Chapter 4 Maintenance Part 1 Failure Code Table 1 System Failure Code Table
Chapter 4 Maintenance Part 1 Failure Code Table 1 System Failure Code Table
Chapter 4 Maintenance
Part 1 Failure Code Table
1 System Failure Code Table
Inquiry method of malfunction display: combine division number and content number to check the
corresponding malfunction.
Indoor:
Error Code Content Error Code Content
Malfunction of lower water temperature
L0 Malfunction of IDU d2
sensor of water tank
Malfunction of ambient temperature
L1 Protection of indoor fan d3
sensor
Malfunction of entry-tube temperature
L2 Auxiliary heating protection d4
sensor
Malfunction of exit-tube temperature
L3 Water-full protection d6
sensor
Abnormal power supply for wired
L4 d7 Malfunction of humidity sensor
controller
L5 Freeze prevention protection d8 Malfunction of water temperature sensor
L7 No main IDU d9 Malfunction of jumper cap
L8 Power supply is insufficient dA Web address of IDU is abnormal
For single control over multiple units,
L9 dH PCB of wired controller is abnormal
number of IDU is inconsistent
For single control over multiple units, Setting capacity of DIP switch code is
LA dC
IDU series is inconsistent abnormal
Malfunction of air outlet temperature
LH Alarm due to bad air quality dL
sensor
LC IDU is not matching with outdoor unit dE Malfunction of indoor CO2 sensor
Malfunction of upper water temperature
LL Malfunction of water flow switch dF
sensor of water tank
Rotation speed of EC DC water pump is Malfunction of backwater temperature
LE dJ
abnormal sensor
Malfunction of inlet tube temperature
LF Malfunction of shunt valve setting dP
sensor of generator
Setting of functional DIP switch code is Malfunction of drainage pipe
LJ dU
wrong temperature sensor of generator
LP Zero-crossing malfunction of PG motor db Debugging status
Outdoor:
Error Code Content Error Code Content
Current sensor of compressor 1 is
E0 Malfunction of ODU FH
abnormal
Current sensor of compressor 2 is
E1 High-pressure protection FC
abnormal
Current sensor of compressor 3 is
E2 Discharge low-temperature protection FL
abnormal
Current sensor of compressor 4 is
E3 Low-pressure protection FE
abnormal
E4 High discharge temperature protection of FF Current sensor of compressor 5 is
122
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
123
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Debugging:
Error Code Content Error Code Content
Alarm because ODU quantity is
U0 Preheat time of compressor is insufficient C6
inconsistent
124
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Status:
Error Code Content Error Code Content
A0 Unit waiting for debugging Ay Shielding status
Refrigerant recovery operation of
A2 n0 SE operation setting of system
after-sales
A3 Defrosting n3 Compulsory defrosting
Limit setting for max. capacity/output
A4 Oil-return n4
capacity
Compulsory excursion of engineering
A6 Heat pump function setting n5
code of IDU
A7 Quiet mode setting n6 Inquiry of malfunction
A8 Vacuum pump mode n7 Inquiry of parameters
AH Heating n8 Inquiry of project code of IDU
AC Cooling n9 Check quantity of IDU on line
AL Charge refrigerant automatically nA Heat pump unit
AE Charge refrigerant manually nH Heating only unit
AF Fan nC Cooling only unit
AJ Cleaning reminding of filter nE Negative code
Debugging confirmation when starting up
AP nF Fan model
the unit
High temperature prevention when
AU Long-distance emergency stop nJ
heating
Eliminate the long-distance shielding
Ab Emergency stop of operation nU
command of IDU
Ad Limit operation nb Bar code inquiry
Length modification of connection pipe
An Child lock status nn
of ODU
Note: Previous faults in the system can be queried on the main board of the ODU and
commissioning software. See n6 Fault Enquiry of the ODU or enquiry function of the commissioning
software for the method.
