1 Performance Data
1 Performance Data
TYPE
RATINGS
STANDARDS
Insulation class: F
Coolant temperature: °C
ASSUMED DATA
EFFICIENCY in %
REACTANCES in %
XD (U): 227,8 XD’ (S): 39,5 XQ’’ (S): 26,8 X0 (U): 14,6
GENERAL
CONSTRUCTION
The stator frame is a rigid welded steel structure construction. The stator core is built of thin
electric sheet steel laminations which are insulated on both sides with heat-resistant inorganic
resin. The radial cooling ducts in the stator core ensure uniform and effective cooling of the
stator.
The rotor consists of a shaft, a hub and poles fixed on the hub. The shaft is machined of steel
forging. The poles are manufactured of 2 mm sheet steel and bolted to the hub. The pole
laminations are pressed together with steel bars which are welded to the end plates.
All windings are completely vacuum pressure impregnated with high quality epoxy resin. The
windings are provided with very strong bracing which withstands all expected mechanical and
electrical shocks and vibrations as well as chemicals. For more information ask for brochure
The stator frame and pedestals are made of fabricated steel. The stator frame is closed with
steel panels that guide the ventilation air and provide the degree of protection required. The
According to IM7303 the machine has two pedestal bearings. The feet are raised. Conical
shaft end.
FOUNDATION
The machine can be mounted using shimming, machined blocks, chock fast or on grouted sole
COOLING
The machine has two shaft mounted fans inside. The surrounding air is used for cooling. The
cooling air is drawn in through air filters (self charging electrostatic panels) and blown out to
CONTROL SYSTEMS
A three phase transformer supplies the excitation power to the field winding of the shaft driven
three phase exciter under the control of the digital automatic voltage regulator (AVR) type ABB
UNITROL 1000. A three phase voltage feedback is supplied by the voltage transformer. A
current feedback is provided by the current transformer. The transformers are installed in the
generator.
Thanks to a permanent magnet pole in the exciter no external power source is required for
initial excitation at start-up. The permanent magnet pole is already magnetized by the
rated values for re-magnetization given on the main connection diagram of the generator are
used. Thanks to Soft Start function it is possible to avoid over shooting at start-up.
Excitation power at short circuit is supplied by the CTs through rectifier. At normal voltage the
contactor is shorting the output of CTs (and preventing over excitation from these CTs). At a
line short circuit AVR will notice the voltage drop and connect CTs to give full short circuit
excitation. ECL-10 current limiter limits sustained short circuit current approx. 250 - 300 % of
rated current.
The circuit breaker protects the field circuit and the AVR against thermal overload and short
circuit. The over voltage relay will trip the circuit breaker in excess of pre-set limit of over
voltage and thus interrupt the supply of the excitation power to the AVR.
Auxiliary supply can be 9 to 250 Vac (3-phase), 50 to 250 Vac (1-phase) or 18 to 300 Vdc.
UNITROL 1000 AVR can be operated using digital and analogue I/O signals, from local panel
under Microsoft Windows. With CMT1000 the tuning of the AVR can be done easily, also by
using preset parameter files. The operation of a synchronous machine can be monitored and
controlled by an on-line power chart, four channel oscilloscope and by several measurements
and status indications with trending and memory functions. Measured data and parameters
UNITROL 1000 single channel AVR plate (dimensions 334x570 mm), includes:
Inputs
- Excitation On
- Gen CB status
- Setpoint Increase
- Setpoint Decrease
- PF mode enable
- Voltage matching
- Reset setpoint
Outputs
- Excitation On Status
- SW Alarm
TESTING
Testing is according to Wärtsilä Generator testing instruction 4V64L0037, IEC and ABB
internal requirements. Test items are listed below. The test may be observed by the customer
without extra charges. The test procedures are described in Machine Description Document
ROUTINE TESTS
1. Visual inspection *
5. Direction of rotation
stator winding
rotor winding
field winding
space heaters
Pt-100 (stator)
Pt-100 (others)
(Performing order of the tests may differ from the listed above.)
SURFACE TREATMENT
Surface treatment C3 according to the ISO 12944 standard, for standard industrial
environment.
DOCUMENTATION
3 ACCESSORIES
No pc/pcs Item
L=50 mm
1 1PT - Voltage transformer for exc.power & actual value meas. - KSG 3PU180/63/E
15000/165/110 V, 50 Hz
3 3CT - Current transformer for short circuit exc.power - KSG IFJ-3 1000
1000/7.5 A, CL 3/10P2.5, 50 Hz
ACFR-17 1000/1/1 A, 50 Hz
Core 1: 20VA, 5P10
The machined coupling half must be delivered latest 1 week before the delivery date of
2 Multidiameter cable entry seals (Rox System) for main cables - NLR...
1 Cable rack for phase cables and conduit for neutral cable
2 Control Valve and Pressure Meter for oil inlet - ZLS SVDN20 and UD1/0...400KPA
Recommended protection
Additional protection
1. Frequency disturbance
2. Reverse power