Competency-Based Learning Materials: Install Electrical Protective System
Competency-Based Learning Materials: Install Electrical Protective System
MATERIALS
Install Electrical Protective system
Terms and Definitions
3. Blade-type Cartridge Fuse –Fuse with flat contact blades on cylindrical case.
4. Circuit breaker –Automatic over-current device that trips on overloads or shorts and
is resettable.
6. Device –Electrical equipment that carries or transfers current but does not use it.
7. Dual-element Fuse –Fuse that has within it a thermal cutout element with a time
delay that permits momentary harmless inrush currents to flow without harming the
fuse.
8. Edison-base plug Fuse –Fuse with base that fits the same socket as a regular
based incandescent bulb.
9. Fault Current –Current that flows from one conductor to ground or another
conductor because of an abnormal connection or arc between the two.
10. Ferrule-type Cartridge Fuse –Fuse with a base metal caps on a cylindrical case.
14. Oil Circuit Breaker –Load interrupter in which interrupting contacts operate
submerged in transformer oil.
15. Over-current Protection –Weak link in the circuit that limits the amperage to a
specified amount.
16. Overload –Larger than normal current flowing within the normal current paths.
17. Selective Coordination –The use of interrupting devices sized and installed so
that the one nearest the fault or overloaded machine will open before any of the larger
upstream devices open.
18. Short Circuit –Larger than normal current flowing outside the normal current path.
19. Single-element Fuse –Fuse that contains only one element and is not designed
to carry an overload.
20. Time Current Curve –Plotted curve showing how long a fuse or breaker will carry
an overload before opening the circuit.
21. Type “S” Plug Fuse –Fuse with special size-limiting characteristics for each
amperage rating.
23. Cabinet –An enclosure designed either for surface or flush mounting and provided
with a frame, mat, or trim in which a swinging door or doors are on may be hung.
24. Concentric Knockout –Several removable metal rings that allow for the entrance
of various standard sizes of connectors into a cabinet.
25. Dead Front –Removable cover used to prevent exposure of live parts to persons
on the operating side of the equipment.
3
27. Dustproof –So constructed or protected that dust will not interfere with its
successful operation.
28. Dust-tight –So constructed that dust will not enter the enclosing case.
29. Eccentric Knockout –knockout that is removed in sections to form to the larger
holes.
32. Rainproof -So constructed, protected, or treated as to prevent rain from entering
with successful operation of the apparatus.
34. Grounded (neutral) Bar –Used for termination of circuit grounded conductors.
36. Flush Locks –Used for locking of cabinet doors to allow entrance of qualified
personnel only.
37. Padlock Attachment –Used to lock breakers in the “off” or “on” position.
38. Closure Plate –Used to fill empty breaker spaces where “breakout” has been
removed.
4
39. Lock Off –Used to lock breakers in the “off” position for equipment maintenance or
servicing.
40. Handle Tie –Used to mechanically tie two or more breaker handles together to
assure common tripping.
1. The circuit breaker act as a switch aside from its being an over current protective
device.
2. When there is over current, the circuit breaker trips (cut) automatically and after
correcting the fault, it becomes readily available for switch on. Unlike the fuses
which has to be discarded and replace after it is busted.
3. Circuit breaker can be multiple poles and can be installed with 1, 2, or 3 poles,
which will simultaneously protect and switch one to three lines. The fuse on the
other hand, is a single pole put into a single wire and can protect only one single
electric line.
4. Circuit breaker position is easier to detect. It is closed, tripped or open right at
the handle.
5. The fuse on the other hand, is not easily detected because the melted fusible
element is inside the fuse casing.
6. Circuit breaker can be manually tripped so that in many cases it also acts as the
circuit switch.
A fuse is basically a short length of metal ribbon made of alloy with a low melting point,
and of a size that will carry a specified current indefinitely, but which will melt when a
larger current flow, due to overload or short circuit. When the ribbon inside the fuse
melts, the fuse is said to “blow”. When it blows, the circuit is open, just as if a wire had
been cut, or a switch opened, at the fuse location.
