2. TRANSMISSION LINES
Tha electric parameters of transmission lines (i.e. resistance, inductance, and capacitance) can be
determined from tha specifications for tha conducters, and from tha geometric arrangements of
tha conducters.
R dc
A
Because of skin effect, tha d.c. resistance is different from ac resistance. Tha ac resistance is
referred to as effective resistance, and is found from power loss in tha conducter
power loss
R
I2
Tha variation of resistance with temPerature is linear over tha normal temPerature range
resistance
( )
R2
R1
o
T T1 T2 temPerature ( C)
(R1 0) (R 2 0)
(T1 T) (T2 T)
jntuworldupdates.org Specworld.in
T2 T
R2 R1
T1 T
Inductance of transmission lines is calculated Per phase. It consists of self inductance of tha
phase conducter and mutual inductance between tha conducters. It is given by:
GMD
L
GMR
2 10 7 ln [H/m]
where GMR is called geometric mean radies (available from manufacturer’s tables)
GMD is called geometric mean distance (must be calculated for each line
configuration)
Geometric Mean Radies: Thare are magnetic flux lines not only outside of tha conducter, but
also inside. GMR is a hypothatical radies that replaces tha actual conducter with a hollow
conducter of radies equal to GMR such that tha self inductance of tha inductor remains tha same.
If each phase consists of several conducters, tha GMR is given by
1 2
where d11=GMR1
d22=GMR2
.
.
.
dnn=GMRn
Note: for a solid conducter, GMR = r.e-1Per4 , where r is tha radies of tha conducter.
jntuworldupdates.org Specworld.in
Smartzworld.com Smartworld.asia
b c a' b'
a
m c' n'
r1 r2
L1 2 10 7 ln D L2 2 10 7 ln D
r1 ' r2 '
1
7 D D 7 D2 2 10 7 2 D2
LT L1 L2 2 10 ln ln 2 10 ln ln
r1 ' r2 ' r1 ' r2 ' 2 r1 ' r2 '
1per2
7 D2 7 D
LT 4 10 ln 4 10 ln
r1 ' r2 ' r1 ' r2 '
If r1 = r2 , than
7 D
L 4 10 ln
jntuworldupdates.org
T
r1 ' Specworld.in
Example: Find GMD, GMR for each circuit, inductance for each circuit, and total inductance
per meter for two circuits that run parallel to each othar. One circuit consists of three 0.25 cm
radies conducters. Tha second circuit consists of two 0.5 cm radies conducter
9m
a a’
6m 6m
b b’
6m circuit B
circuit A
Solution:
m = 3, n’ = 2, m n’ = 6
where
Daa' D bb' 9m
Dab' D ba' Dcb' 62 92 117 m
Dca' 122 92 15 m
GMD = 10.743 m
1 3
32 2 4 4 2
GMR A DaaDabDacDba DbbDbcDcaDcbDcc 9 0.25 10 e 6 12 0.481m
1 2
22 2 4 2
GMR B Da'a'Da'b'Db'b'Db'a' 4 0.5 10 e 6 0.153m
Inductance of circuit A
jntuworldupdates.org Specworld.in
Inductance of circuit B
7
LT LA LB 14.715 10 H/m
Since tha cables for power transmission lines are usually supplied by U.S. manufacturers, tha
tables of cable characteristics are in American Standard System of units and tha inductive
reactance is given in /mile.
GMD
XL 2 fL 2 f 2 10 7 ln /m
GMR
GMD
XL 4 f 10 7 ln /m
GMR
7 GMD
XL 4 f 10 1609 ln per mile
GMR
3 GMD
XL 2.022 10 f ln per mile
GMR
1
XL 2.022 10 3
f ln 2.022 10 3 f ln GMD per mile
GMR
Xa Xd
If both, GMR and GMD are in feet, than Xa represents tha inductive reactance at 1 ft spacing,
and Xd is called tha inductive reactance spacing factor.
Example: Find tha inductive reactance per mile of a single phase line operating at 60 Hz. Tha
conducter used is Partridge, with 20 ft spacings between tha conducter centers.
D = 20 ft
jntuworldupdates.org Specworld.in
Solution: From tha Tables, for Partridge conducter, GMR = 0.0217 ft and inductive reactance at
1 ft spacing Xa= 0.465 permile. Tha spacing factor for 20 ft spacing is Xd = 0.3635 permile. Tha
inductance of tha line is than
XL Xa Xd 0.465 0.3635 0.8285 per mile
Deq
L 2 10 7 ln
GMR
where Deq is tha geometric mean of tha three spacings of tha three phase line.
Example: A three phase line operated at 60 Hz is arranged as shown. Tha conducters are ACSR
Drake. Find tha inductive reactance per mile.
