Test Procedure - CT & PT
Test Procedure - CT & PT
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
Page No.
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
Secondary winding resistance test is to verify the CT & PT secondary winding resistance with
specified one and no discontinuity in the winding, This value can be used in other calculations.
Measure the D.C. resistance value across the CT & PT secondary and record. The same shall be
done for all taps and cores. These values are infuenced by temperature, so ambient temperature
must be recorded during this test.
3
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
Insulation tester leads shall be connected between one phase conductor and earth. Test voltage
shall be select according to combinationa and voltage class.
Before disconnecting the test leads test object shall be discharged through ground. The same
procedure shall be followed for other phases.
LIMITS
Value of insulation resistance should meet the manufacturer minimum. If this value is not
available, the component tested should have at least one Meg ohm for every 1000 volts of
rated voltage plus an additional one Meg ohm.
4
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
c. Polarity Check
Polarity test is to confirm the polarity marking on the CT & PT primary and secondary and verify it is
matching with drawing. More ever it is giving an idea, how to connect the secondaries to make the
protection (like directional, differential) and metering function properly.
Close and open the battery switch connected on the primary. Observe the pointer is moving +ve
direction, while closing and -ve direction while opening for correct polarity.
5
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
This test is to ensure the CT & PT circuits are properly connected with respected cores and there is
no mix up in the circuit (phase identification).
Core identification:
When one CT / PT is having several cores used for different purposes. The cores can be identified
during primary injection test by shorting the one of the core at CT / PT terminal itself and check
there is no current only at relevant load. The same can be verified for other cores.
Inject 20% to 80% of rated primary current / voltage between phase to phase with all connected
burden. Measure secondary current at all points of CT / PT circuits. It shall be done for other phases.
6
Consultancy |Third party Inspection |RLA | Testing & Commissioning |Training in Power Sector
Magnetization Curve test is to confirm the magnetization characteristics of CT with name plate
specification.
This test shall be conducted before ratio test and after secondary resistance and polarity test, since
residual magnetism left in the core due to DC test (polarity, resistance), which leads additional error
in ratio test.
The circuit connection shall be made as shown Fig below. The primary should be open during test.
Demagnetization:
Before start the test demagnetize the core by Inject voltage on secondary terminals and increase up to where
considerable increment in current with small voltage increment. Now start decreasing the voltage to zero, the rate
at which increased.
Magnetization test:
Now increase the voltage and monitor the excitation current up to the CT reaching near to saturation point.
Record the reading of voltage and current at several points. Plot the curve and evaluate the Vk and Image from
the graph.
Limits:
Class X CT:
The obtained Vk should be greater than specified one; magnetizing current should be less than specified one.
Protection class CT:
The secondary limiting voltage can be calculated as follow
Vk = (VA * ALF)/ Is
Is - rated secondary current
VA- rated CT burden
ALF-Accuracy limit factor