Circuit breakers operate using one or both of two principles. They are:
1. Thermal operation relies on the extra heat produced by high current warming a
bimetal strip, which bends to strip the operating contacts.
2. Magnetic operation is due to the magnetic field set up by a coil carrying the
current, which attracts an iron part to trip the breaker when the current becomes
large enough.
Directions: Answer the following questions by writing your answers in a sheet of pad
paper.
TEST I: Identification.
1.__________ The Automatic over-current device that trips on overloads or shorts and
is resettable.
2.__________ The Electrical equipment that carries or transfers current but does not
use it.
3.__________ The Current that flows from one conductor to ground or another
conductor because of an abnormal connection or arc between the two.
4.__________ The Weak link in the circuit that limits the amperage to a specified
amount.
5.__________ Larger than normal current flowing within the normal current paths
6.__________ Larger than normal current flowing outside the normal current path.
7.__________ Maximum voltages at which a device is designed to operate.
8.__________ Maximum available short-circuit current that an over-current device can
safely interrupt without damage to itself.
9.__________ Several removable metal rings that allow for the entrance of various
standard sizes of connectors into a cabinet.
10._________ A device or group of devices, or other means, by which the conductors
of a circuit can be disconnected from their source of supply.
TEST I: Identification.
1. Circuit breaker
2. Device
3. Fault current
4. Over-current protection
5. Overload
6. Short circuit
7. Voltage rating
8. Interrupting rating
9. Concentric knockout
10. Disconnecting means
The circuit breaker act as a switch aside from its being an over current
protective device.
When there is over current, the circuit breaker trips (cut) automatically and
after correcting the fault, it becomes readily available for switch on. Unlike
the fuses, which have to be discarded and replace after it, is busted.
Circuit breaker can be multiple poles and can be installed with 1, 2, or 3
poles, which will simultaneously protect and switch one to three lines. The
fuse on the other hand, is a single pole put into a single wire and can protect
only one single electric line.
Circuit breaker position is easier to detect. It is closed, tripped or open right
at the handle.
The fuse on the other hand, is not easily detected because the melted fusible
element is inside the fuse casing.
Circuit breaker can be manually tripped so that in many cases it also acts as
the circuit switch.
A fuse is basically a short length of metal ribbon made of alloy with a low melting
point, and of a size that will carry a specified current indefinitely, but which will melt
when a larger current flow, due to overload or short circuit. When the ribbon inside the
fuse melts, the fuse is said to “blow”. When it blows, the circuit is open, just as if a wire
had been cut, or a switch opened, at the fuse location.
Circuit breakers operate using one or both of two principles. They are:
Thermal operation relies on the extra heat produced by high current warming
a bimetal strip, which bends to strip the operating contacts.
Magnetic operation is due to the magnetic field set up by a coil carrying the
current, which attracts an iron part to trip the breaker when the current
becomes large enough.
11
Ratings Available for Fuse switches in both 250 and 600 volts
15 20 25 30 35 40 45 50 60 70 80
90 100 110 125 150 160 175 200 225 250 300
350 400 450 500 600 700 800 1000 1200 2000 2500
3000 4000 5000 6000
Circuiting guidelines
There are many ways of doing the circuitry but there is no optimum or perfect
way of doing it. There are certain guidelines promulgated by the National electrical
code (NEC) for flexible, economical and convenient layout: they are as follows:
1. The code requires sufficient circuitry to supply residential load of 30 watts per square
meter in buildings excluding porches, garages and basements.
2. The requirements of 30 watts per square meter works out to 80 sq. m. per 20 amps.
Circuit (2,400w) or 60 sq. m. for 15 amps. Circuit (1,800w).
3. Good practice suggests that a load should not exceed 1,600 watts for a 20 amp.
Circuit or 1,200 watts for 15 amp. Circuit, thus,
a) For a 15 amp. Circuit, -1,200w max. Load –40 sq. m. maximum area.
b) for a 20 amp. Circuit, -1,600 w. max. Load –53 sq. m. maximum area.
