IJERT A Review On Switchgear Analysis An
IJERT A Review On Switchgear Analysis An
Abstract— The digitization of manufactured goods has now components in a switchgear assembly: control components
become a phenomenon with the implementation of new sensor that conduct or disrupt the stream of electrical power, such as
technology and the growth of IoT instruments. People with switches, circuit breakers, fuses, and lightning, control
large, exorbitant machinery would like to keep a record of the systems for monitoring, controlling, and safeguarding of
assets' critical parameters. As a result, medium voltage
equipment, mainly switchgear diagnostics has become incredibly
power driving elements, such as control panels, current
valuable. On-site analyses and monitoring of circuit breaker transformers, future transformers, protection relays, and
drives, contacts, gas quality, gas density, and partial discharges related circuits. Security, which is the disruption of short-
could be achieved with varying degrees of tolerance and circuiting and overload fault currents while sustaining
operational efficiency. They are mounted in substations to operation to unaffected circuits Gts, is one of the most basic
supply energy to cities from electrical networks from overhead features of switchgear. Alienation of circuits from power
power lines or underground cables. Safety and efficiency are supplies is also provided by switchgear. Switchgear can also
major concerns in this equipment due to the high voltage and improve system availability by allowing several sources to
current flow. Thus, various types of sensors are used in the feed a load. Gas-insulated switchgear saves space compared
system to keep track of the system’s performance. This paper
presents a detailed examination of the Switchgear Study, its
with air-insulated equipment, although the equipment cost is
implementations, and the challenges observed. higher. An effective although more costly form of switchgear
is the gas-insulated As compared to air-insulated switchgear,
Keywords— Medium Voltage Switchgears, Gas Insulated gas-insulated switchgear takes up less room, but the cost of
Switchgear, IoT, Safety methods, Operational Efficiency, System the equipment is higher, pressurized sulfur hexafluoride
Performance. gas(SF6) is used to insulate conductors and contacts in
I. INTRODUCTION switchgear (GIS)[2]. The switchgear enclosure's mix of
devices allows them to interrupt fault currents of thousands of
Switchgears predate the invention of electricity. The volts. The primary component that interrupts fault currents is
first versions were very basic, with all elements directly a circuit breaker (located inside a switchgear enclosure).
attached to a wall. They were then installed on wood frames. When the circuit breaker breaks apart the contacts
The wood was substituted with slate or marble for fire safety (disconnects the circuit), the arc must be quenched with
purposes. Since the switching and measurement instruments caution. Gas (SF6) circuit breakers use a magnetic field to
could be connected to the front while the wire was on the extend the arc and then concentrate on the SF6 gas's dielectric
rear, this resulted in further modifications. The simplest type power to quench the extended arc. Since there is little to
of switchgear is a tumbler switch with an ordinary fuse, ionize other than the contact medium in circuit breakers with
which was used to operate and secure lights and other vacuum interrupters, the arc quenches as it is extended by a
appliances in houses, workplaces, and other places. A high- tiny distance (about 2–8 mm)[3]. The arc isn't hot enough to
rupturing capacity (H.R.C.) fuse and a switch can be used to hold a plasma at zero current, so the current stops; the void
control and secure higher-rated circuits. Moreover, on a will then tolerate the voltage spike. Current medium-voltage
high-voltage grid, though, such switchgear is unprofitable. switchgear up to 40,500 volts commonly uses vacuum circuit
Switchgear is made up of electrical disconnect switches, breakers. Since there is no "current zero" time for DC,
fuses, and circuit breakers that are used to operate, secure, vacuum circuit breakers are unsuitable for breaking high DC
and separate electrical devices in an electric power system. voltages. The plasma arc can be fed on its own by starting to
Switchgear is used to de-energize machinery so that it can gasify the contact material[4]. Today, the Medium voltage
perform maintenance operations on it, as well as to clear GIS mostly uses SF6, due to their efficient isolation and
faults downstream[1]. The efficiency of the power supply is thermal properties, as the insulation and the break-down
directly associated with this type of equipment. Arc energy medium. While SF6 has excellent properties, it also
can be stored and securely handled with oil-filled switchgear. represents the world's most dangerous greenhouse gas. Each
By the early twentieth century, it was almost clear that a year, only SF6 pollution led to a huge 0.5% of global
switchgear line-up would be a metal-enclosed structure with warming. Due to the extreme greenhouse effects of SF6, an
electrically operated switching components and oil circuit alternative approach to SF6 in switchgear is required.[5]
breakers. Today, air-blast, vacuum or SF6 equipment has
effectively replaced oil-filled equipment today, allowing
broad currents and input voltages to be safely controlled by
automatic equipment. There are two categories of
new modular solution for online condition monitoring should [8] Ji, Tong & Xie, Wei & Wang, Xiaoqing & Zhang, Jinbo. (2017). The
research of high voltage switchgear detecting unit. IOP Conference
be introduced in order to implement condition-based
Series: Materials Science and Engineering. 222. 012021. 10.1088/1757-
maintenance for medium voltage (MV) switchgear and 899X/222/1/012021.
breakers. [15]. The solution can predict potential failures [9] Djekic, Z.: ‘Online circuit breaker monitoring system’. Master thesis,
allowing maintenance schedule in advance by applying University of Novi Sad, Serbia, December 2007.
dedicated sensing technologies. Circuit breaker failure modes [10] Goh, Hui Hwang & Sim, Sy & Hamzah, Nur & Mazlan, Sulaiman &
regard, for instance, open and close commands malfunction, Ling, Chin & Chua, Qing & Goh, Kai Chen. (2017). Types of Circuit
charging mechanism malfunction, current interruption issues Breaker and its Application in Substation Protection. Indonesian
(contact wear), overheating, and overall health index of the Journal of Electrical Engineering and Computer Science. 8. 213-220.