125
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
126
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Fault
Fault Possible reasons Solution
code
compressor's drive board. If the fault is solved, the
compressor's drive board is faulty.
1)Check if the cable connecting the fan's drive
board and the compressor's drive board is loose. If
yes, reconnect it;
1.The communication cable is not 2)Check if the cable connecting the fan's drive
Communication connected. board and compressor's drive board is broken. If
failure between 2.The communicator is yes, replace the cable;
C3 main control board disconnected. 3)Check the contact of the communication cable
and variable 3.The communication cable is connecting the fan's drive board and compressor's
frequency fan drive poorly connected. drive board;
4.The communicator is faulty. 4)Replace the control board. If the fault is solved,
the control board is faulty. Replace the fan's drive
board. If the fault is solved, the fan's drive board is
faulty.
1. Check the number of online indoor units through
outdoor unit and compare it with the number of
indoor units that are actually installed. Confirm the
number of missing indoor units.
2. Check whether all the indoor units are
power-connected. If some are not, connect them
to power. If power connection is fine, check further
whether there is any indoor unit that fails to display
1.Some indoor units in the system
on wired controller or receiver board. If such
are not power-connected.
indoor unit exists, it means its main board is
2.Communication wires of some
abnormal and needs to be replaced. If everything
Malfunction of lack indoor units in the system are
C4 said above is confirmed OK, continue to check
of indoor unit disconnected or have loose
according to step 3.
contact.
3. The missing indoor units will display error C0
3.Controllers of some indoor units
on wired controller or receiver board. Check the
in the system are abnormal.
communication wire of the missing indoor unit
whether it is disconnected or has loose contact. If
yes, connect the communication wire tightly. If
communication wire is OK, check whether it is
connected reversely. Power on the indoor unit
again and see if error C0 occurs. If C0 is
displayed, it means main board is abnormal and
needs to be replaced.
Indoor unit project
1.Project numbers conflict with 1.Change conflicting project numbers and ensure
C5 number conflict
each other. that no IDU's project number is repeated.
warning
1.Communication cables between
ODUs are loose.
Outdoor unit 1.If the communication cable is loose, reconnect it;
2.Communication cables between
number 2.If the communication cable is broken, replace it;
C6 ODUs are broken.
inconsistency 3.Check contact of the communication cable;
3.Communication cables between
warning 4.Replace the control board.
ODUs are poorly connected.
4.The control board is faulty.
The SA8 dial switch of the ODU is
1.Switch the SA8 dial switch of an ODU to 00;
not switched to 00.
CC No controlling unit 2.Replace the control board or switch an ODU's
The SA8 dial switch of the ODU is
SA8 dial switch to 00.
faulty.
SA8 dial switches of multiple
1.Leave one SA8 dial switch unchanged, while
Multiple controlling ODUs are switched to 00.
CF switch all the other dial switches to 11;
units Dial switches of multiple ODUs
2.Replace the control board.
are faulty.
The master IDU is powered off. Check if the master IDU is powered on. If yes,
L7 No master IDU
The communication of the master replace the main board;
127
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
Fault
Fault Possible reasons Solution
code
IDU fails. Check the contact of the communication cable of
The main board of the master IDU the master IDU. If no communication failure (C0) is
is faulty. reported, replace the main board.
No master IDU is set in the Replace the IDU's main board and reset the
system. master IDU.
Set the master IDU.
Note: Solution of C5 fault when multiple cooling systems are controlled in a centralized way
When multiple cooling systems are controlled in a centralized way, the C5 fault, i.e. project number
conflict, may occur on different cooling systems. In such case, set project numbers of each system and
solve the fault as follows:
1) Project number conflict:
When multiple systems are controlled in a centralized way, if two or more IDUs share the same
project number, the engineer number conflict occurs. In that case, IDUs cannot be switched to varied
modes or be turned on or off. The whole device cannot be started before the conflict is solved. The
commissioning software will show the following page:
Figure 1
128