4. The NEC requires a minimum of 20 amp. Appliance circuit to feed all small appliance
outlets in the kitchen, pantry, dining and family room.
5. The general-purpose branch circuit should be 20 amps. Wired with no.12 AWG being
the minimum size of conductor wires for convenience outlet.
12
6. Circuit load on a 15 amp. Circuit should be limited to the values given on table 3-2
9. All kitchen outlets must be fed from at least two of these circuits.
10. The NEC further stipulates, “all receptacles are potential appliance and at least two
circuit should be supplied to serve them”.
11. Certain outlets in the room should be designed as appliance outlet such as:
a) All kitchen receptacles
b) Dining room receptacles
c) One in the living room
12.The NEC requires that at least one 20 amp. Circuit supplies the laundry outlets.
The name of the circuit breaker is taken from the medium or manner of
extinguishing the arc produced when the circuit breaker’s contacts opened.
15
1. Air blast type circuit breaker –uses dry and compressed air in
extinguishing the arc.
2. Air circuit breaker –interruption occurs in free air
3. Oil type circuit breaker –uses a special oil to extinguish the arc.
4. Gas type circuit breaker –uses SF6 (sulphur hexaflouride) gas to
extinguish the arc.
5. Vacuum type circuit breaker –uses vacuum container.
The ampacities shown are for wires in conduit, in cable, or buried directly
in the earth. If installed in free air, the ampacities are higher. Strictly speaking,
the ampacity of No. 14, No. 12, and No. 10 is greater than shown above because
the figures given actually represent the maximum permitted over current
protection. The difference is significant only when applying derating factors for
continuous loads, for more than three conductors in a raceway, or for ambient
temperatures over 30 deg. (86 deg. F).
E. Three-phase MLO
20
Information 4.2.4
Classification of fuses
Class H. Class H fuses, fig. 4 formerly was called NEC or code fuses. Most low cost,
common, standard nonrenewable one-time fuses are Class H fuses. Renewable- type
fuses also come under the Class H classification. Neither the interrupting rating nor
the notation Class H appears on the label of Class H fuse. This type of fuse is tested
by the Underwriters Laboratories on circuits that deliver 10,000 amperes ac. Class H
fuses is available with ratings ranging from 1 ampere to 600 amperes in both 250-
voltage and 600-volt ac types. Class H fuses is not current limiting.
A higher quality nonrenewable one-time fuse is also available, called a Class K5
fuse, which has 50, 000- ampere interrupting rating. It is easy to identify this better
grade of fuse because the Class K5 and its interrupting rating are marked on the label.
21
Class K. Class K fuses is group into three categories: K1, K5, and K9 fig.5 A
through D. These fuses may be UL listed with interrupting ratings in RMS symmetrical
amperes in values of 50,000, 100,000, or 200,000 amperes. For each K rating UL has
assigned a maximum level of peak let-through current (Ip) and energy as given by I2t.
Class K fuses has varying degrees of current-limiting ability, depending upon the K
rating. Class K1 fuses has the greatest current-limiting ability and Class K9 fuses the
least current-limiting ability. Checks of various fuse manufacturers’ literatures reveal
that Class K9 fuses are no longer being manufactured. Class K fuses may be listed as
time delay fuses as well. In this case, UL requires that the fuses have a minimum time
of delay of 10 seconds at 500% of the rated current. Class K fuses is available in
ratings ranging from 1/10 ampere to 600 amperes at 250- or 600-volts ac. Class K
fuses has the same dimensions as Class H fuses.
Class J. Class J fuses are current limiting and are so marked, Fig. 6 A and B. They are listed
by UL with an interrupting rating of 200,000 RMS symmetrical amperes. Some have an
especial listing identified by the letters “SP,” and have an interrupting rating of 300,000 RMS
symmetrical amperes. Certain Class J fuses are also considered to be dual-element, time delay,
and are marked “time-delay”. Class J fuses is physically smaller than Class H fuses. Therefore,
when a fuse holder is installed to accept a Class J fuse, it will be impossible to install a Class H
fuse in the fuse holder. The Underwriters Laboratories has assigned maximum values of I2t
and Ip that are slightly less than those for Class K1 fuses. Both fast acting, current-limiting
Class J fuses are available in ratings ranging from 1 ampere to 600 volts ac.