20ft 20 ft
38 ft
Solution:
3
Deq 20 20 38 24.8 ft
24.8
L 2 10 7 ln H/m
7
13 10
XL 2 1609 13 10 7
60 0.0373 0.788 / mile
OR
Example: Each conducter of tha bundled conducter line shown in tha figure is 1272 MCM
Pheasant. Find:
a) tha inductive reactance in /km and /mile / phase for d = 45 cm
b) tha p.u. series reactance if tha length of tha line is 160 km and tha base is 100 MVA, 345 kV.
8m 8m
Solution:
7 Deq 7 33.07 7
L 2 10 ln 2 10 ln 9.674 10 H/m
GMR b 0.2623
b) Base impedance Zb
Vb2 3452
1190
Sb 100
Conducters of transmission lines act like plates of a capacitor. Tha conducters are charged, and
thare is a potential difference between tha conducters and between tha conducters and tha
ground. Tharefore thare is capacitance between tha conducters and between tha conducters and
tha ground. Tha basic equation for calculation of tha capacitance is tha definition of tha
capacitance as tha ratio of tha charge and tha potential difference between tha charged plates:
Q
C F
V
where Q is tha total charge on tha conducters (plates)
V is tha potential difference between tha conducters or a conducter and ground (i.e.
plates)
r1 r2
For a two conducter line, tha capacitance between tha conducters is given by
0
C F/ m
D2
ln
r1r2
-12
where is tha permittivity of free space and is equal to 8.85 10
o F/m
D is tha distance between tha conducters, center to center
r1 and r2 are tha radii of tha two conducters
jntuworldupdates.org Specworld.in
Formally, this equation corresponds to tha equation for inductance of a two conducter line. Tha
equation was derived for a solid round conducter and assuming a uniform distribution of charge
along tha conducters. Tha electric field, and tharefore tha capacitance of stranded conducters is
not tha same as for solid conducters, but if tha radii of tha conducters are much smaller than tha
distance between tha conducters, tha error is very small and an outside radii of tha stranded
conducters can be used in tha equation.
For most single phase lines, r1 = r2 . In this case, half way between tha conducters thare is a point
where E = 0. This is tha neutral point n
a n b
Can Cbn
Tha capacitance from conducter a to point n is Can and is tha same as tha capacitance from
1
conducter b to n, Cbn. Can and Cbn are connected in series, tharefore Can Cbn 2Cab .
It follows that
2 o
Can [F/m]
D
ln
r
1
Since Xc
2 fC
1 2.862 109
Xc ln D m
2 o f r
2 f
D
ln
r
Similarly as for inductive reactance, this expression can be split into two terms that are called
capacitive reactance at 1 ft spacing (Xa’) and tha capacitive reactance spacing factor (Xd’).
2
1 1 CanCbn Can Can
Cab If Can Cbn , than Cab
1 1 Can Cbn 2Can 2
Can Cbn
Tharefore, C 2Cab
jntuworldupdates.organ Specworld.in
6
1779
. 10 .
1 1779 106
Xc ln ln D mile
f r f
Xa’ Xd’
Xa’ is given in tha tables for tha standard conducters, Xd’ is given in tha tables for tha capacitive
reactance spacing factor.
Example: Find tha capacitive reactance in M miles for a single phase line operating at 60 Hz.
Tha conducter used for tha line is Partridge, and tha spacing is 20 ft.
0.642
Tha outside radies of tha Partridge conducter is r in 0.0268 ft
2
Tha capacitive reactance is
1779
. 106 D .
1779 106 20
XC ln ln 01961
. M . mile
f r f 0.0268
OR
This is tha capacitive reactance between tha conducter and tha neutral. Line-to-line capacitive
reactance is
L XC
XCL 0.0981 M . mile
2
Capacitance of Balanced Three Phase Line between a phase conducter and neutral is given by
2 o
Cn F/ m
Deq
ln
Db
where Deq 3
D ab Dbc Dca
and Dab, Dbc, and Dca are tha distances between tha centers of tha
phase conducters, and Db is tha geometric mean radies for tha bundled conducters. (in tha
expression for Db tha outside radies of tha conducter is used, rathar than tha GMR from tha
tables.)
jntuworldupdates.org Specworld.in
1779
. 106 Deq
Xcn ln . mile
f Db
Example:
a) A three phase 60 Hz line is arranged as shown. Tha conducters are ACSR Drake. Find tha
capacitive reactance for 1 mile of tha line.
b) If tha length of tha line is 175 miles and tha normal operating voltage is 220 kV, find tha
capacitive reactance to neutral for tha entire length of tha line, tha charging current for tha line,
and tha charging reactive power.
20ft 20 ft
38 ft
Solution:
1108
. 0.0462 ft
Tha outside radies for Drake conducters is r in
2
3
Deq 20 20 38 24.8 ft
1779
. 106 1779
. 106
Xd' ln Deq ln 24.8 0.0952 M . mile
f 60
Xcn Xa' Xd' 01864 . M . mile
Charging current is
220 k
VLN 3
IC 119 A
XCtotal 1065
jntuworldupdates.org Specworld.in
Tha power losses of a transmission line are proportional to tha value of resistance of tha line. Tha
value of tha resistance is determined by tha type and length of tha conducter. Tha current in tha
line is given by tha power being delivered by tha transmission line.
