Load Calc - Pipe Supports

This document provides calculations for wind loads on structures based on the ultimate wind speed of 120 miles/hr and exposure category C. It gives formulas to calculate the wind design force based on importance factor, velocity pressure, and shape coefficients. Wind loads are calculated for structural shapes, pipes, and a flare line up to a span of 80 feet. It also provides calculations for dead and live loads on the structure and pipes based on their weights and friction loads.

Uploaded by

sridhar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
159 views3 pages

Load Calc - Pipe Supports

This document provides calculations for wind loads on structures based on the ultimate wind speed of 120 miles/hr and exposure category C. It gives formulas to calculate the wind design force based on importance factor, velocity pressure, and shape coefficients. Wind loads are calculated for structural shapes, pipes, and a flare line up to a span of 80 feet. It also provides calculations for dead and live loads on the structure and pipes based on their weights and friction loads.

Uploaded by

sridhar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

WIND LOAD CALCULATIONS (MPS)

* IMPORTANCE FACTOR, I =
* NORMAL STRUCTURES: I = 1.0

* BASIC ULTIMATE WIND SPEED (3-SEC GUST) 120 miles/hr


* EXPOSURE CATEGORY = C (Open Terrain)
* Kzt = 1.0 UNLESS STRUCTURE LOCATED ON HILL OR ESCARPMENT
* qz = 0.00256 * Kz * Kzt * V2 * I (psf)
* WIND DESIGN FORCE = qz * Kd * G * Cf * Af
I 1
Kzt 1
Vz 120 MPH
Kz 0.9 upto 20'
Kz 0.98 20'-40'
Kz 1.09 40'-60'
Kz 1.21 60'-80'

qz 33.18 psf upto 20'


qz 36.13 psf 20'-40'
qz 40.18 psf 40'-60'
qz 44.61 psf 60'-80'

For Structural Shapes:


F qz x Kd x G x Cf x Af
G 0.85 Gust Factor
Cf 2 Shape factor
Kd 0.85 Directionality factor
G*Cf*Kd 1.45
Af L*W
Assume the width as (W10) 0.833 ft (conservatively)
Wind Load on the structure F 39.951 lbs/ft
Wind Load on the column:
Wind Load on the column 39.951 lbs/ft
Wind load on the longitudinal beam 39.951 lbs/ft
Span of the longitudinal beam 20 ft
Wind load on column due to Long beam 0.80 kips

For Pipes:
F qz x Kd x G x Cf x Af
G 0.85 Gust Factor
Cf 0.7 Shape factor
Kd 0.85 Directionality factor
G*Cf*Kd 0.51
Max dia of the pipe 0.833 ft (conservatively)
Span of the pipe 20.000 ft
Wind Load on the coumns due to pipe 0.28 lbs

DOW RESTRICTED
Dia of the flare line 1.500 ft (conservatively, including insulation)
Span of the pipe 20.000 ft
Wind Load on the coumns due to pipe 0.50 lbs

DOW RESTRICTED
DL & LL Calculation:
Self weight of the structure It's assigned in RISA separately
Total weight of the pipes 40 psf
Consider 50% of that under DL & remaining under LL
20 psf
Span of the pipes 20 ft
DL due to the pipes 0.4 lbs/ft
LL due to the pipes 0.4 lbs/ft
Friction on beams due to pipe loads 10% of the pipe load
4 psf
Friction on beams due to pipe loads 0.08 lbs/ft
Friction loads is considered as LL

Flare line: Dia of flare line 14 in


Consider it as SCH80 dia pipe
Weight of SCH80 dia pipe with insulation 120 lbs/ft
Span of the pipe 20 ft
Load from the SCH80 pipe 2.4 kip
Consider it's full of water 110 pcu
Area of pipe 1.07 sq.ft
117.59 lbs/ft
Span of the pipe 20
Live load on the pipe 2.35 kip
Friction on beams due to flare pipe 0.48 kip (10% of pipe load)
Friction loads is considered as LL

DOW RESTRICTED