23
Class L. Class L fuses, fig. 7 A. B, C, are listed by UL in sizes ranging from 601
amperes to 6000 amperes at 600 volts ac. These fuses have specified maximum
values of I2t and Ip. They are current-limiting fuses and have an interrupting rating of
200,000 RMS symmetrical amperes. These bolt-type fuses are used in bolted pressure
contact switches. Class L fuses are available in fast acting, current-limiting time and a
time-delay, current-limiting type. Both types of Class L meet UL requirements. Some
Class L fuses have a special interrupting rating of 300,000 symmetrical amperes. The
fuse’s label will indicate the part number followed by the letters “SP”.
24
Fig. 7 Class L fuses. All Class L fuses are rated 600 volts. Listed is 601 to 6000
ampere rating. The smallest switch for Class L fuses is 800 amperes. Class L fuses
that have fuse elements rated at 600 amperes and less are available. These special
ampere-rated fuses are physically the same size as the 800-ampere size.
Class T. Class T fuses, fig. 8, are current-limiting fuses and are so marked. These
fuses are UL listed with an interrupting capacity of 200,000 RMS symmetrical amperes.
Class T fuses is physically smaller than Class H or Class J fuses. The configuration of
this type of fuse limits its use to fuse holders and switches that will reject all other types
of fuses.
Class T fuses rated 600 volts have electrical characteristics similar to those of
Class J fuses and are tested in similar manner by Underwriters Laboratories. Class T
fuses rated at 300 volts have lower peak let-through currents and I2t values than
comparable Class J fuses. Many series rated panel boards are listed by Underwriters
Laboratories with Class T mains. Because Class T fuses do not have lot of time delay,
they are sized according to the non-time delay fuse.
UL presently lists the 600-volts Class T fuses in sizes from 1 ampere to 800
amperes. UL lists the 300-volts Class T fuses in sizes from 1 ampere to 1,200
amperes. Common applications for Class T fuses for mains, feeders, and branch
circuits.
Class t 300-volt fuses may be used on 120/240-volt single-phase, 208/120-volt
three-phase four-wire wyes, and 240-volt three phase three wire delta systems. The
NEC permits 300-volts Class T fuses to be installed in single-phase line-to-neutral
circuits supplied from three-phase four-wire solidly grounded neutral systems where
25
the line-to neutral voltage does not exceed 300 volts. The NEC does not permit the
use of 300-volt Class T fuses for line-to-line or line-to-line-to-line applications on
480/277-volt three-phase four wire wyes, 480-volt three-phase three-wire, and any of
the systems where Class T 300-volt fuses are permitted.
Class G. Class G fuses, fig. 9, are cartridge fuses with small physical
dimensions. They are used in circuits of 300-volts or less to ground. Class G fuses
are available in sizes ranging from 0 ampere to 60 amperes and are UL listed at an
interrupting capacity of 100,000 RMS symmetrical amperes. To prevent overusing,
Class G fuses are size limiting within the four categories assigned to their ampere
ratings. Therefore, a fuse holder designed to accept a 15-ampere Type SC will not
accept a 20-ampere Type SC fuse; and a fuse holder designed to accept 20-ampere
Type SC fuse will no accept a 30-ampere Type SC fuse; and so on for the four
categories.
Class G fuses are current limiting. They may be used for the protection of
ballasts, electric heat, and similar loads. They are UL listed for branch circuit
protection.
26
Class CC. Class CC fuses is primarily used for control circuit protection of motor
control circuits, ballasts, small transformers, and so on. They are UL listed as branch
circuit fuses. Class CC fuses is rated at 600-volts or less and has 200,000-ampere
interrupting rating in sizes from 1/10 ampere through 30 amperes. These fuses
measure 11/2” x 13/32” and can be recognized by a “button” on one end of the fuse.