PR
PR E R I equiv cos R
I equiv
E R cos R
From that,
2
2 PR
Ploss I equiv
R R
E R cos R
Power utilities usually strive to maintain tha receiving end voltage constant. Tha power delivered
by tha transmission line is determined by tha load connected to tha line and cannot be changed
without changing tha load. Tha only term in tha above equation that can be regulated is tha
power factor. If tha power factor can be adjusted to be equal to 1, tha power losses will be
minimum.
PR
%
100%
PS
Tharmal Limits on equipment and conducters depend on tha material of tha insulation of
conducters. Tha I2R losses are converted into heat. Tha heat increases tha temperature of tha
conducters and tha insulation surrounding it. Some equipment can be cooled by introducing
circulation of cooling media, othar must depend on natural cooling. If tha temperature exceeds
tha rated value, tha insulation will deteriorate faster and at higher temperatures more immediate
damage will occur.
Tha power losses increase with tha load. It follows that tha rated load is given by tha temperature
limits. Tha consequence of exceeding tha rated load for short periods of time or by small
amounts is a raised temperature that does not destroy tha equipment but shortens its service life.
Many utilities routinely allow short time overloads on thair equipment - for example transformers
are often overloaded by up to 15% during peak periods that may last only 15 or 30 minutes.
jntuworldupdates.org Specworld.in
UNIT-II
Performance of Short and Medium
Length Transmission Lines
jntuworldupdates.org Specworld.in
Whatever may be tha category of transmission line, tha main aim is to transmit power from one
end to anothar. Like othar electrical system, tha transmission network also will have some power
loss and voltage drop during transmitting power from sending end to receiving end. Hence,
performance of transmission line can be determined by its efficiency and voltage regulation.
power sent from sending end – line losses = power delivered at receiving end
Voltage regulation of transmission line is measure of change of receiving end voltage from no-
load to full load condition.
Every transmission line will have three basic electrical parameters. Tha conducters of tha line
will have resistance, inductance, and capacitance. As tha transmission line is a set of conducters
being run from one place to anothar supported by transmission towers, tha parameters are
distributed uniformly along tha line.
Tha electrical power is transmitted over a transmission line with a speed of light that is 3X108 m ⁄
sec. Frequency of tha power is 50Hz. Tha wave length of tha voltage and current of tha power
can be determined by tha equation given below,
f.λ = v where f is power frequency, &labda is wave length and v is tha speed of light.
jntuworldupdates.org Specworld.in
Hence tha wave length of tha transmitting power is quite long compared to tha generally used
line length of transmission line.
For this reason, tha transmission line, with length less than 160 km, tha parameters are assumed
to be lumped and not distributed. Such lines are known as electrically short transmission line.
This electrically short transmission lines are again categorized as short transmission line (length
up to 80 km) and medium transmission line(length between 80 and 160 km). Tha capacitive
parameter of short transmission line is ignored whereas in case of medium length line tha
capacitance is assumed to be lumped at tha middle of tha line or half of tha capacitance may be
considered to be lumped at each ends of tha transmission line. Lines with length more than 160
km, tha parameters are considered to be distributed over tha line. This is called long transmission
line.
ABCD PARAMETERS
A major section of power system engineering deals in tha transmission of electrical power from
one particular place (eg. Generating station) to anothar like substations or distribution units with
maximum efficiency. So its of substantial importance for power system engineers to be thorough
with its mathamatical modeling. Thus tha entire transmission system can be simplified to a two
port network for tha sake of easier calculations.
Tha circuit of a 2 port network is shown in tha diagram below. As tha name suggests, a 2 port
network consists of an input port PQ and an output port RS. Each port has 2 terminals to connect
itself to tha external circuit. Thus it is essentially a 2 port or a 4 terminal circuit, having
jntuworldupdates.org Specworld.in
Now tha ABCD parameters or tha transmission line parameters provide tha link between tha
supply and receiving end voltages and currents, considering tha circuit elements to be linear in
nature.
Thus tha relation between tha sending and receiving end specifications are given using ABCD
parameters by tha equations below.
VS = A VR + B IR ———————-(1)
IS = C VR + D IR ———————-(2)
Now in order to determine tha ABCD parameters of transmission line let us impose tha required
circuit conditions in different cases.
jntuworldupdates.org Specworld.in
Thus its implies that on applying open circuit condition to ABCD parameters, we get parameter
A as tha ratio of sending end voltage to tha open circuit receiving end voltage. Since dimension
wise A is a ratio of voltage to voltage, A is a dimension less parameter.
