T54B Type E Heat Probe Detector: Rugged, Reliable and Responsive
T54B Type E Heat Probe Detector: Rugged, Reliable and Responsive
T54B Type E
Heat Probe
Detector
Rugged, Reliable
and Responsive
KEY FEATURES
// IP67 Ingress Protection
// Robust Stainless Steel Construction
// Proven Reliability
// Normally-open and Normally-closed versions
DESCRIPTION SPECIFICATIONS
The T54B Type E heat detector is a sealed stainless steel Operating Voltage (max.) 32Vdc / 32VAC
tubular device operating on a principle of differential Switching Current1 5mA to 200mA
coefficients of expansion. The T54B is available in either Contact Resistance <1 ohm
normally-open or normally-closed contact configurations. Actuating Temp. Range2 60°C to 240°C
When subjected to heating, the outer stainless steel case Accuracy
lengthens more than the inner strut assembly. Sufficient Set Point +60°C to +145°C +/- 5°C
lengthening of the outer case causes contacts mounted on Set Point +160°C to +240°C +/- 5%
the inner struts to make or break, as required. This creates Fixed Temp. only Type E
a short circuit (or open circuit, as applicable) across the Dimensions (dia.x D) 15 mm x 100 mm
alarm zone circuit triggering an alarm at the control and M20x1.5 Thread
indicating equipment. Material Stainless Steel
An alarm is triggered when the temperature reaches the Weight 95g
detector’s factory-set actuation point. However, a rapid Ambient Temperature
temperature rise will magnify the difference in expansion Set Point +60°C to +145°C -40°C to +175°C
rates and the detector will alarm faster than if the Set Point +160°C to +240°C -40°C to +280°C
temperature rise is slow. This partially compensates for the Relative Humidity 100%
detector’s body temperature lagging behind the ambient Ingress Protection IP67
temperature. The T54B is non-latching and returns to its ActivFire Listed afp-1612
normal state when the temperature drops below the set FPANZ Listed VF/214
point. Part Number Format3 T4EnnnX/T4EnnnNC
1. Resistive loads only. 2. Actuating temperature is factory-set. 3. nnn represents
temperature in degrees C.
INSTALLATION T54B SELECTION GUIDE
Mounting For reliable operation, it is recommended that T54B
The T54B’s external M20 conduit thread is used to screw detectors have set points 20°C or 20% (whichever
the device to a suitable bracket or mounting enclosure. The is higher) above the maximum anticipated ambient
T54B is not certified as flameproof, but may be used as temperature.
a simple device in an intrinsically safe system when used The nearest preferred value T54B detector above the
with an appropriate I.S. barrier, with the approval of the calculated set point should be used - refer to the table
authority having jurisdiction. below.
Note: Do not tighten by tubular body, always use the
hexagon provided. Do not exceed torque of 25 Nm.
LATCHING INDICATORS
Tyco Fire Protection Products has available a range of Latching Indicators suitable for use with the T54B probe-type heat
detectors. These indicators provide a visual alarm indication even after a T54B has self-reset. The Indicators are reset from the
CIE during a zone reset. Note: These Latching Indicators are not suitable for use in hazardous areas and thus must not be
connected to a T54B that is in a hazardous location.
The latching indicators are rated at: 30Vdc maximum, 25mA @45°C; 15mA@75°C, Maximum Ambient Temp. 75°C.
Copyright © 2016 Tyco Australia Group Pty Limited. All rights reserved. Tyco reserves the right to make changes to any aspect of this publication at any time without notice.
TYCO is a trademark of Tyco International Services GmbH. T54BdatTFPP1610