Manuscript Lab CPE622
Manuscript Lab CPE622
Controllers Tuning
MUADZ BIN CHE ABDULLAH (2019451942), MUHAMMAD ZA’IM BIN MD FARIDUL ATHAS
(2019872684)
Abstract—This experiment presents typical techniques permanent state error. The error is distributed over a
used for PID tuning. The techniques are developed for PID time until the error is zero. It holds the value to the final
tuning and optimization techniques applied for tuning control unit with error zero. Comprehensive control
purposes. Based on the process linearity graph, shows reduces the output if negative error occurs. It decreases
slightly nonlinear relation of process response and reaction speed and affects system stability. Reaction
manipulated variable. the higher the value of the
rates are improved by decreased integrated Ki gain.The
proportional gain, Kc, the lower the value of the process
output response to an error produces a marginally higher
dead time. An increases in PB and I values, make the MV
initial deviation from that which can be achieved
action slower. A slower action of MV results in slower
individually by means of a proportional plus integral
process response because PB and I are inversely
proportional to MV. Thus, the new process response curve regulation and used in the output signal (J.Hall, 2017). It
shift to the right. Although the values of Proportional Band is because of a change to the integral control signal.
(PB) and Integral (I) obtained in this rule is not Therefore, the oscillation decreases and no offset can be
generalized to work with all processes, the starting values obtained. This control mode is used commonly because
will work on many processes. the proportional component is suitable in a cycle where
moderate changes are happening whereas the integral
Keywords—PID tuning; process linearity; proportional
gain; disturbances; controller settings. component makes large changes to the load and
eliminates the offset. A derivative (D) reaction
I. INTRODUCTION anticipates a process load shift and sends a correction
The PID is the most common control algorithm used in
signal to reduce the error. Depending on the adjustment
industry and is universally accepted in industrial control.
of the variance from the setpoint, this action corrects.
Part of the success of PID controllers is due to their
Related action results in proportional movement of the
reliable performance in a wide variety of operating
valve more rapidly and more than would usually occur
conditions and partly to their flexibility, which makes it
with just proportional operation. Typically, temperature
fast and convenient to run
control systems require differential operation. Such
P is a short term for proportional but PB is a common methods are subject to lengthy processes and calculation
concept in most industrial controllers with a unit lags. Even derivative action is used for different
percentage. The proportional factor is easier to applications, including anti-surge systems where a quick
understand. The product of the gain and measurement valve reaction is imperative (A.Poe, 2012). Derivative
error is the output of the proportional factor. Therefore, control has the property that the controller output
greater proportional gain or error produces a higher changes are commensurate with the intensity. Change
proportional factor output. Setting the proportional gain from shorter to longer times in order to change the
too high causes a monitor to override the set-point again derivatives manually. The longer the derivative time is
and again, leading to oscillation. When the error is too set, the greater and the oscillatory the corrective action.
small, the loop output becomes negligible. The
downside of a proportional only loop. Therefore, there is
always error even though the proportional loop is
constant (Avery, 2009). As the p-controller is limited
b.
III. THEORY
PROCESS LINEARITY
Process linearity is a relationship between elements of a
process and the output. Linearity represents a sensor’s ability In determining the linearity of the process,
to respond to changes in a measured variable over the entire
range in the same way. It is to determine whether the 0% change is linear
relationship between dependent variable and independent 50 ≥ % change > 0 is slightly linear
variable is linear or nonlinear. Figure 1 compares the process 50 < % change is highly nonlinear
behaviour between linear and nonlinear processes.
PROCESS CHARACTERISTICS
Process characteristics determination such as dead time,
time constant and response rate is observed using graphical
and numerical analyses. Graphical analysis contain Tangent
method and Reformulated Tangent Method to identify and
calculate the process dead times and response rates of self
regulating and non-self regulating processes. Figure 3 shows
the analysis of Dead time and Response Rate using Alternative
Mathematical Approach
Where,
IV. PROCEDURES
𝑇𝑐 = 𝑇63.2% − 𝑇𝑑
1. The control loops is selected:
RR= 0.05288/s
4. TIME CONSTANT LIC11 (Level Control) – EMERSON
b=60s/42mm = 1.4285s/mm
Tangent Method
b=60s/43mm = 1.3953s/mm
𝑇 = 70mm
𝑇 = 9 mm
2-Point Method
𝑇 = (11.5-9)*(1.3953) =3.48825s
dy = 10mm
The process time constant (Tc) is determined for how fast the PV
is responding. The distinctive methods that are used for this
process are tangent method, 2-point-method and tangent-and-
Tangent & point point method. The values obtained varies from one another.
Time constant value as calculated based on tangent method,
𝑇 = 11mm tangent and point method and 2-point method for FIC21 are
3.48825s, 2.09295s and 2.7906s respectively. For LIC11 tangent
method, tangent and point method and 2-point method The
𝑇 = (11mm - 9mm)(1.3953) = 2.7906s
values vary because of the different sets of equation provided.
5. NUMERICAL METHOD In Objective 5, time constant describes how fast the PV responds to
a change in CO.in this experiment values Tc is 2.7872 s. However,
the variation of values is expected due to the methods having
different sets of equations (Ishak, 2018). Furthermore, the values of
maximum response rate (RR) and dead time (Td) was obtained at
0.288675 s-1 and 33.8928 s via the numerical method. Dead time can
be defined as the delay from when a controller output (CO) is being
issued until when the process variable (PV) begins to respond. From
the dead time obtained above, it is observed that the value is quite
high but does not exceed the values of time constant obtained which
could be an issue. Since the dead time is the denominator of
controller gain, KC, the higher the dead time gets, the smaller the KC
which implies a less active controller which makes it more cautious
and conservative approach.This might be due to the condition
around the sensor such as high flowrate which could add
troublesome delay for the detection of flow (Control Guru, 2015)
Based on the data given, FIC31 flow cotroller response rate, dead
time and time constant can be determined.
Flow rate
time (s) (m3/hr) PV(%) RR