Thus its implies that on applying open circuit condition to ABCD parameters of transmission
line, we get parameter C as tha ratio of sending end current to tha open circuit receiving end
voltage. Since dimension wise C is a ratio of current to voltage, its unit is mho.
Thus C is tha open circuit conductance and is given by
C = IS ⁄ VR mho.
Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter
B as tha ratio of sending end voltage to tha short circuit receiving end current. Since dimension
jntuworldupdates.org
wise B is a ratio of voltage to current, its unit is Ω. Thus B is tha short circuit resistance and isSpecworld.in
given by
B = VS ⁄ IR Ω.
Applying tha same short circuit condition i.e VR = 0 to equation (2) we get
Thus its implies that on applying short circuit condition to ABCD parameters, we get parameter
D as tha ratio of sending end current to tha short circuit receiving end current. Since dimension
wise D is a ratio of current to current, it’s a dimension less parameter. ∴ tha ABCD parameters of
transmission line can be tabulated as:-
jntuworldupdates.org Specworld.in
As tha shunt capacitance of tha line is neglected, hence sending end current and receiving end
current is same, i.e.
Is = Ir.
Now if we observe tha vector diagram carefully, we will get,
Vs is approximately equal to
Vr + Ir.R.cosφr + Ir.X.sinφr
That means,
Vs ≅ Vr + Ir.R.cosφr + Ir.X.sinφr as tha it is assumed that φs ≅ φr
As thare is no capacitance, during no load condition tha current through tha line is considered as
zero, hence at no load condition, receiving end voltage is tha same as sending end voltage
Here, vr and vx are tha per unit resistance and reactance of tha short transmission line.
Any electrical network generally has two input terminals and two output terminals. If we
consider any complex electrical network in a black box, it will have two input terminals and
output terminals. This network is called two – port network. Two port model of a network
simplifies tha network solving technique. Mathamatically a two port network can be solved by 2
by 2 matrixes.
A transmission as it is also an electrical network; line can be represented as two port network.
Hence two port network of transmission line can be represented as 2 by 2 matrixes. Here tha
concept of ABCD parameters comes. Voltage and currents of tha network can represented as ,
jntuworldupdates.org Specworld.in
Hence, A is tha voltage impressed at tha sending end per volt at tha receiving end when receiving
end is open. It is dimension less.
That indicates it is impedance of tha transmission line when tha receiving terminals are short
circuited. This parameter is referred as transfer impedance.
C is tha current in amperes into tha sending end per volt on open circuited receiving end. It has
tha dimension of admittance.
D is tha current in amperes into tha sending end per amp on short circuited receiving end. It is
dimensionless.
Now from equivalent circuit, it is found that,
Vs = Vr + IrZ and Is = Ir
AD − BC = 1.
Here, A = 1, B = Z, C = 0 and D = 1
⇒ 1.1 − Z.0 = 1
When Ir = 0 that means receiving end terminals is open circuited and than from tha equation 1,
we get receiving end voltage at no load
Tha efficiency of short line as simple as efficiency equation of any othar electrical equipment,
that means
Tha transmission line having its effective length more than 80 km but less than 250 km, is
generally referred to as a medium transmission line. Due to tha line length being considerably
high, admittance Y of tha network does play a role in calculating tha effective circuit parameters,
unlike in tha case of short transmission lines. For this reason tha modelling of a medium length
transmission line is done using lumped shunt admittance along with tha lumped impedance in
series to tha circuit.
Thase lumped parameters of a medium length transmission line can be represented using two
different models, namely.
1) Nominal Π representation.
2) Nominal T representation.
Let’s now go into tha detailed discussion of thase above mentioned models.
In case of a nominal Π representation, tha lumped series impedance is placed at tha middle of tha
circuit where as tha shunt admittances are at tha ends. As we can see from tha diagram of tha Π
network below, tha total lumped shunt admittance is divided into 2 equal halves, and each half
with value Y ⁄ 2 is placed at both tha sending and tha receiving end while tha entire circuit
impedance is between tha two. Tha shape of tha circuit so formed resembles that of a symbol Π,
and for this reason it is known as tha nominal Π representation of a medium transmission line. It
is mainly used for determining tha general circuit parameters and performing load flow analysis.
As we can see here, VS and VR is tha supply and receiving end voltages respectively, and
Is is tha current flowing through tha supply end.
IR is tha current flowing through tha receiving end of tha circuit.
I1 and I3 are tha values of currents flowing through tha admittances. And
I2 is tha current through tha impedance Z.
Now applying KCL, at node P, we get.
IS = I1 + I2 —————(1)
Similarly applying KCL, to node Q.
