Technical and Operating Documentation: Smoke and Heat Exhaust Control Unit MCR 9705
Technical and Operating Documentation: Smoke and Heat Exhaust Control Unit MCR 9705
Table of Contents
1. Introduction .......................................................................................................... 3
2. About the mcr 9705 control unit ........................................................................... 4
3. Exploitation........................................................................................................... 8
4. Assembly and start up ........................................................................................ 12
5. Instruction manual for checking connection and performance of the mcr 9705
control unit.......................................................................................................... 14
6. Typical connection diagrams .............................................................................. 16
7. Service and maintenance ................................................................................... 20
8. Warranty terms and conditions ........................................................................... 20
9. Technical specifications ..................................................................................... 22
10. The Declaration of Performance ........................................................................ 23
11. European Certificate of Constancy of Performance ........................................... 23
The mcr 9705 control unit meets the requirements of the National Technical
Assessment CNBOP-PIB-KOT-2018/0051-1009 issue 2 and the essential
requirements of EU directives:
2014/35/EU (LVD) regarding electrical equipment provided for use within
certain voltage limits;
2014/30/EU (EMC) regarding electromagnetic compatibility.
Related documents:
- European certification of constancy of performance of construction
products CNBOP-PIB No.1438-CPR-0607 and The Declaration of 18
Performance No. 092/HO/2018 of 12/09/2018 confirming the compliance
of the power supply with the requirements of EN 12101-10: 2007.
- EU Declaration of Conformity No. 091/HO/2018 dated 09/12/2018. 1438
The above documents can be downloaded from the "MERCOR” S.A. company
website - www.mercor.com.pl
Thank you for selecting the mcr 9705 control unit. Please, read these
instructions carefully and follow the guidelines. This will ensure smooth and reliable
operation of the device.
“MERCOR” S.A. reserves the right to modify the product or the documentation
without notice.
We wish to ensure your full satisfaction with our products and we will be glad to
provide You with professional service and assistance if necessary.
„MERCOR” S.A.
Strona 2 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
1. Introduction
The mcr 9705 control unit is used in smoke exhaust systems to control the operation
of:
- electrical actuators and in particular vent actuators in mcr PROLIGHT,
mcr THERMOLIGHT, mcr ULTRA THERM, mcr LAM, mcr LAM-N,
- valves of alarm boxes with CO2 cartridges,
- drive of automatic rolled curtains PROSMOKE CE/CE1, mcr
PROSMOKE FSv2 CE,
- electromagnetic door locks and in other mcr series products used for fire
protection purposes, which require 24 V= power supply.
The electrical mcr 9705 unit should be installed near the smoke exhaust
window or in the building supervision room. The unit is powered with 230 V AC
voltage. The working DC voltage is 24 V on output terminals to which the devices of
the electrical smoke exhaust control system are connected. The unit is equipped with
batteries which ensure system operation for 72 hours after a power outage. After that
time a single emergency opening of smoke vents is possible. If the mcr 9705 control
panel is used to control the PROSMOKE FSv2 CE mcr curtains, the standby time
depends on the number of connected curtains (for details refer to the mcr
PROSMOKE FSv2 CE curtains).
The mcr 9705 unit is equipped with audio and visual alarm indicators of its
operating status, which allows easy identification of the alarm’s source or a system
defect.
Smoke exhaust vents which were opened in emergency mode can be closed
(cancellation of the alarm state) providing that the cause of the alarm has been
removed. If mcr 9705 is equipped with manual pushbutton mcr RPO-1, remote
operation and display of the unit’s status is possible (defect and alarm signals,
remote alarm reset and closing vents after the alarm).
mcr 9705 is performed in two series of type, which are based on modules:
- 5 A, 2 x 5 A, 3 x 5 A, 4 x 5 A, 5 x 5 A, 6 x 5 A, 7 x 5 A, 8 x 5 A;
or
- 8 A, 2 x 8 A, 3 x 8 A, 4 x 8 A, 5 x 8 A, 6 x 8 A, 7 x 8 A, 8 x 8 A.
