Compilation of Plates For Building Design
Compilation of Plates For Building Design
QUEZON CITY
CE413
BUILDING DESIGN
COMPILATION OF PLATES
SUBMITTED BY:
ALDRIN P. ORIGENES
CE42S2
SUBMITTED TO:
WC LAV
LAV
HB
KS
RISER
RISER
LAV WC ss LAV WC ss
WM R
RISE
GV ss
R
RISE WC
LAV LAV
WC HB
KS
R
RISE
ss
C
R LAV W
RISE
ss
WC
LAV
PLATE NO. 3
WASTE WATERLINE PLAN
------------------------------------------------------------------------------------
PLATE NO. 4
WASTE WATERLINE ISOMETRIC
ST
PUBLIC
DRAIN SYSTEM
WC
LAV
LAV
WC
DP 6ӯ
DP 6ӯ
KS
DP 6ӯ DP
DP 6ӯ
LAV LAV
WC WC
SUPPLEMANTARY PLATE ACTIVITY:
WATER SUPPLY PIPE SIZE CALCULATIONS
TECHNOLOGICAL INSTITUTE OF THE PHILIPPINES
QUEZON CITY
CE413
BUILDING DESIGN
SUBMITTED BY:
ALDRIN P. ORIGENES
CE42S2
SUBMITTED TO:
1.57
ESTIMATED WATER DEMAND = 1.57
LPS
Step 5: Pressure available in water supply pipes
Calculate the pressure available for friction loss in the water supply pipes by subtracting the sum of loss in
static pressure and the pressure to be maintained at the highest fixture from the average minimum daily
service pressure. The result will be the pressure available for friction loss in the supply pipes, if no water
meter is used. If a meter is to be installed, the friction loss in the meter for the estimated maximum demand
should also be subtracted from the service pressure to determine pressure loss available for friction loss in
the supply pipes.
32mm
1.57
77.17
PLATE NO. 5
LIGHTING PLAN
------------------------------------------------------------------------------------
PLATE NO. 6
POWER PLAN
Sn
Sl HB
Sm S1 S2
S jk
S45
Syz S3
Shi
M
PANEL
BOARD
Sg Sr
SERVICE ENTRANCE
M ELECTRIC KW METER
Sq
Sf
Sop PANEL BOARD
Sc Sde 2 Sv
Sstu # CIRCUIT HOMERUN
Swx
1
S 1 GANG SWITCH
Sab
S678
S2 2 GANG SWITCH
100 W
INCANDESCENT LIGHT
DUPLEX OUTLET
HB
5
4 8
9
ACU
PANEL
M
BOARD
SERVICE ENTRANCE
M ELECTRIC KW METER
7 PANEL BOARD
10
6 # CIRCUIT HOMERUN
ACU
ACU
3
S 1 GANG SWITCH
S2 2 GANG SWITCH
100 W
INCANDESCENT LIGHT
DUPLEX OUTLET
TECHNOLOGICAL INSTITUTE OF THE PHILIPPINES
QUEZON CITY
CE413
BUILDING DESIGN
PLATE NO. 7
Load Schedule and Single-Line Diagram
SUBMITTED BY:
ALDRIN P. ORIGENES
CE42S2
SUBMITTED TO:
Hence, applying 100% for the first 10kW load gives us the same load of 10kW or 10000
watts. Deducting 10kW from the 13198 watts gives us 3198 watts. Applying 40% for the
3198 watts remaining load gives us 1279.2 watts.
Given that there are two circuits which are dedicated for each 1 hp air-conditioner
connected to each circuits, we have 746 watts for each circuit. Applying 100% demand
factor for air-conditioner loads based from the table above, we have 2238 watts.
Summing up the initial 10000 watts load, the 3198 watts from the remaining load in
excess of the 10kW applied with 40% demand factor, and the 2238 watts from the air-
conditioner load, gives us 15436 watts. From this calculated value, we still need to add
25% of the largest motor load among all connected electrical equipment. Hence, adding
25% of the 746 watts load of an air-conditioner to the previously calculated 15436 watts,
gives us 15622.5 watts.
Let's calculate the current load by dividing the current load by the voltage. According to
the provisions in the Philippine Electrical Code (PEC), the standard nominal voltage is
230V for residential services. Hence, dividing 15622.5 watts by 230V gives us 67.92
amperes.
Step 2: Determine the appropriate size of conductor wires: main
feeder and neutral line
Let us focus on the column which corresponds to the TW type of wire having pure
copper conductor core. For the 67.92 ampere requirement, the 38.0mm2 TW
wire having an ampere capacity or ampacity of 100 amperes is appropriate. According
to code, if the computed load exceeds 10000 watts, the conductor and the overcurrent
protection shall be rated not less than 100 amperes.
For the neutral conductors, it is stated in the code that neutral conductors shall have an
ampacity of not less than 70% of the ungrounded (live wire) conductor or two trade size
smaller than the ungrounded conductor. Given these two conditions, let's determine the
sizes of wires for each condition. For the first one that is less than 70% of the ampacity
of the conductor wire (main feeder), it is taken as 70 amperes since 70% of the 100
amperes capacity of the main feeders is 70 amperes. Using 70 amperes, we shall
use 22mm2 TW wire. On the other hand, two trade size smaller than the 38mm2 TW
conductor wire (main feeder) gives us 22mm2 TW wire based from the table on
conductor wire sizes. Since the ampacity of the neutral wire should not be less than
either of these two conditions, and both conditions came up with the same conductor
size, we shall use 2 pieces 38mm2 TW wire for the main feeder and one piece
22mm2 TW wire for the neutral line both for the service entrance.
Step 3: Determine the appropriate size of conduit pipe
For the service entrance, we'll use three pieces of wire for its main feeders and neutral
line. It was obtained that the appropriate size for two main feeders is 38.0mm2 while the
appropriate size of one neutral line is 22.0mm2. Using the larger size wire and three
pieces of wire, we shall use 32mm diameter as the appropriate minimum size of conduit
pipe.
It = 100 Amperes. Use 2-38 mm ² TW copper wire and 1-8 mm ² TW copper wire for Main and
Neutral Feeder respectively, one 100 ampere 2 pole, 3 wire, 250 volts breaker