speed CPU

The document discusses an ON error related to the SD3U device not operating properly at the bottom floor of a building. Specifically: 1. SD3U is meant to operate at all floors except the bottom floor to prevent potential clash accidents from forced reduction not working. 2. Steps to troubleshoot the issue include checking wiring and input buffer voltage, as well as ensuring the LIMIT S/W CAM is not bent. 3. Diagrams of the hardware skeleton and switch layout are provided for reference in troubleshooting.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views

SD3U ON Error: DI120 150 DI180 420 Run CPU Speed CPU

The document discusses an ON error related to the SD3U device not operating properly at the bottom floor of a building. Specifically: 1. SD3U is meant to operate at all floors except the bottom floor to prevent potential clash accidents from forced reduction not working. 2. Steps to troubleshoot the issue include checking wiring and input buffer voltage, as well as ensuring the LIMIT S/W CAM is not bent. 3. Diagrams of the hardware skeleton and switch layout are provided for reference in troubleshooting.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Point of ● Run CPU ○ DI120~150

TCD - 109 SD3U ON Error Application


Detection ○ Speed CPU ● DI180~420

[Meaning] SD3U does not operate at the bottom floor. [Actions to take]
※ To prevent any possible clash accidents caused by forced reduction
function not working at bottom floor on account of any ON errors such 1. Check wiring network for LIMIT S/W
as SD3U deposition, etc. - Check for bad connection of MIC and signal voltage

[Diagram] << S/W SKELETON >> 2. Check the operation of input buffer
ERR_EEPROM_FHT_SUMERR_NVRAM_FHT_SUM Err_Digital_Floor FAST_RUN_COMMAND
- Verify if voltage changes from 48V to 0V at the operation of SD3U.
- Check the address value from NVRAM READ MODE of Ann.
(Refer to H/W SKELETON)
(Normally, 0xFF should be changed into x00 at the operation of
POWER_READY_T ZONE_135MM LDC IS_CDS D1 IS_SD3U(ADDR:0x5011))
S - For 180 or more m/min, refer to H/W SKELETON drawing (3X02228
I/O C.[2])
D1 *Logical_Current_Floor =1 Equ_Sds_Tot_No & SDS3 BIT OR(SD3U) tmp_TXSDSR
check_off_history(XSD3U) = TRUE
3. Check any bend of LIMIT S/W CAM
tmp_TXSDR = TXSDSR tmp_TXSDR & SD3U - Visually check LIMIT S/W CAM for any bend
TCD 109 - Verify if roller does not deviate from the CAM when cage is
fluctuated right and left within car.
tmp_TXSDR
tmp_TXSDR
TXSDSR

<< H/W SKELETON >>


P48C ABOVE 180m/min OR BELOW 105m/min GD48
LSU-06 RCA-12 RCA-12
Y6-03

LSU-05 SD1U Y6-02 INB-05 DOR-200 IS_SD1U


INB-05 5005
ABOVE 180m/min OR BELOW 105m/min
LSU-08 RCA-14 RCA-14

LSU-07 SD2U Y6-03 INB-06 DOR-200 IS_SD2U


INB-06 5010

SD3U Y6-04 INB-07 DOR-200 IS_SD3U


5011
INB-07
ABOVE 180m/min OR BELOW 105m/min
LSD-06 RCA-13 RCA-13

LSD-05 SD1D Y6-05 INB-08 DOR-200 IS_SD1D


5007
ABOVE 180m/min OR BELOW 105m/min INB-08
LSD-08 RCA-15 RCA-15

LSD-07 SD2D Y6-06 INB-09 DOR-200 IS_SD2D


INB-09 5008

SD3D Y6-07 INB-10 DOR-200 IS_SD3D


INB-10 5009