Series of type [8A] shall be used only for natural smoke and heat exhaust systems.
Strona 3 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Closing of the vent after its emergency opening (deleting the alarm state) takes place
after the cause of the alarm has been removed.
Connecting of the mcr RPO-1 manual smoke exhaust pushbutton enables remote
control panel operation (alarm enabling, alarm deleting and closing the vent after the
alarm) and remote signalling of the system status (READY, FAULT, ALARM).
On the front panel, there are diodes which indicate the status of the control center:
No. Description Color Function
1 POWER SUPPLY green indicates that both power supplies are
present
2 READY yellow indicates no alarm, system ready for
operation
3 ALARM red optical alarm indicator
4 FAULT yellow general system failure signal
5 VENT OPEN red indicates that smoke vents are open
or: CURTAIN or door closed*
(DOOR CLOSED)*
* doors closed (in remote door control systems).
Strona 4 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
7 8 9
10 11 12 13
14 15 16 17
18
23
19
20
21
22
On the inside of the control unit’s door there’s an audio alarm device (22) and the
optical indicator board (23). Optical indicators are used for the system diagnostics:
Strona 5 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
To the left of the RESET button there is an eight-position switch SW1 (27), designed
to set the functions of the control unit:
Switch position Function
SW1-1 Disconnection of the actuator line
SW1-2 Disconnection of the sensor line
SW1-3 Disconnection of the ROP pushbutton line
SW1-4 Disconnection of the in/out relay contacts
SW1-5 Full opening of the vents during non-emergency ventilation in
in "ventilation" and "hatch" mode
SW1-6 Activation of the mode – “door’s control”
SW1-5 Enabling the electric locking drive/ activating alarm boxes
+ ------------------------------------------------------------------------
SW1-6 Activation of automation mode in mcr PROSMOKE CE/CE1
curtain (for control panels with the "curtain" option)
SW1-7 -
SW1-8 Disabling the autoreset function
Note: the default setting for SW1-1 to SW1-7 – is OFF position,
SW1-8 – is ON position.
Strona 6 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Above the RESET pushbutton there are jumpers regulating the vent’s opening time in
ventilation and entrance mode (combinations of settings can be found in Chap. 3.2):
No. Description Function
46 H6 depending on the combination created with the H5 jumper
47 H5 depending on the combination created with the H6 jumper
Along the top edge of the module's PCB there are terminal strips which are used to
connect the system’s elements:
No. Description Function
28 P6 Input for ventilation (U-up, D-down, ┴ - joint, closing
contacts)
29 P7 input for wind/rain controls (closing contact)
30 P8 output for actuators (-,+)
31 P9 RPO(+,-) pushbutton line
32 P10 control input from ROP-1 (R,U)
33 P11 sensor’s line (+,-)
34 P12 power supply of the alarm signal loop (+, -)
35 P13 external alarm input, 24V= relay
36 P14 alarm indication output - relay contact
37 P15 defect indication output - relay contact
38 P16 programmable / service output (ex. opening the vent/ door
closing) - relay contact
39 P17 RPO-1 indication output (1, 2, 3)
48 P19 power supply for alarm signaling loop (-, +)
Note: For control units designed for the purpose of a smoke curtain, above the elements [30,44]
there is additional 4 poles terminal strip for mcr PROSMOKE CE/CE1 curtains’ actuators.
On-board fuses:
No. Description Function
43 FS1 batteries protection (6.3 A or 8 A* quick)
44 FS3 actuator’s line protection (6.3 A or 8 A* quick)
230 V 50 Hz power supply is connected to the terminal strip (42) in the top left
corner of the assembly board (inside the control unit).
Overload circuit breaker FS2 (45) – C 4 A or 6 A* on the assembly board
provides protection for the 230 V mains circuit and the possibility for disconnecting
power supply.
