This document provides information on the communication protocols for a flow computer used on the GLCC MPFM for Belida Extension Project. It details the data points that will be read from ultrasonic and coriolis flow meters via Modbus, and the data that will be communicated to the ICSS-PLC/HMI via Ethernet/IP. 44 data points including flow rates, densities, temperatures and diagnostic information will be available at specified addresses for read and write functions.
This document provides information on the communication protocols for a flow computer used on the GLCC MPFM for Belida Extension Project. It details the data points that will be read from ultrasonic and coriolis flow meters via Modbus, and the data that will be communicated to the ICSS-PLC/HMI via Ethernet/IP. 44 data points including flow rates, densities, temperatures and diagnostic information will be available at specified addresses for read and write functions.
Ultrasonic Flow Meter Modbus ID = 1 Baud Rate = 9600, Stop Bit = 1, Data Bit = 8, Parity = None No Modbus Description Unit Data Type R/W 1 30000 Gas Actual Volumetric Flowrate ACFD Float R 2 30004 Mas Flowrate lb/day Float R 3 30006 Molar Mass - Float R 4 30010 Gas Velocity ft/sec Float R 5 30012 Velocity of sound ft/sec Float R 6 30014 Gain 1 Float R 7 30016 Gain 2 Float R 8 30018 Gain 3 Float R 9 30020 Gain 4 Float R
Read Data From Coriolis Flow Meter
Coriolis Flow Meter Modbus ID = 2 Baud Rate = 9600, Stop Bit = 1, Data Bit = 8, Parity = None No Modbus Description Unit Data Type R/W 1 20247 Liquid Mass Flowrate lb/Day Float R 2 20249 Liquid Density lb/ft3 Float R 3 20251 Liquid Temperature degF Float R 4 20253 Liquid Volumetric Flowrate BBL/Day Float R 5 20259 Mass flow Totalizer lbs Float R 6 20261 Volumetric Totalizer BBL Float R 7 20291 Diagnostic : Drive Gain % Float R
Communication With ICSS - PLC/HMI
Protocol : Ethernet / IP - Allen Bradley Speed : 100 Mbit/s, Auto-negotiate, Full Duplex Address No Description Unit Data Type R/W (Note 1) 1 TBA Well No Integer R 2 TBA Test Duration Minute Integer R 3 TBA Purging Volume BBL Float R 4 TBA Operator ID Integer R 5 TBA Well Test Start Command 0=Off; 1=Start Boolean R 6 TBA Stop Command 0=Off;1=Stop Boolean R 7 TBA Water Standard Density lb/ft3 Float R 8 TBA Oil Standard Density lb/ft3 Float R 0=Stby; 9 TBA Well Test Status 1=Purge; Integer W 2=Test 10 TBA Real Time Clock Float W 11 TBA Purging Start Time Stamp Float W Flow Computer LIST Data Communication Doc.No. 345-1709-IN-LI-003 Protocol MPFM-1709
13 TBA Well Test Start Time Stamp Float W 14 TBA Well Test Stop Time Stamp Float W 15 TBA Purging Elapsed Time Float W 16 TBA Well Test Elapsed Time Float W 17 TBA Operating Pressure Psig Float W 18 TBA Operating Temperature degF Float W 19 TBA Gas Volumetric Flow Rate - Actual ACFD Float W 20 TBA Gas Volumetric Flow Rate - Standard MMSCFD Float W 21 TBA Gas Velocity ft/sec Float W No Address Description Unit Data Type R/W 22 TBA Liquid Density lb/ft3 Float W 23 TBA Liquid Temperature degF Float W 24 TBA Liquid Volumetric Flowrate - Actual BBL/Day Float W 25 TBA Liquid Mass Flowrate lb/hr Float W 26 TBA Volumetric Totalizer BBL Float W 27 TBA Mass flow Totalizer lb Float W 28 TBA Diagnostic : Drive Gain % Float W 29 TBA Water Actual Density lb/ft3 Float W 30 TBA Oil Actual Density lb/ft3 Float W 31 TBA Water Cut - Actual % Float W 32 TBA Net Water Flow Rate - Actual BBL/Day Float W 33 TBA Net Oil Flow Rate - Actual BBL/Day Float W 34 TBA Gross Flow Rate - Standard SCFD Float W 35 TBA Net Water Flow Rate - Standard BBL/Day Float W 36 TBA Net Oil Flow Rate - Standard