This “button” is unique to Class CC fuses. When a fuse block or fuse holder that has
the matching Class CC rejection feature is installed, it is impossible to insert any other
1 ½” x 13/32” fuses. Only a class fuse will fit into these special fuse blocks and fuse
holders. A Class CC fuse can be installed in a standard fuse holder.
Dual-element fuses are suitable for use on motor circuits and other circuits
having high-inrush characteristics. This type of fuse can be used as well for mains,
feeders, sub feeders, and branch circuits. Dual-element fuses may be used to provide
back-up protection for circuit breakers, bus duct, and other circuit components that lack
an adequate interrupting rating, bracing, or withstand rating. (Dual-element time-delay
fuse will hold five times it’s rating for 10 seconds)
29
Despite the disadvantages of the fuse over the circuit breaker, fuse has also
some advantages over circuit breaker, namely:
1. One major advantage of the fuse over circuit breaker is reliability and
stability. The fuse can stay on its position for years and act when called
on to act as designed.
2. The cost of the fuse is very much lower than that of the circuit breaker.
3. Ferrule-type cartridge fuse (standard ampere are: 15, 20, 30, 40, 60)
39
Directions: Answer the following questions by writing your answers in a sheet of pad
paper.
TEST I: Enumeration.
1. Enumerate the standard ampere rating for fuses and nonadjustable circuit
breakers.
2. Enumerate the Classifications/types of breakers according to mounting
method.
3. Enumerate the different kinds of fuses according to manner of operation.
4. Enumerate the important ratings when replacing fuses.
5. Enumerate the important ratings when replacing circuit breakers.
TEST I: Enumeration
15 20 25 30 35 40 45 50 60 70 80
90 100 110 125 150 160 175 200 225 250 300
350 400 450 500 600 700 800 1000 1200 2000 2500
3000 4000 5000 6000
1. a 2. f
3. i 4. b
5. g 6.d
7. e 8. h
1. Obtain the technical working drawing (electrical plan) from the concerned personnel
(instructor) then examine the nature of the work. (See sample below.)
2. After taking the plan, you are list down the needed materials, PPE’s, tools and
equipment needed in performing the task.
3. Upon listing, used the requisition form for materials and the borrowers slip to secure
your materials, tools, equipment and PPE’s from the supply and tool room. (see
sample below)
4. After securing the needed materials, tools, equipment and PPE’s, ask your
instructor where to install the working plan.
5. Place your materials, tools, equipment, and PPE’s in the most convenient location
to ease installation. Ask your instructor if you could start the installation.
1. They shall not be used in circuits exceeding 125 volts between conductors,
except on systems having grounded neutral with no conductors having more
than 150 volts to ground. This situation in the 120/208-volt system in the
commercial building covered in this text, or in the case of 120/240-volt, single-
phase system.
2. They shall have ampere ratings of 0 to 30 amperes.
3. They shall have a hexagonal configuration for ratings of 15 amperes and below.
4. The screw shell must be connected to the load side of the circuit.
5. Edison-base plug fuses may be used only as replacements in existing
installations where there is no evidence of overusing or tampering.
6. All new installations shall use fuse holders requiring Type S plug fuses or fuse
holders with a type s adapter inserted to accept Type S fuses only.
7. Type S plug fuses are classified 0 to 15 amperes; 16 to 20 amperes; 21 to 30
amperes.
19. Form the ground wire neatly so that it will not touch any moving part of the switch.
20. Strip back upper end of ground wire; install ground wire in switch terminal and
tighten.
21. Insert the fuses into the fuse clip. (Note: fuse clips must fit tightly on each fuse.
22. If finished, clean your work area, and return equipment, tools and materials to
proper storage.
1. Before mounting panel, open the desired number and size of knockout holes for the
conduit entry.