Strona 7 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
3. Exploitation
VENT OPEN
ALARM
READY
FAULT
UNIT STATUS
+ VENT OPEN □ ANY STATUS
- VENT CLOSED
B ACTUATOR IN OPERATION + ON
- + ALARM
+ + - - NORMAL OPERATION - OFF
- - B MAINS FAILURE
+ - - + DEFECT B BLINKS
+ - - - DISCONNECTION
mcr 9705 is a maintenance-free device. It requires constant 230 V mains power
supply. In case of power shortage caused by mains failure, the installed batteries will
ensure 72-hour emergency power supply. Any power outage exceeding 72 hours
can result in permanent damage of the batteries.
Strona 8 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
If the system is additionally equipped with a key switch (Pic. 4), setting the ignition
switch in the "1" position activates the "hatch" mode in place of the "ventilation"
mode. When "hatch" mode is active:
- the weather station’s displays don’t cause vent’s closing,
- it is not possible to close the vent with the ventilation button ,
- the vent opens, just like in "ventilation" mode, by pressing the ventilation button,,
- the time of opening the damper depends on the settings on the H6 and H5 jumpers,
the vents:
*default settings
NOTE!!
The ventilation function is inactive when an emergency alarm is
active or if there’s mains power outage!
Strona 9 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Note!
1. In case of the ALARM signal, smoke exhaust vents will be opened regardless of
weather conditions!
2. Do not use alarm buttons for non-emergency ventilation!
In automatic door mode, in the ALARM state, the control panel cuts off the power
from the actuators, which releases the door holders.
The door automation mode is also used to control the operation of mcr
PROSMOKE FSv2 CE smoke curtains. In this case, after cutting off the power from
the actuators, the curtains automatically fall into the working position.
NOTE: the door automation mode is not intended for the controlling the mcr
PROSMOKE CE/CE1 curtains.
In the electric locking drive/activating alarm boxes, in the ALARM state, the
control panel gives a fixed 24 V signal, but does not give a signal with reversed
polarity in the alarm reset state.
Alarm release methods:
Manual - break the glass of the smoke release pushbutton and push the button.
Automatic – depending on the type of sensors used, they will be automatically
activated when the temperature rises or the smoke conditions will
appear.
Automatic release from an external source – a signal from an external device
(e.g. Fire Alarm Unit) is supplied to the alarm signal-in terminals of the control
unit (Pic. 3 item 35). The alarm will cause 24 V power outage on P13 terminals.
Strona 10 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
pushbutton, delete the alarm either using the RESET button on the casing of the
control unit or by using the ALARM RESET button in the RPO-1 unit (hold the button
down for at least 1 s). The red ALARM diode will be turned off, and the yellow
READY diode will light up.
After alarm release from a smoke sensor (the sensor line), delete the alarm using
the RESET button. The sensor will not activate the alarm again if there’s no longer
excessive smoke/high temperature. The red ALARM diode will be turned off, and the
yellow READY diode will light up.
After alarm release from an external source (in/out) one first needs to delete the
alarm in the device which initiated the response of the mcr 9705 control unit.
Depending on the SW1-1 setting, there are 2 possible ways to delete the alarm:
SW1-8 in ON position - After deleting the alarm in the device which initiated the
response of control unit, delete the alarm with the RESET key. The ALARM diode
goes out, the READY diode lights up.
SW1-8 in the OFF position - After deleting the alarm in the device which initiated the
response of the control unit it will be cleared automatically (in door automation mode
with a delay of 75 s). The ALARM diode goes out, the READY diode lights up. The
actuators of the devices will be actuated by the control unit in the closing direction.
Then delete the alarm using the RESET button. The red ALARM diode will be turned
off, and the yellow READY diode will light up.
If the cause of the alarm can’t be removed (for example, when there’s an alarm
source failure), one needs to access the segment representing the relevant alarm
source in the SW1 switch in the control centre module (Pic. 3 item 27) and adjust it
from the “OFF” to the “ON” position (in accordance to the description on the optical
signal board – disconnection of the RPO/sensor/in-out line). In next step delete the
alarm using the RESET button. The red ALARM diode will be turned off.
