Pressure Vessel Sizing Calculation: Project: Al Rayyan Villa MEP Contractor: Lead Cooling Contracting & Trading

The document provides calculations to size a pressure vessel for a booster pump set for the Al Rayyan Villa project. It calculates the required vessel volume of 95.45 litres based on the mean flow of 3.5 L/s, head of 43.6 meters, cut-in pressure of 4 bar, cut-out pressure of 6 bar, and maximum pump starts per hour of 60. It recommends fitting two 100 litre pressure vessels.

Uploaded by

Mohammed Javid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
465 views1 page

Pressure Vessel Sizing Calculation: Project: Al Rayyan Villa MEP Contractor: Lead Cooling Contracting & Trading

The document provides calculations to size a pressure vessel for a booster pump set for the Al Rayyan Villa project. It calculates the required vessel volume of 95.45 litres based on the mean flow of 3.5 L/s, head of 43.6 meters, cut-in pressure of 4 bar, cut-out pressure of 6 bar, and maximum pump starts per hour of 60. It recommends fitting two 100 litre pressure vessels.

Uploaded by

Mohammed Javid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PRESSURE VESSEL SIZING CALCULATION

Project: AL RAYYAN VILLA

MEP Contractor: Lead Cooling Contracting & Trading

BOOSTER PUMP SET


Flow 3.5 L/S 1 No. of Duty Pump
Head 43.6 Meters 1 No. of Standby Pump

Q X 1000 X P1
V=
4 X Nmax X (DP+0.2)

V = Tank Volume in litres

Q = Mean Flow (M3/h) =


3
12.6 M /H

DP = Difference between cut in & cut out = 2 BAR


Nmax = Maximum starts/hour possible by the pump, For E-HM series pumps Nmax is 60

P1 Cut in = 4 Bar (From pump performance curve )


P1s Cut out = 6 Bar (From pump performance curve )

Q X 1000 X P1
V=
4 X Nmax X (DP+0.2)

50400
V=
528

V= 95.45 LITRES

Pumps are fitted with 2 nos. 100 litres vessel