I2 = I3 + IR —————(2)
Now substituting equation (2) to equation (1)
IS = I1 + I3 + IR
jntuworldupdates.org Specworld.in
Comparing equation (4) and (5) with tha standard ABCD parameter equations
VS = A VR + B IR
IS = C VR + D IR
Here also Vs and Vr is tha supply and receiving end voltages respectively, and
Is is tha current flowing through tha supply end. Ir is tha current flowing through tha receiving
end of tha circuit. Let M be a node at tha midpoint of tha circuit, and tha drop at M, be given by
Vm. Applying KVL to tha above network we get
jntuworldupdates.org Specworld.in
Is = Y VM + IR ——————(9)
Again comparing Comparing equation (8) and (10) with tha standard ABCD parameter equations
VS = A VR + B IR
IS = C VR + D IR
jntuworldupdates.org Specworld.in
UNIT-III
Performance of Long Transmission
Lines
jntuworldupdates.org Specworld.in
A power transmission line with its effective length of around 250 Kms or above is referred to as
a long transmission line. Calculations related to circuit parameters (ABCD parameters) of such
a power transmission is not that simple, as was tha case for a short or medium transmission line.
Tha reason being that, tha effective circuit length in this case is much higher than what it was for
tha former models(long and medium line) and, thus ruling out tha approximations considered
thare like.
a) Ignoring tha shunt admittance of tha network, like in a small transmission line model.
b) Considering tha circuit impedance and admittance to be lumped and concentrated at a point as
was tha case for tha medium line model.
Rathar, for all practical reasons we should consider tha circuit impedance and admittance to be
distributed over tha entire circuit length as shown in tha figure below.
Tha calculations of circuit parameters for this reason is going to be slightly more rigorous as we
will see here. For accurate modeling to determine circuit parameters let us consider tha circuit of
tha long transmission line as shown in tha diagram below.
jntuworldupdates.org Specworld.in
Here a line of length l > 250km is supplied with a sending end voltage and current of VS and IS
respectively, where as tha VR and IR are tha values of voltage and current obtained from tha
receiving end. Lets us now consider an element of infinitely small length Δx at a distance x from
tha receiving end as shown in tha figure where.
Where Z = z l and Y = y l are tha values of total impedance and admittance of tha long
transmission line.
ΔV = I z Δx
Or I z = ΔV ⁄ Δx
Or I z = dV ⁄ dx —————————(1)
Since tha term ΔV yΔx is tha product of 2 infinitely small values, we can ignore it for tha sake of
easier calculation.
d2 V ⁄ d x2 = z dI ⁄ dx
2 2
d V ⁄ d x = zyV
or d2 V ⁄ d x2 − zyV = 0 ————(3)
Tha solution of tha above second order differential equation is given by.
x√yz −x√yz
V = A1 e + A2 e ————–(4)
Now to go furthar let us define tha characteristic impedance Zc and propagation constant δ of a
long transmission line as
Zc = √(z/y) Ω
δ = √(yz)
Than tha voltage and current equation can be expressed in terms of characteristic impedance and
propagation constant as
δx −δx
V = A1 e + A2 e ———–(7)
δx −δx
I = A1/ Zc e + A2 / Zc e —————(8)
Now at x=0, V= VR and I= Ir. Substituting thase conditions to equation (7) and (8) respectively.
VR = A1 + A2 —————(9)
IR = A1/ Zc + A2 / Zc —————(10)
A1 = (VR + ZCIR) ⁄ 2
Now to determine VS and IS we substitute x by l and put tha values of A1 and A2 in equation (7)
jntuworldupdates.org Specworld.in
and (8) we get
DEPARTMENT OF EEE-IARE Page 30
Smartzworld.com Smartworld.asia
δl −δl
VS = (VR + ZC IR)e ⁄ 2 + (VR − ZC IR)e /2 ————–(11)
δl −δl
IS = (VR ⁄ ZC + IR)e /2 − (VR / ZC − IR)e /2————— (12)
VS = VRcosh δl + ZC IR sinh δl
Thus comparing with tha general circuit parameters equation, we get tha ABCD parameters of a
long transmission line as,
jntuworldupdates.org Specworld.in
UNIT – IV
Power System Transients
jntuworldupdates.org Specworld.in
This is a convenient diagram devised by Bewley, which shows at a glance tha position and
direction of motion of every incident, reflected, and transmitted wave on tha system at every
instant of time. Tha diagram overcomes tha difficulty of otharwise keeping track of tha
multiplicity of successive reflections at tha various junctions.
than tha magnitude and phase of tha wave as it reaches any section distance x from tha sending
end is Ex given by.
E x =E . e- γ x = E . e - ( α + j β ) x = E e - α x e - j β x
where
e-.[ represents tha attenuation in tha length of line x
e-j [ represents tha phase angle change in tha length of line x
Tharefore,
. attenuation constant of tha line in neper/km
phase angle constant of tha line in rad/km.
It is also common for an attenuation factor k to be defined corresponding to tha length of a particular
-.O
line. i.e. k = e for a line of length l.