The yellow READY diode will not light up.
In this case CALL THE SERVICE
Strona 11 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Never change the default settings of the voltage potentiometer for the batteries.
For mcr PROSMOKE FSv2 CE curtains, use the standard mcr 9705 control
panel. The control panel should be set to door automation mode (SW1-6 ON).
The control unit’s standby time in cooperation with the curtains mcr PROSMOKE
FSv2 CE depends on the number of connected smoke curtains - additional
information in the DTR of mr PROSMOKE FSv2 CE smoke curtains.
1. Sensors line - 2 leads (e.g. YnTKSY) from P11 terminals. Terminal resistor 5,1
kΩ in the base of the last sensor. The maximum number of sensors is limited in
accordance with the list of technical parameters (see chapter 9 Technical
specifications).
2. Smoke exhaust pushbuttons line (RPO) - 7 leads from P9 (alarm closing
contact), P10 (control inputs) and P17 terminals (indicator output). Terminal
resistor 10 kΩ in the last pushbutton. The maximum number of pushbuttons in
accordance with the technical parameters (see page 20).
3. Actuators line - 2 leads in silicone insulation (feature PH30, for example HLGs),
from P8 terminals. Terminal resistor 10 kΩ in the last connection box. The line is
protected by a 6,3 A or 8 A fuse (FS3). The maximum number of actuators in
accordance with the technical parameters. Only specific leads shall be used,
leads that are compatible with actual regulations.
Attention: In case of multi module centrals – do not connect galvanized outputs
[to actuators] of different modules.
4. Ventilation - pushbuttons for ventilation (manual vent control- upwards,
downwards) – 3 leads (e.g. YTKSY or YDY) from P6 terminals. It is possible to
connect several pushbuttons in parallel.
5. Hatch function - switch with key (for switching between the functions
"ventilation" - "hatch") - 2 wires (YTKSY or YDY) from terminals P1
6. Automatic weather monitoring unit for closing the vents in case of a strong
wind/ heavy rain - 2 leads (e.g. YTKSY or YDY) from P7 terminals.
7. External alarm input to the 24 V relay coil – 2 leads (e.g. YnTKSY) from P13
terminals. If the device which activates the alarm (fire alarm control unit) has a
24 V output, it shall be connected directly to the P13 terminal. Loss of voltage at
the P13 terminal will activate the alarm. If the device which activates the alarm is
equipped with a voltage-free null contact (NC), we have to use the loop power
supply available on the P12 terminal (see Diag. 1 or Pic. 3). The P12 terminal is
short-circuit resistant and can carry a load of maximum two relays. Once the line
is connected remove the H1 jumper which blocks the external alarm.
Strona 12 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Strona 13 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
- in the case of a device without a separate power source, connect the 2 wires
(YnTKSY) with the power supply from terminal P19.
An example of both variants of connection is shown in Diag. 4.
NOTE - the maximum load on the alarm loop terminals is 110 mA!
17. Start-up. Before switching on the power supply, check if the leads are connected
properly.
Note: the leads should be placed and connected in accordance with relevant
standards and basic rules for wiring. First switch on the 230 V mains voltage, and
only then connect the batteries. The reverse order is not recommended because
of a large current surge that occurs during the charging of the condenser in the
power supply adaptor.
18. In a correctly operating unit, the following LED indicator are on: READY, POWER
SUPPLY, and VENT OPEN. When the CLOSE VENTS button is pressed, the
VENT OPEN diode begins to blink and then switches off after about 5 minutes.
When the actuator is in operation, the VENT OPEN diode keeps blinking.
19. In order to check the operation of ventilation, the weather monitoring unit should
be disconnected. The weather monitoring unit blocks ventilation for several
minutes after the wind has ceased, and in case of rain the sensor needs to get
dry, which takes even more time.
20. The LEDs on the inside of the unit’s door make detailed defect identification
possible. To test their operation, press the TEST button and hold it down for
about 1 s. To test the operation of the audible alarm indicator, press
simultaneously the TEST and RESET buttons.
