Fault Calculation
Fault Calculation
Base kV = 6.6 kV
Base kA = 6.123 kA
ST Min % imp inclusive of Tol at Min Tap ST Min % imp inclusive of Tol at Nor Tap
% %
Impedance Tolerance In P.U Impedance Tolerance
Zh -0.0244 -0.0657
Zl1 0.2093 0.2477
Zl2 0.4356 0.3972
Max. S/C current interruption contribution from 11kV board OBA = 1.94
S/C MVA at 11 kV = 37.04
Fault impedance at 70 MVA base & 6.6kV base = 5.2499
= 14.80 18.36
%
In P.U Impedance Tolerance In P.U
-0.0913
0.2791
0.3657
kA
MVA
P.U.
at maximum tap of ST
0.2758
3.6262
22.21
24.43
62.29
Station bus OBA fed from Station transformer 5A
Base kV = 11 kV
Base kA = 3.674 kA
ST Min % imp inclusive of Tol at Min Tap ST Min % imp inclusive of Tol at Nor Tap
% %
Impedance Tolerance In P.U Impedance Tolerance
Zh -0.0244 -0.0657
Zl1 0.2093 0.2477
Zl2 0.4356 0.3972
Board Contribution
5CA 5.03
5CB 4.07
OCA 0.04
OCB 0.04
OCC-A 0.57
OCC-B 0.29
Max. S/C current interruption contribution from 6.6kV board OCA = 10.04
S/C MVA at 6.6 kV = 114.73
Fault impedance at 70 MVA base & 6.6kV base = 0.2196
= 19.65 20.69
Board Contribution
OCA 0.04
Max. S/C current interruption contribution from 6.6kV board OCA = 0.04
S/C MVA at 6.6 kV = 0.44
Fault impedance at 70 MVA base & 6.6kV base = 56.76
= 19.58 19.90
%
In P.U Impedance Tolerance In P.U
-0.0913
0.2791
0.3657
kA
MVA
P.U.
at maximum tap of ST
0.1749
5.7183
21.01
23.11
58.93
kA
MVA
P.U.
at maximum tap of ST
0.1905
5.2492
19.29
21.21
54.10
Fault contribution from 6.6kV motors on board 5CA
I. Momentary consideration
= 21.41 kA peak
Peak value during HP/LP bypass condition, 2 mill motors are not working, therefore
= 20.48 kA
RMS value during HP/LP bypass condition, 2 mill motors are not working, therefore
= 5.03 kA
Fault level calculations 5CA/5CB
UAT Impedance
= 25.26 24.97
% Tol
% Tol
0.0915
10.9285
23.90
26.29
67.04
kA rms
kA peak
Fault contribution from 6.6kV motors on board 5CB
I. Momentary consideration
= 17.90 kA peak
Peak value during HP/LP bypass condition, 3 mill motors are not working, therefore
= 16.97 kA
RMS value during HP/LP bypass condition, 3 mill motors are not working, therefore
= 4.07 kA
Fault contribution from 6.6kV motors on board OCC Sec-A
I. Momentary consideration
= 3.64 kA peak
I. Momentary consideration
= 1.86 kA peak
I. Momentary consideration
= 0.25 kA peak
I. Momentary consideration
= 0.25 kA peak
I. Momentary consideration
= 7.44 kA peak
I. Momentary consideration
= 7.44 kA peak
B Unit running at 100% MCR, one UAT out of service,one unit swbd fed from ST
B Unit running at 100% MCR, both UATs healthy, ST-5B not available
B Unit running at 100% MCR, both UATs healthy, ST-5A not available
ors connected to bus 5CA, OCA & OCC with interruption consideration
ors connected to bus 5CA, OCA & OCC with momentary consideration
ors connected to bus OCA, OCB & OCC with momentary consideration
ors connected to bus 5CA, 5CB, OCA, OCB & OCC with interruption consideration
ors connected to bus 5CA, 5CB, OCA, OCB & OCC with momentary consideration
ors connected to bus 5CB, OCB & OCC with interruption consideration
ors connected to bus 5CB, OCA & OCC with momentary consideration
ors connected to bus OCA, OCB & OCC with momentary consideration
ors connected to bus 5CA, 5CB, OCA, OCB & OCC with interruption consideration
ors connected to bus 5CA, 5CB, OCA, OCB & OCC with momentary consideration