BBL/Day Float W 37 TBA Gross Flow Rate - Standard BBL/Day Float W 38 TBA Water Cut - Standard (WLR) % Float W 39 TBA Gas - Oil Ratio (GOR) - Standard BBL/SCF Float W 40 TBA Gas Volume Fraction (GVF) - Actual % Float W 41 TBA Liquid Level (% Level) % Float W 42 TBA Liquid Level Transmitter DP in-H2O Float W 43 TBA Average Operating Pressure Psig Float W 44 TBA Average Operating Temperature degF Float W 45 TBA Average Gas Volumetric Flow Rate - Standard SCFD Float W 46 TBA Average Gas Mass Flow Rate - Standard lb/hr Float W 47 TBA Average Gas Velocity ft/sec Float W 48 TBA Average Liquid Density lb/ft3 Float W 49 TBA Average Liquid Temperature degF Float W 50 TBA Average Liquid Mass Flowrate lb/hr Float W 51 TBA Average Water Cut - Actual % Float W 52 TBA Average Net Water Flow Rate - Actual BBL/Day Float W 53 TBA Average Net Oil Flow Rate - Actual BBL/Day Float W 54 TBA Average Gross Flow Rate - Actual BBL/Day Float W Flow Computer LIST Data Communication Doc.No. 345-1709-IN-LI-003 Protocol MPFM-1709
55 TBA Average Net Water Flow Rate - Standard BBL/Day Float W
56 TBA Average Net Oil Flow Rate - Standard BBL/Day Float W 57 TBA Average Gross Liquid Flow Rate - Standard BBL/Day Float W 58 TBA Average Mass Liquid Flow Rate - Standard lb/hr Float W 59 TBA Average Water Cut - Standard (WLR) % Float W 60 TBA Average Gas - Oil Ratio (GOR) - Standard SCF/BBL Float W 61 TBA Average Gas Volume Fraction (GVF) - Actual % Float W 62 TBA Average Liquid Level % Level Float W 63 TBA Totalizer - Gas Volumetric Flow Rate - Standard MMSCF Float W 64 TBA Totalizer - Gas Mass Flow Rate - Standard lbs Float W 65 TBA Totalizer - Net Water Flow Rate - Standard BBL Float W 66 TBA Totalizer - Net Oil Flow Rate - Standard BBL Float W 67 TBA Totalzer - Gross Liquid Flow Rate - Standard BBL Float W 68 TBA Totalizer Mass Liquid Flow Rate - Standard lbs Float W 69 TBA Gas Mol Weight - Float W 70 TBA Gas Density lb/ft3 Float W 71 TBA Gas viscosity cP Float W 72 TBA Gas compressibility - Float W Notes : 1. Detail of data address will be available and finalized later after the FCU PLC program has been developed. 2. Following concern need to be addressed to PLC programmer. a. For the GLCC communication with ICSS PLC, where both use PLC AB, will be configured by "Messaging" where the data will be transmitted via Ethernet communication module. b. With this CIP Messaging, GLCC PLC will be provide the Element Data array with the detail of : - Architecture system and type CPU to define massage type - Name of Element data array completed with detail data represent to the array - Data type (Real, Integer, Boolean)
5100 12. Post Inspection Sampling Mandatory sampling and inspection after 100% visual inspection. Sampling plan as per ANSI/ASQ Z1.4 – 2008 (or ISO 2859-1): General Inspection Level – II, Single sampling plans for Normal inspection with an AQL of 0.65%. Batch releasing criteria: NMT the specified number of units contains visible particulates. Special level sampling (reduced sample quantity) for destructive inspections (for powder filled, lyophilized products, coloured containers, etc.). AQL Failure Is the test Destructive ? Investigation Re-inspection of 100% units Batch Rejection Yes No PerformAQLinspection Slide No. 12 13. Particle Separation, Identification and Characterization Manufacturers should have knowledge on their particulate matter rejections. Type of particles. Source of each particle type. Routine trend / capability of particulate rejections. Morphology of each type of particle. Chemistry of each particle type. Manufacturers should have comprehensive