HT Cable Sizing Calculation

The document provides input data and calculations to determine the appropriate cable size for different load ratings. It calculates the required cable cross sectional area based on short circuit current, then applies derating factors to determine the final cable current rating. It also checks voltage drop and ensures it is below the allowable limit. The final cable sizes selected are 1R x 3C x 240 Sq.mm Al XLPE cable for a 1500 KVA load, 1R x 3C x 185 Sq.mm Al XLPE cable for a 750 KVA load, and a cable is required but size not provided for a 500 KVA load.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (10 votes)
20K views

HT Cable Sizing Calculation

The document provides input data and calculations to determine the appropriate cable size for different load ratings. It calculates the required cable cross sectional area based on short circuit current, then applies derating factors to determine the final cable current rating. It also checks voltage drop and ensures it is below the allowable limit. The final cable sizes selected are 1R x 3C x 240 Sq.mm Al XLPE cable for a 1500 KVA load, 1R x 3C x 185 Sq.mm Al XLPE cable for a 750 KVA load, and a cable is required but size not provided for a 500 KVA load.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Input Data

Voltage = 11 KV
Load Rating = 1500 KVA
Full load Current = 78.7 Amps
IK - Short Cicuit Current in KA = 20 KA
Duration of Short Circuit Current = 1 Sec As per IS: 3043, Pg.No-31
K - Conductor connstant = 94 K - Factor Copper Aluminium
A - Area of conductor Size = ? XLPE Cables 143 94
PVC Cables 115 76
Calculation
Area of Aluminium cable = I x √t
K
= 20 x 1.00
94
= 212.766
Area of aluminium conductor is = 1 x 240 Sq.mm (total 240 Sq.mm)

Cable Data
1. Rating factor for variation in ground temperature at 45⁰ C = 0.87
2. Rating factor of cable for laying arrangement = 0.99
3. Rating factor for variation in thermal resistivity of soil at 150⁰ C = 1
4. Rating factor for cable laid in ground in horizondal formation in 2 cable @
45mm distance = 0.9
3. No of Runs = 1
Cable Current Rating for 240 Sq.mm = 355 A
Derating Factor Calculation
Total Derating factor = (1) x (2) x (3) x (4)
= 0.77517
Derated Current for cable = 355 x 0.77517 x 1
After Derating Cable current is = 275.1854 Amps

Therefore The derated Current is more then the Full load Current, So The Selected Cable is Sufficient to carry the Load

Cable Data
Resistance (ohm/Km) R = 0.13
Reactance @50Hz X = 0.103
Operating P.F. cos Φ = 0.8
Actual.Length (Meters) = 250
Maximum AllowableLength (M) = 500
Voltage Drop Calculation
Impedence (ohm/km) R cos f + X sin f = 0.166
Required Number of Runs = 1
Impedence when laid parallImpedence/ No of Runs = 0.1658
Calculated Voltage Drop 1.732x I x Impedx Length/ 1000 = 5.65
Calculated % Voltage Drop Cal Voltage drop/Sys Voltagex 100 = 0.051%
Allowable % Voltage Drop = 2.5%
Note:
Voltage drop at the cable between the HT SWGR to HT SWGR shall be limited to 2.5% as per standard practice.

CABLE SIZE IS OK

The Final Cable Size is 1R x 3C x 240 Sq.mm Al XLPE


Input Data
Voltage = 11 KV
Load Rating = 750 KVA
Full load Current = 39.4 Amps
IK - Short Cicuit Current in KA = 18.5 KA
Duration of Short Circuit Current = 1 Sec As per IS: 3043, Pg.No-31
K - Conductor connstant = 94 K - Factor Copper Aluminium
A - Area of conductor Size = ? XLPE Cables 143 94
PVC Cables 115 76
Calculation
Area of Aluminium cable = I x √t
K
= 18.5 x 1.00
94
= 196.809
Area of aluminium conductor is = 1 x 185 Sq.mm (total 185 Sq.mm)

