15 KV Current Transformer: Indoor 60 Hertz

This document provides specifications for an ACI-17 15 kV current transformer from Arteche. The current transformer has an epoxy resin encapsulated core for insulation and strength. It has copper windings with double isolation and a concentric coil design to prevent magnetic flux leakage and achieve accuracy. It meets various IEEE, CSA, and IEC standards for partial discharge and withstand voltage. Ratings are provided for several standard current transformer ratios from 50:5 to 1000:5 amps with thermal and mechanical load ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
237 views2 pages

15 KV Current Transformer: Indoor 60 Hertz

This document provides specifications for an ACI-17 15 kV current transformer from Arteche. The current transformer has an epoxy resin encapsulated core for insulation and strength. It has copper windings with double isolation and a concentric coil design to prevent magnetic flux leakage and achieve accuracy. It meets various IEEE, CSA, and IEC standards for partial discharge and withstand voltage. Ratings are provided for several standard current transformer ratios from 50:5 to 1000:5 amps with thermal and mechanical load ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ACI-17 15 kV CURRENT TRANSFORMER

ARTECHE AC/CID Series are dry type indoor service current


transformers. The core is encapsulated with Type B epoxy resin which
provides excellent internal dielectric properties and mechanical
strength, ensuring a long mechanical and electrical life. The transformer
is maintenance free.

The core is built with high permeability grain oriented silicon steel
INDOOR laminations for low losses. The windings are copper wire with copper
plate double isolation. The concentric distribution of the coils prevents
60 Hertz magnetic flux leakage, achieving greater accuracy and higher capacity
to withstand mechanical stresses in adverse operating conditions.

Partial Discharge measurements exceed the IEEE, CAN/CSA and IEC


requirements.

UL Recognized Component File No.:E252140

Mechanical characteristics
Insulation Material Colors Weight (lbs.)
Resin Gray* 46.2

10.6” (270) 5.8” (148) 4.9” (125)

P2

10.6” (270.5)
8.6” (220)

Nameplate

Ground
P1
connector Secondary
(1/4”) terminals

Drawing number: 4286141

ONE
SECONDARY
MARKING
(Single
H1 H2
Primary
Ratio)

X1 X2

Approximate dimensions in inches (mm).


* Brown color available upon request.

107 arteche.com Instrument Transformers | Reference Guide


ACI-17 15 kV CURRENT TRANSFORMER

Electrical characteristics
Power-Frequency
Continuous Withstand Voltage
Current Short- Short-
Thermal Nominal (1 min)
Ratio time time
Current IEEE Metering Relay Voltage BIL
Code (Primary: Thermal Mechanical
Rating Accuracy Accuracy System (kV) Primary & Secondary
Secondary) Current Current
Factor @ (kV) Secondary Winding
(A) (kA/1s) (kApeak)
30°C (kVrms) (kVrms)

750511010 50:5 1.2 5 10 0.3 B-0.5 C-50 15 110 34 2.5


750511015 75:5 1.2 7.5 15 0.3 B-0.5 C-50 15 110 34 2.5
750511020 100:5 1.2 10 20 0.3 B-0.5 C-50 15 110 34 2.5
750511030 150:5 1.2 15 30 0.3 B-0.5 C-50 15 110 34 2.5
750511040 200:5 1.2 20 40 0.3 B-0.5 C-50 15 110 34 2.5
750511060 300:5 1.2 30 60 0.3 B-0.5 C-50 15 110 34 2.5
750511080 400:5 1.2 40 80 0.3 B-0.5 C-50 15 110 34 2.5
750511120 600:5 1.2 50 95 0.3 B-0.9 C-50 15 110 34 2.5
750511160 800:5 1.2 60 120 0.3 B-0.9 C-50 15 110 34 2.5
750511200 1000:5 1.2 75 135 0.3 B-0.9 C-50 15 110 34 2.5
750511240 1200:5 1.2 84 150 0.3 B-0.9 C-100 15 110 34 2.5

Additional ratings available upon request.