Three-Phase Overvoltage and Undervoltage Relay: 1MRS 750359-MBG Spau 130 C
Three-Phase Overvoltage and Undervoltage Relay: 1MRS 750359-MBG Spau 130 C
Features • Combined overvoltage and undervoltage • Flexible matching of the relay to the
protection relay intended protection application
• Three-phase definite time or inverse time • Numerical display of setting values, mea-
overvoltage stage sured values, recorded fault values, indica-
tions, etc.
• Three-phase definite time undervoltage
stage • Serial interface for bus connection module
and fibre-optic substation bus
• Control input for blocking the function of
the undervoltage stage by means of an • Continuous self-supervision of relay hard-
external control signal ware and software for enhanced system
reliability and availability
• Automatic blocking of the undervoltage
stage on loss of energizing voltage • Auto-diagnostic fault indication to facilitate
repair of an internal relay fault
• Fully field-configurable output relay func-
tions • Powerful software support for parameter-
ization and supervision of the relay
Application The three-phase voltage relay SPAU 130 C is The overvoltage stage can be given definite
intended to be used for overvoltage and time characteristic or inverse time character-
undervoltage protection and supervision in istic. The undervoltage stage features definite
distribution substations. The relay can also be time characteristic alone.
used for overvoltage and undervoltage pro-
tection of generators, motors and transform- An external control signal can be used to
ers. Generally, the relay measures the three block the operation of the undervoltage stage.
phase-to-phase voltages of the system, but it
can also be programmed for single-phase The relay forms a whole including overvolt-
measurement. age stage, undervoltage stage as well as flexi-
ble trip and alarm functions.
1
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
2
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
7DEOH2XWSXWFRQWDFWUDWLQJV
Type of contact Tripping Signalling
Terminals 65-66, 68-69 70-71-72, 77-78, 80-81
Rated voltage 250 V ac/dc
Thermal withstand Carry continuously 5A 5A
capability Make and carry for 0.5 s 30 A 10 A
Make and carry for 3 s 15 A 8A
Breaking capacity for dc, 220 V dc 1A 0.15 A
when the control/ 110 V dc 3A 0.25 A
signalling circuit time
48 V dc 5A 1A
constant L/R ≤ 40 ms, at
the control voltages
Contact material AgCdO2
7DEOH&RQWUROLQSXWFRPPXQLFDWLRQDQGSRZHUVXSSO\
External control input Terminals 10-11
Control voltage level 18…265 V dc or
80…265 V ac
Power consumption when input activated 2…20 mA
Data communication Transmission mode Fibre-optic serial bus
Data code ASCII
Selectable data transfer rates 300, 1200, 2400, 4800 or
9600 Bd
Fibre-optic bus for plastic fibre cables SPA-ZC 21BB
connection module, for glass fibre cables SPA-ZC 21MM
powered from the host
relay
Fibre-optic bus for plastic fibre cables SPA-ZC 17BB
connection module with for glass fibre cables SPA-ZC 17MM
a built-in power supply
unit
Auxiliary supply modules Power supply and I/O SPTU 240S1 80…265 V ac/dc
modules and voltage SPTU 48S1 18…80 V dc
ranges
Power consumption under quiescent ~4 W
conditions
under operating ~6 W
conditions
3
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
7DEOH7HVWVDQGVWDQGDUGV
Test voltages Dielectric test voltage (IEC 255-5) 2.0 kV, 50 Hz, 1 min
Impulse test voltage (IEC 255-5) 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance (IEC 255-5) >100 MΩ, 500 V dc
Interference tests High-frequency (1 MHz) 2.5 kV
disturbance test (IEC 255-22-1),
common mode
High-frequency (1 MHz) 1.0 kV
disturbance test (IEC 255-22-1),
differential mode
Fast transients (IEC 255-22-4, 4 kV, 5/50 ns
class III and IEC 801-4, level 4),
power supply inputs
Fast transients (IEC 255-22-4, 2 kV, 5/50 ns
class III and IEC 801-4, level 4),
other inputs
Electrostatic discharge 8 kV
(IEC 255-22-2 and IEC 801-2,
class III), air discharge
Electrostatic discharge 6 kV
(IEC 255-22-2 and IEC 801-2,
class III), contact discharge
Environmental conditions Service temperature range -10…+55°C
Transport and storage -40…+70°C
temperature range (IEC 68-2-8)
Damp heat test (IEC 68-2-3) <95%, +40°C, 96 h
Relative humidity (IEC 68-2-30) 93…95%, +55°C, 6 cycles
Degree of protection by enclosure IP 54
when panel mounted
Weight 3 kg
4
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
Block diagram L1
L2
L3
A Rx Tx
N
SPA-ZC_
n
a
+ (~)
Uaux
- (~)
100V
110V
100V
110V
100V
≅_
E D C B A
+ - U3 1 1 1 1
SGR/1
U3 SGR 3 2 4 7 5 8 6
IRF
SS1
t>,k> TS1
3U>
SGB/5 SS2
t< TS2
3U<
U1 I/O
SPAU 130 C U2
5
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
139 ±1
Panel cut-
136
162
out
dim100
Semi-flush mounting
a b
Raising frame a b
SFM100_1
SPA-ZX104 SPA-ZX110
SPA-ZX105 SPA-ZX115
SPA-ZX106
+0,4 158 263
482,6 –0 (19")
115
ø6
10
177 –0 (4U)
101,6
7
+0,4
312
292
21,5
6
115 98
104_6_10
Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm)
6
Three-phase overvoltage and SPAU 130 C
undervoltage relay 1MRS 750359-MBG
Ordering :KHQRUGHULQJSOHDVHVSHFLI\
Ordering information Ordering example
1. Type designation and quantity SPAU 130 C, 5 pieces
2. Order number RS 422 020-AA
3. Rated values Un = 110 V, fn = 50 Hz
4. Auxiliary voltage Uaux = 110 V dc
5. Accessories -
6. Special requirements -
2UGHUQXPEHUV
Three-phase overvoltage and undervoltage relay RS 422 020-AA, CA, DA, FA
SPAU 130 C without test adapter
Three-phase overvoltage and undervoltage relay RS 422 220-AA, CA, DA, FA
SPAU 130 C including test adapter RTXP 18
The last two letters of the order number indicate the AA equals fn = 50 Hz and Uaux = 80…265 V ac/dc
rated frequency fn and the auxiliary voltage Uaux of CA equals f = 50 Hz and U
n aux = 18…80 V dc
the relay as follows:
DA equals fn = 60 Hz and Uaux = 80…265 V ac/dc
FA equals fn = 60 Hz and Uaux = 18…80 V dc