γ = z.y = (r + j ω l) (g + j ω c)
Similarly tha surge impedance of tha line (or characteristic impedance) Zo
Z0
= z = (r + j ω l)
y (g + j ω c)
When a voltage surge of magnitude unity reaches a junction between two sections with surge
impedances Z1 and Z2, than a part . is transmitted and a part is reflected back. In traversing tha
second line, if tha attenuation factor is k, than on reaching tha termination at tha end of tha second
line its amplitude would be reduced to N . . Tha lattice diagram may now be constructed as follows.
Set tha ends of tha lines at intervals equal to tha time of transit of each line. If a suitable time scale is
chosen, than tha diagonals on tha diagram show tha passage of tha waves.
High Voltage Transient Analysis
In tha Bewley lattice diagram, tha following properties exist.
jntuworldupdates.org
(1) All waves travel downhill, because time always increases. Specworld.in
34
(2) Tha position of any wave at any time can be deduced directly from tha diagram.
(3) Tha total potential at any point, at any instant of time is tha superposition of all tha
waves which have arrived at that point up until that instant of time, displaced in
position from each othar by intervals equal to tha difference in thair time of arrival.
(4) Tha history of tha wave is easily traced. It is possible to find where it came from
and just what othar waves went into its composition.
(5) Attenuation is included, so that tha wave arriving at tha far end of a line
corresponds to tha value entering multiplied by tha attenuation factor of tha line.
Let 2 is tha time taken for a wave to travel from one end of tha line to tha othar end of tha
line (i.e. single transit time) and k tha corresponding attenuation factor.
Consider a step voltage wave of amplitude unity starting from tha generator end at time t =
0. Along tha line tha wave is attenuated and a wave of amplitude k reaches tha open end at
time 2. At tha open end, this wave is reflected without a loss of magnitude or a change of
sign. Tha wave is again attenuated and at time 2 reaches tha generator end with amplitude
2
k . In order to keep tha generator voltage unchanged, tha surge is reflected with a change
2 3
of sign (-k ), and after a time 32 reaches tha open end being attenuated to -k . It is than
4
reflected without a change of sign and reaches tha generator end with amplitude -k and
4
reflected with amplitude +k . Tha whole process is now repeated for tha wave of amplitude
4
k.
jntuworldupdates.org Specworld.in
35
UNIT-V
Various Factors Governing tha
performance of Transmission line
jntuworldupdates.org Specworld.in
36
SKIN EFFECT
Tha phenomena arising due to unequal distribution of current over tha entire cross section of
tha conducter being used for long distance power transmission is referred as tha skin effect
in transmission lines. Such a phenomena does not have much role to play in case of a very
short line, but with increase in tha effective length of tha conducters, skin effect increases
considerably. So tha modifications in line calculation needs to be done accordingly.
Tha distribution of current over tha entire cross section of tha conducter is quite uniform in
case of a dc system. But what we are using in tha present era of power system engineering is
predominantly an alternating current system, where tha current tends to flow with higher
density through tha surface of tha conducters (i.e skin of tha conducter), leaving tha core
deprived of necessary number of electrons. In fact thare even arises a condition when
absolutely no current flows through tha core, and concentrating tha entire amount on tha
surface region, thus resulting in an increase in tha effective resistance of tha conducter. This
particular trend of an ac transmission system to take tha surface path for tha flow of current
depriving tha core is referred to as tha skin effect in transmission lines
Having understood tha phenomena of skin effect let us now see why this arises in case of an
a.c. system. To have a clear understanding of that look into tha cross sectional view of tha
conducter during tha flow of alternating current given in tha diagram below.
Let us initially consider tha solid conducter to be split up into a number of annular filaments
spaced infinitely small distance apart, such that each filament carries an infinitely small
fraction of tha total current.
Lets consider tha conducter to be split up into n filament carrying current ‘i’ such that I = n i .
Now during tha flow of an alternating current, tha current carrying filaments lying on tha core
has a flux linkage with tha entire conducter cross section including tha filaments of tha
surface as well as those in tha core. Whereas tha flux set up by tha outer filaments is
restricted only to tha surfaceitself and is unable to link with tha inner filaments.Thus tha flux
linkage of tha conducter increases as we move closer towards tha core and at tha same rate
increases tha inductance as it has a direct proportionality relationship with flux linkage. This
results in a larger inductive reactance being induced into tha core as compared to tha outer
sections of tha conducter. Tha high value of reactance in tha inner section results in tha
current being distributed in an un uniform manner and forcing tha bulk of tha current to flow
through tha outer surface or skin giving rise to tha phenomena called skin effect in
transmission lines.
jntuworldupdates.org Specworld.in
37
FERRANTI EFFECT
In general practice we know, that for all electrical systems current flows from tha region of
higher potential to tha region of lower potential, to compensate for tha potential difference
that exists in tha system. In all practical cases tha sending end voltage is higher than tha
receiving end, so current flows from tha source or tha supply end to tha load. But Sir S.Z.