Cable Data
1. Rating factor for variation in ground temperature at 45⁰ C = 0.87
2. Rating factor of cable for laying arrangement = 0.99
3. Rating factor for variation in thermal resistivity of soil at 150⁰ C = 1
4. Rating factor for cable laid in ground in horizondal formation in 2 cable @
45mm distance = 0.9
3. No of Runs = 1
Cable Current Rating for 185 Sq.mm = 275 A
Derating Factor Calculation
Total Derating factor = (1) x (2) x (3) x (4)
= 0.77517
Derated Current for cable = 275 x 0.77517 x 1
After Derating Cable current is = 213.1718 Amps

Therefore The derated Current is more then the Full load Current, So The Selected Cable is Sufficient to carry the Load

Cable Data
Resistance (ohm/Km) R = 0.21
Reactance @50Hz X = 0.11
Operating P.F. cos Φ = 0.8
Actual.Length (Meters) = 350
Maximum AllowableLength (M) = 500
Voltage Drop Calculation
Impedence (ohm/km) R cos f + X sin f = 0.234
Required Number of Runs = 1
Impedence when laid parallImpedence/ No of Runs = 0.2340
Calculated Voltage Drop 1.732x I x Impedx Length/ 1000 = 5.58
Calculated % Voltage Drop Cal Voltage drop/Sys Voltagex 100 = 0.051%
Allowable % Voltage Drop = 2.5%
Note:
Voltage drop at the cable between the HT SWGR to HT SWGR shall be limited to 2.5% as per standard practice.

CABLE SIZE IS OK

The Final Cable Size is 1R x 3C x 185 Sq.mm Al XLPE


Input Data
Voltage = 11 KV
Transformer Rating = 500 KVA
Full load Current = 26.2 Amps
IK - Short Cicuit Current in KA = 18.5 KA
Duration of Short Circuit Current = 0.5 Sec As per IS: 3043, Pg.No-31
K - Conductor connstant = 94 K - Factor Copper Aluminium
A - Area of conductor Size = ? XLPE Cables 143 94
PVC Cables 115 76
Calculation
Area of Aluminium cable = I x √t
K
= 18.5 x 0.71
94
= 139.165
Area of aluminium conductor is = 1 x 185 Sq.mm (total 480 Sq.mm)

Cable Data
1. Rating factor for variation in ground temperature at 45⁰ C = 0.87
2. Rating factor of cable for laying arrangement = 0.99
3. Rating factor for variation in thermal resistivity of soil at 150⁰ C = 1
4. Rating factor for cable laid in ground in horizondal formation in 2 cable @
45mm distance = 0.9
3. No of Runs = 1
Cable Current Rating for 185 Sq.mm = 275 A
Derating Factor Calculation
Total Derating factor = (1) x (2) x (3) x (4)
= 0.77517
Derated Current for cable = 275 x 0.77517 x 1
After Derating Cable current is = 213.1718 Amps

Therefore The derated Current is more then the Full load Current, So The Selected Cable is Sufficient to carry the Load

Cable Data
Resistance (ohm/Km) R = 0.21
Reactance @50Hz X = 0.11
Operating P.F. cos Φ = 0.8
Actual.Length (Meters) = 15
Maximum AllowableLength (M) = 20
Voltage Drop Calculation
Impedence (ohm/km) R cos f + X sin f = 0.234
Required Number of Runs = 1
Impedence when laid parallImpedence/ No of Runs = 0.2340
Calculated Voltage Drop 1.732x I x Impedx Length/ 1000 = 0.16
Calculated % Voltage Drop Cal Voltage drop/Sys Voltagex 100 = 0.001%
Allowable % Voltage Drop = 2.5%
Note:
Voltage drop at the cable between the HT SWGR to HT SWGR shall be limited to 2.5% as per standard practice.

CABLE SIZE IS OK

The Final Cable Size is 1R x 3C x 185 Sq.mm Al XLPE