Note: in order to connect the unit you should use leads which satisfy the
requirements of current regulations.
3. Perform the control panel start-up in accordance with the Operation Manual
(Chapt. 4, par. 17, 18).
4. Check whether the control panel remains in the normal operating state
(Chapt. 3.1).
5. After min. 12 hours of charging the batteries, check the voltage at the battery
terminals. The measurement must be carried out in the normal operating state
(Chapt. 3.1). The voltage at the battery terminals should be in the range of 26.5 ÷
28 V =.
6. Perform auditing of optical and acoustic signalling (Chapt. 4, Par. 18, 20).
7. Check the correctness of fault detection by the control unit: damage to the sensor
line (e.g. take out the last sensor from the socket), damage to the RPO button
line (e.g. to open the RPO line, P9 terminal), damage to the actuator lines (e.g.
Strona 14 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
open the actuators line, the control panel in mode smoke exhaust), power supply
damage (e.g. 230 V disconnect), battery detection (e.g. disconnect the batteries).
Tests should be performed in a normal operating state for any potential damage.
In each test case, the fault condition should be detected and signalled on the
front panel of the control unit, on the service panel for selected faults, by means
of the mcr RPO-1 button (if connected) and on the fault indication output (by
ohmmeter control).
8. Check whether the control panel is correctly detecting alarms. Check all
connected alarm sources:
a. alarm from the RPO line (press the mcr RPO-1 button),
b. alarm from the sensor line (activate the sensor),
c. alarm from the external alarm line (activate external device or open the line).
Tests should be performed in the normal operating state independently for each
connected alarm source. In any case, the alarm condition should be detected
and signaled by the control unit (Chapt. 3.4) on the front panel, on the service
panel with the diode of the proper alarm source, with the diode of the button mcr
RPO-1 (if connected) and on the alarm signal output (ohmmeter control), and all
connected fire devices controlled by the control panel should be controlled.
9. Check the correctness of the line disconnection signaling on the service panel:
after switching the segments (1 ÷ 4) of switch SW1 (page 6) the appropriate
LEDs should light up on the service panel, and the READY diode on the front
panel should go out. After the test, restore the lines to the connection status.
10. If applicable, check that the daily ventilating function (Chapt. 3.2) and the
programmable \ service output (page 7) are connected.
11. Check whether the control unit remains in the normal operating state after all
tests have been performed (Chapt. 3.1).
12. The control panel can be put into operation if all tests have been completed
correctly. Only an efficient and properly connected control unit can work in fire
protection systems. In the event that at least one result of the above tests is not
correct, the control panel cannot be used in security systems and should be
restored for proper operation.
After checking the above points, make a record in all fields of the table below.
Strona 15 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Diag. 1 Typical configuration of a smoke exhaust system equipped with the mcr 9705-5A
control unit.
Elements:
CP - weather monitoring unit mcr P054
LT - ventilation pushbutton
ŁNK - key switch for activating the "hatch" mode
ME - electromechanical actuator
OCD – optical smoke sensor (e.g. KL731)
PM - connection box
RPO – manual smoke exhaust pushbutton mcr RPO-1
Attention!
Not all the elements of the system (in particular the fire protection control unit and the
weather monitoring unit) must be present in the smoke exhaust system.
Strona 16 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Diag. 2 Typical connection of smoke curtain to control unit mcr 9705 (Execution for curtains
mcr PROSMOKE CE/CE1).
Elements:
OCD – optical smoke sensor (sensors should be connected according to advice of
a manufacturer)
RPO – manual smoke exhaust pushbutton mcr RPO-1
PM – connection box
ME – electromechanical actuator 24 V = curtain mcr PROSMOKE CE/CE1
Attention!
1. Not all the elements of the system (in particular the connection with fire protection
control unit) must be present in the smoke exhaust system.