10.11591/ijeecs.v8.i1.pp213-220
monitored equipment should be calculated. The arc flash
[11] Yu, Zhanqing. (2018). Temperature Rise Test and Analysis of High
threat is related to electrical safety at the workplace and has Current Switchgear in Distribution System. The Journal of
received a great deal of attention as part of the safety Engineering. 2019. 10.1049/joe.2018.8371
programme for many installations[16]. An effective approach [12] Y. Nakano, M. Kozako, M. Hikita, T. Tanaka and M. Kobayashi,
to the reduction of arc flash hazards in existing industrial and "Estimation of Internal Pressure of Vacuum Interrupter by Measuring
commercial facilities is a very important objective. Failure of Partial Discharge Current," 2018 28th International Symposium on
Discharges and Electrical Insulation in Vacuum (ISDEIV), Greifswald,
electrical equipment is usually accompanied by abnormal 2018, pp. 611-614, doi: 10.1109/DEIV.2018.8537045.
temperature changes[17]. Therefore, the temperature [13] “Methods for Arc-Flash Prediction in Medium Voltage and Low
monitoring of power equipment is the most effective and Voltage Switchgear” Ghulam Amjad Hussain ,Aalto University
economical way of power equipment safety monitoring, publication series DOCTORAL DISSERTATIONS 221/2015.
which is of great significance to the safe operation of power [14] “Switchgear Condition Monitoring” M. Budyn , H. M. Karandikar , M.
equipment. This further leads us to management of the net- G. Urmson ABB Corporate Research1 (PL), ABB Inc.2,3 (USA)
CIGRÉ Canada 21, rued#39; Artois, F-75008 PARIS CIGRE-115
pressure inside the switchgear to avoid any over pressure Conference on Power Systems http : //www.cigre.org Vancouver,
which may lead to serious hazards, thus this should be October 17- 19, 2010..
maintained using affordable developed technologies where [15] “Modular online monitoring system to allow condition-based
we can constantly monitor the system health of the maintenance for medium voltage switchgear” Kevin Perdon 1,
switchgear and its components using online monitoring Massimo Scarpellini 2, Stefano Magoni 3, Luca Cavalli 4 ABB S.p.A.,
Via Friuli4, 24044 Dalmine (BG), Italy, 24th International Conference
systems. & Exhibition on Electricity Distribution (CIRED) 12-15 June
2017.
ACKNOWLEDGMENT [16] A. M. Graham and M. Hodder, “Current methods for conducting an arc
flash hazard analysis,” Conference Record of the 2004 IEEE Industry
We would like to thank our project guide and faculty
Applications Conference, 2004. 39th IAS Annual Meeting., Seattle,
Senior Assistant Professor Chennakeshava R for providing us WA, USA, 2004, pp. 1741-1748 vol.3, doi:
with the resources and knowledge to conduct the 10.1109/IAS.2004.1348706. Osaka, Japan, 2020, pp. 130-134, doi:
experiments. 10.1109/ICCRE49379.2020.9096479.
[17] “An Effective Approach to Reducing Arc Flash Hazards in Power
REFERENCES Systems” Xiaodong Liang, Senior Member, IEEE, Bagen Bagen,
Senior Member, IEEE, and David Wenzhong Gao, Senior Member,
[1] K. Matsushita, Y. Matsuura, T. Funabashi, N. Takeuchi, T. Kai and M.
IEEE.
Oobe, "Study for the performance of high speed switchgear for
protection of in-house generation system," Proceedings of 1996 IAS
Industrial and Commercial Power Systems Technical Conference, New
Orleans, LA, USA, 1996, pp. 91-95, doi: 10.1109/ICPS.1996.533941.
[2] Bolin, Phil & Koch, Hermann. (2008). Gas insulated substation GIS. 1
- 3. 10.1109/TDC.2008.4517307.
[3] Saurabh Saxena Maroof Ali Alok Singh Kapil Gandhi, “Various
Types of Circuit Breakers used in Power System for Smooth Working
of the Transmission Line,” MIT International Journal of
Electrical and Instrumentation Engineering, Vol. 2, No. 2, Aug. 2012,
pp. (106-111) [4] S. Tokoyoda, T. Inagaki, K. Tahata, F. Page, K.
Kamei, T. Minagawa
[4] IEEE Transactions on components, packaging and manufacturing
technology —PART A, VOL. 21, NO. 1, MARCH 1998 33 “Arc
Motion and Pressure Formation in Low Voltage Switchgear” ,Manfred
Lindmayer and Joachim Paulke.
[5] Preve, Christophe & Lahaye, Gérard & Richaud, Myriam & Maladen,
Romain & Penelon, Thibauld & Galas, Simon. (2017). Hazard study of
medium-voltage switchgear with SF6 alternative gas in electrical room.
CIRED - Open Access Proceedings Journal. 2017. 198-201.
10.1049/oap-cired.2017.0385.
[6] Wang, Jingqin & Wang, Li & Zhang, Guangzhi & Chi, Changchun.
(2019). Study on prior information fusion method of low-voltage
switchgear. Advances in Mechanical Engineering. 11.
168781401982667. 10.1177/1687814019826674.
[7] Ma, Canpeng & Moesch, Gilles & Cabaret, Bertrand & Tobias, J..
(2012). Innovative MV switchgear for today's applications. 1-4.
10.1109/CICED.2012.6508711.