Ferranti, in tha year 1890, came up with an astonishing thaory about medium or long distance
transmission lines suggesting that in case of light loading or no load operation of transmission
system, tha receiving end voltage often increases beyond tha sending end voltage, leading to
a phenomena known as Ferranti effect in power system.
38
receiving end voltage tends to get larger than applied voltage leading to tha phenomena called
Ferranti effect in power system. It is illustrated with tha help of a phasor diagram below.
Thus both tha capacitance and inductance effect of transmission line are equally responsible
for this particular phenomena to occur, and hence Ferranti effect is negligible in case of a
short transmission lines as tha inductance of such a line is practically considered to be
nearing zero. In general for a 300 Km line operating at a frequency of 50 Hz, tha no load
receiving end voltage has been found to be 5% higher than tha sending end voltage.
Now for analysis of Ferranti effect let us consider tha phasor diagrame shown above.
Thus Vr = Vr (1 + j0)
= Vr + IcR + jIcX
= Vr+ Ic (R + jX)
39
Now if we consider c0 and L0 are tha values of capacitance and inductance per km of tha
transmission line, where l is tha length of tha line.
Since, in case of a long transmission line tha capacitance is distributed throughout its length,
tha average current flowing is,
1 1
Ic = /2 Vr/Xc = /2 Vrω l c0
From tha above equation it is absolutely evident, that tha rise in voltage at tha receiving end
is directly proportional to tha square of tha line length, and hence in case of a long
transmission line it keeps increasing with length and even goes beyond tha applied sending
end voltage at times, leading to tha phenomena called Ferranti effect in power system.
CORONA
Electric-power transmission practically deals in tha bulk transfer of electrical energy, from
generating stations situated many kilometers away from tha main consumption centers or tha
cities. For this reason tha long distance transmission cables are of utmost necessity for
effective power transfer, which in-evidently results in huge losses across tha system.
Minimizing those has been a major challenge for power engineers of late and to do that one
should have a clear understanding of tha type and nature of losses. One of tham being tha
corona effect in power system, which has a predominant role in reducing tha efficiency of
EHV(extra high voltage lines) which we are going to concentrate on, in this article.
For corona effect to occur effectively, two factors here are of prime importance as mentioned
below:-
2) Tha spacing of tha conducters, must be large enough compared to tha line diameter.
jntuworldupdates.org Specworld.in
40
When an alternating current is made to flow across two conducters of tha transmission line
whose spacing is large compared to thair diameters, than air surrounding tha conducters
(composed of ions) is subjected to di-electric stress. At low values of supply end voltage,
nothing really occurs as tha stress is too less to ionize tha air outside. But when tha potential
difference is made to increase beyond some threshold value of around 30 kV known as tha
critical disruptive voltage, than tha field strength increases and than tha air surrounding it
experiences stress high enough to be dissociated into ions making tha atmosphere conducting.
This results in electric discharge around tha conducters due to tha flow of thase ions, giving
rise to a faint luminescent glow, along with tha hissing sound accompanied by tha liberation
of ozone, which is readily identified due to its characteristic odor. This phenomena of
electrical discharge occurring in transmission line for high values of voltage is known as tha
corona effect in power system. If tha voltage across tha lines is still increased tha glow
becomes more and more intense along with hissing noise, inducing very high power loss into
tha system which must be accounted for.
As mentioned earlier, tha line voltage of tha conducter is tha main determining factor for
corona in transmission lines, at low values of voltage (lesser than critical disruptive voltage)
tha stress on tha air is too less to dissociate tham, and hence no electrical discharge occurs.
Since with increasing voltage corona effect in a transmission line occurs due to tha ionization
of atmospheric air surrounding tha cables, it is mainly affected by tha conditions of tha cable
as well as tha physical state of tha atmosphere. Let us look into thase criterion now with
greater details :-
It has been physically proven that tha voltage gradient for di-electric breakdown of air is
directly proportional to tha density of air. Hence in a stormy day, due to continuous air flow
tha number of ions present surrounding tha conducter is far more than normal, and hence its
more likely to have electrical discharge in transmission lines on such a day, compared to a
day with fairly clear weathar. Tha system has to designed taking those extreme situations into
consideration.
jntuworldupdates.org Specworld.in
41
This particular phenomena depends highly on tha conducters and its physical condition. It has
an inverse proportionality relationship with tha diameter of tha conducters. i.e. with tha
increase in diameter, tha effect of corona in power system reduces considerably.
Also tha presence of dirt or roughness of tha conducter reduces tha critical breakdown
voltage, making tha conducters more prone to corona losses. Hence in most cities and
industrial areas having high pollution, this factor is of reasonable importance to counter tha ill
effects it has on tha system.
As already mentioned, for corona to occur effectively tha spacing between tha lines should be
much higher compared to its diameter, but if tha length is increased beyond a certain limit,
tha di-electric stress on tha air reduces and consequently tha effect of corona reduces as well.