2. Central unit or module operating with smoke curtain cannot be connected
simultaneously to smoke vent’s actuators, weather central unit or ventilation push
buttons.
Strona 17 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Diag. 3 Typical connection of smoke curtain mcr PROSMOKE FSv2 to control unit mcr 9705
(central unit in the mode “doors control”).
Elements:
PM - connection box
MECU XL - work controller of smoke curtain mcr PROSMOKE FSv2 CE
P - service pushbutton for temporary lowering of the curtain
a b
Diag. 4 An example of connection of external alarm device: (a) with its own power source,
(b) without its own power source.
Strona 18 z 24
Strona 19 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
mcr 9705 control unit/steering module mcr 9705 control unit/controlled module
Attention:
1. Remove jumper H1 in controlled module!
2. Controlled module is activated by the alarm signal from steering module.
3. The autoreset function in controlled module should be enabled (SW1-8 OFF).
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
The obligation to carry out service inspections of fire-fighting equipment results from
the provisions of the Ordinance of the Minister of Interior and Administration of June
7, 2010 on fire protection of buildings, other construction objects and areas (Journal
of Laws of 2010 No. 109, item 719).
In order to be able to perform activities included in the scope of service inspections,
as well as service and warranty activities such as visual inspection or repair, it is
necessary to provide physical access to the devices.
Strona 20 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
As regards matters not regulated by these "Warranty terms and conditions", relevant
regulations in the Civil Code, and in particular Art. 577-581 shall apply.
Strona 21 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
9. Technical specifications
The data in the table below applies to the control panel with a single module:
Item Value
Base type: 5A 8A
Control unit type conventional
Power supply voltage – basic power supply 230 V 15
10%
% 50 Hz
Rated power 150 VA 250 VA
Output voltage (power supply for actuators) 24 V DC, max. 24 V DC, max. 8 A
5,2 A
Stand-by power supply 2 pcs. of batteries (3,2 Ah, 12 V)
connected in series
Charging voltage for set of batteries 27,5 V 0,2 V @20C
Working temperature range -5C ... +55C
Maximum number of sensors in line: 20 pcs.*
Maximum number of RPO-1 pushbuttons: 8 pcs.
Maximum number of actuators – by type:
MCRL KT10x and MCRL KR10x 5 pcs. 8 pcs.
or
KT10x and KR10x
MCRW 08x or G08x or SG08x or S08x 6 pcs. 10 pcs.
MCRW 10x or G10x or SG10x or S10x 5 pcs. 8 pcs.
MCRW 16x or G16x or SG16x 3 pcs. 5 pcs.
MCRW 20x or G20x or SG20x 2 pcs. 4 pcs.
MCRW 26x or G26x or SG26x 2 pcs. 3 pcs.
MCRW 40x or G40x or SG40x 1 pcs. 2 pcs.
MCRW 60x or G60x or SG60x - 1 pcs.
MCRW 80x or G80x or SG80x - 1 pcs.
(other types of electric actuators depending - -
upon consumed and maximum current.)
Maximum number of electromagnetic door
locks – by type:
mcr TE 50 40 pcs. 40 pcs.
mcr TE 100 30 pcs. 30 pcs.
The maximum number of curtain modules 2 pcs. 2 pcs.
CE/CE1 Width < 4 m Width >= 4 m
The maximum number of curtain modules 12 pcs.
FSv2 CE
Operation time without mains voltage, in
READY mode min. 72 h**
Load for relay outputs max 100 mA, 24 V
Environmental class according to KOT I
Environmental class of the power supply I
according to PN-EN 12101-10
Protection level for housing IP 54
Dimensions (H x W x D) 300 x 300 x 120 mm
* In standby mode, the current consumption of 1 sensor cannot exceed 60 μA!
** After this time, the control unit can open actuators once and alarm for 30 minutes.
The backup time in the door automation mode depends on the number of connected
devices.
Strona 22 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Strona 23 z 24
Smoke and Heat Exhaust Control Unit mcr 9705 – User Instruction Manual
Strona 24 z 24