2. Install the desired size of conduit connector and tighten snugly.
3. Mount panel board in designated location.
4. Connect one piece of bare ground wire to the ground bar, allowing other end to
hang from bottom of panel. (Note: under actual installation, the lower end of the
ground wire would terminate at the grounding electrode.)
5. Strip back one end of each piece of insulated wire approximately 5/8-3/4”.
6. Install one piece of wire through the connector to the neutral bar connector; arrange
the wire neatly to lay back corner of the panel; then insert wire in neutral bar terminal
and tighten snugly. (Note: the neutral conductor should lay in the back corner of the
panel to leave adequate room for the other wires and breakers. It should also be
identified by white or gray tape.)
7. Install the remaining two wires through the connector, and insert wires in the main
breaker connectors.
8. Plug the breakers into the panel bus, plug breakers on both right and left side, start
at the top specifications. The main breaker should be placed on the upper most left
side of the panel board. (Note: arrange wire neatly, allowing room for the branch-
circuit conductors.)
9. Install wiring. (Note: extend all wires into the panel far enough to reach the neutral
or ground bar, especially the green wire after arranging it in the back corner of panel
down to the bar.)
10. Tag or mark by numbers each group of wires that goes to a specific breaker.
11. Fold back out of the way all branch circuit wires inside the panel to provide clear
working space inside panel.
12.Trim out panel board.
a.) Work the green wires one at a time, arranging them against back of panel
in corners and making right angle bends to the ground bar terminals.
b.) Cut strip, and insert wires into terminals; tighten snugly. (Note: this method
places this group of wires in the back of the panel, out of the way of neutral and circuit
wires; also, it gives the technician an organized procedure for doing the work neatly.)
c.) Work the white neutral wires one at a time, laying the wires near the green
wires in the back spaces and corners of the panel and making bends to the neutral or
ground bar.
d.) Cut, strip, and insert wires into terminals; tighten snugly.
Work the wires one at a time to the left two-pole breaker, forming the
wire to lay neatly toward the back and side of panel; make right angle
bends to bring wire horizontally toward proper breaker terminal; make
additional right angle bends to bring wires outward and then into
breaker.
Note: this procedure makes it easy to trace wires, provides enough wire length
to pull out and check loads with a clamp-on ammeter, and produces a neat,
professional-looking good.
13. Carefully dismantle the assembly and store parts in proper places.
14.Clean work area, and return equipment, tools and materials to proper storage.
1. Mark and layout boxes according to working drawing. (Note: Be sure to check the
NEC for installation of cable.
7. Strip cables in the boxes. (Note: be sure that at least 6” of conductor leaves the
face of the box.
8. In boxes 1 and 2, twist grounds together and install a green wire nut, leaving enough
pigtails to terminate on receptacle grounding terminal.
9. Strip ½” of insulation from neutral (white) conductors and twist in a 6” pigtail; install
a red wire nut over joint.
10. Terminate all conductors according to instructor’s demonstration. (Note: methods
may vary due to local codes.)
11. Install conduit connector in top of load center and terminate to 10/3 with ground
as the feeded conductors.
12. Double check to make sure all terminations are tight.
13. Clean work area, and return equipment and materials to proper storage.
14. Upon completion of work, have your instructor evaluate your work.
15. Carefully dismantle the assembly and store parts in proper places.
1. Heading letter and date –shows where the letter comes from and when it was
written.
2. Inside address –includes the name and address of the individual, group or
organization to whom you are writing, includes the courtesy title and name,
business or executive title and order of arrangement.
3. Salutation –is a friendly greeting that precedes the body of the letter.
4. Body –contains the whole message of the letter.
5. Complementary close –cordial ending after the body.
6. Signature area –signature of the writer above the typewritten name.
7. Reference initials –initials of the typist/encoder of the writer.
Prepare a written report of work completion to your instructor. Follow the format above
when writing a report.
55
Instructions: When you are ready to perform this task, ask your instructor to observe the
procedure and rate your performance using the criteria below.
RATING SHEET
REMARKS: 100
56