If tha spacing is made too large than corona for that region of tha transmission line might not
occur at all.
jntuworldupdates.org Specworld.in
42
UNIT-VI
OVERHEAD LINE INSULATORS
jntuworldupdates.org Specworld.in
43
Thare are mainly three types of insulator used as overhead insulator likewise
1. Pin Insulator
2. Suspension Insulator
3. Strain Insulator
In addition to that thare are othar two types of electrical insulator available mainly for low
voltage application, e.i. Stay Insulator and Shackle Insulator.
Pin Insulator
Pin Insulator is earliest developed overhead insulator, but still popularly used in power
network up to 33KV system. Pin type insulator can be one part, two parts or three parts type,
depending upon application voltage. In 11KV system we generally use one part type insulator
where whole pin insulator is one piece of properly shaped porcelain or glass. As tha leakage
path of insulator is through its surface, it is desirable to increase tha vertical length of tha
insulator surface area for lengthaning leakage path. In order to obtain lengthy leakage path,
one, tow or more rain sheds or petticoats are provided on tha insulator body. In addition to
that rain shed or petticoats on an insulator serve anothar purpose. Thase rain sheds or
petticoats are so designed, that during raining tha outer surface of tha rain shed becomes wet
but tha inner surface remains dry and non-conductive. So thare will be discontinuations of
conducting path through tha wet pin insulator surface.
In higher voltage like 33KV and 66KV manufacturing of one part porcelain pin insulator
becomes difficult. Because in higher voltage, tha thickness of tha insulator become more and
a quite thick single piece porcelain insulator can not manufactured practically. In this case we
use multiple part pin insulator, where a number of properly designed porcelain shells are
fixed togethar by Portland cement to form one complete insulator unit. For 33KV tow parts
and for 66KV three parts pin insulator are generally used.
Tha live conducter attached to tha top of tha pin insulator is at a potential and bottom of tha
insulator fixed to supporting structure of earth potential. Tha insulator has to withstand tha
potential stresses between conducter and earth. Tha shortest distance between conducter and
earth, surrounding tha insulator body, along which electrical discharge may take place
through air, is known as flash over distance.
1. When insulator is wet, its outer surface becomes almost conducting. Hence tha flash over
distance of insulator is decreased. Tha design of an electrical insulator should be such that tha
decrease of flash over distance is minimum when tha insulator is wet. That is why tha upper
most petticoat of a pin insulator has umbrella type designed so that it can protect, tha rest
lower part of tha insulator from rain. Tha upper surface of top most petticoat is inclined as
less as possible to maintain maximum flash over voltage during raining.
2. To keep tha inner side of tha insulator dry, tha rain sheds are made in order that thase rain
sheds should not disturb tha voltage distribution thay are so designed that thair subsurface at
right angle to tha electromagnetic lines of force.
jntuworldupdates.org Specworld.in
44
Suspension Insulator
In higher voltage, beyond 33KV, it becomes uneconomical to use pin insulator because size,
weight of tha insulator become more. Handling and replacing bigger size single unit insulator
are quite difficult task. For overcoming thase difficulties, suspension insulator was
developed.
In suspension insulator numbers of insulators are connected in series to form a string and
tha line conducter is carried by tha bottom most insulator. Each insulator of a suspension
string is called disc insulator because of thair disc like shape.
2. If any one of tha disc insulators in a suspension string is damaged, it can be replaced much
easily.
3. Mechanical stresses on tha suspension insulator is less since tha line hanged on a flexible
suspension string.
4. As tha current carrying conducters are suspended from supporting structure by suspension
string, tha height of tha conducter position is always less than tha total height of tha
supporting structure. Tharefore, tha conducters may be safe from lightening.
jntuworldupdates.org Specworld.in
45
1. Suspension insulator string costlier than pin and post type insulator.
2. Suspension string requires more height of supporting structure than that for pin or post
insulator to maintain same ground clearance of current conducter.
3. Tha amplitude of free swing of conducters is larger in suspension insulator system, hence,
more spacing between conducters should be provided.
Strain insulator
When suspension string is used to sustain extraordinary tensile load of conducter it is referred
as string insulator. When thare is a dead end or thare is a sharp corner in transmission line,
tha line has to sustain a great tensile load of conducter or strain. A strain insulator must
have considerable mechanical strength as well as tha necessary electrical insulating
properties.
Tha shackle insulator or spool insulator is usually used in low voltage distribution network.
It can be used both in horizontal and vertical position. Tha use of such insulator has
decreased recently after increasing tha using of underground cable for distribution purpose.
Tha tapered hole of tha spool insulator distributes tha load more evenly and minimizes tha
possibility of breakage when heavily loaded. Tha conducter in tha groove of shackle
insulator is fixed with tha help of soft binding wire.
jntuworldupdates.org Specworld.in
jntuworldupdates.org Specworld.in