TECHNICAL SPECIFICATION
OF
33/11KV MOBILE SUB-STATION
1×10MVA
1×16MVA
1. GENERAL
1.2 STANDARDS
The applicable standard to design the equipments and accessories shall be the latest IEC
recommendation .
1.3 SCHEDULES
The tenderer shall duly fill in the schedules of guaranteed technical particulars , prices ,
delivery time schedules and deviations attached to this specification . Incomplete tenders will be
rejected.
2. General Requirements:
The materials shall be of first class quality and designed for continuous satisfactory
operation as continuity of supply is of prime importance and to operate satisfactorily under
variation of load, voltage and short circuit or other conditions which may occur on the system
provided that these variations are within the assigned rating of the apparatus. The materials used
shall be suitable for the following climatic conditions:
Maximum 92% at 40 °C
Minimum 12%
Yearly average 44%
2.4 Altitudes:
The equipments shall be suitable for outdoor installations and subjected to frequent sand
storms and heavily polluted atmospher.
(1-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
3. TECHINCAL REQUIREMENT
b- 11 KV system
Nominal voltage 11000 volts
Highest system voltage 12000 volts
System 3-phase,3 wire with neutral earthed through an earthing resistance
of 21.1 ohm to limit earth fault current to 300Amps.
Short circuit level 25 KA r.m.s at 11000 volts
c-L.T.System
Nominal voltage 416 volts + 6%, -10%
System 3- phase, 4 wire with neutral solidly earthed
Short circuit level 35 KA r.m.s at 400 volts
(2-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
current of 5 AMP. The third shall be designed for differential protection with rated current of 1
AMP. Of special class with suitable accuracy class and a saturation factor protecting the
instrument in case of short circuit in the main installation , and the protective CT shall ensure
correct operation up to the maximum fault current which can be attained or any developed C.T
to fulfill the above requirements.
All indicating instruments must be water and dust proof designed for tropical climate and
capable of continuous operation at full load current as well by fault current.
All relays shall be of ELECTRONIC type. Relays shall be of withdrawable type to carry out
routine tests in service. and for early replacement. Additional protection relay without auxiliary
supply or supplied through capacitor storage unit shall be added to operate the protection when
there is no D .C supply in the substation .
7. PROTECTION RELAYS:
7.1 ALL panels shall be provided with over current and earth fault relay (2 O/C + 1E /F) of
IDMTL type as follows:-
Time range 0 – 3 sec.
Current setting for O/C 30-200 % × In
Current setting for E/F 5-40% × In
Instantaneous element 400-1600%(when required)
7.2 Under voltage relay on the 33kv side to trip the 33kv C. B. in case of supply voltage failure.
• Earth fault alarm relay self rest of two normally open contact for local and remote
alarm should be connected to the open delta winding of V.T on the 11kv side.
• 7.3 Transformer Neutral point. this protection shall be definite time earth fault
relay connected to the C. T. of the neutral earthing resistor to make trip of 33kv
C.B , in case of earth fault
• 7.4 Differential protection for the transformer.
8. SWITCHGEAR:
8.1 The switchgear shall comply with IEC 60289, completely metal- clad type with suitable air
insulated bus bar covered by proper insulation assigned for indoor installation equipped with
vacuum type circuit breaker. The switchgear shall be provided with suitable interlocks and
adequate safety devices to prevent access to the live compartment. 33 KV and 11Kvcircuit
breakers to be withdrawable type. A set of metal shutters shall be provided to cover all live parts.
Shutters shall open automatically by positive drive initiated by the movement of circuit breaker
carriage. The circuit breaker should be fixed with suitable fixation facility in test position during
transportation of mobile substation in order to protect the plug and socket isolating devices.
8.2 CIRCUIT BREAKER OPERATING MECHANISM:-
Circuit breaker operating mechanism shall be of the spring powered stored energy. Each
equipment shall be provided with visual indicating device to show the circuit breaker "Open" or
"closed" it shall operative when the circuit breaker is in the "service" "isolated" and "earthed"
positions.
(3-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
It shall be possible to complete the closing tripping indication and interlock circuits when
the circuit breaker is isolated . Locking facilities shall be provided so that the circuit breaker can
be locked in each position.
The closing mechanism shall be provided with electrical release coils and shall be of "trip
free" type. It shall be possible to charge the mechanism spring with circuit breaker ineither the
"open" or the "closed" position . In normal operation the recharging of the operating spring shall
be commenced immediately and automatically upon completion of the circuit breaker closure . A
visual mechanical indicating device shall be provided to indicated the state of the spring " spring
charged" when the spring is in condition to close the C.B and "spring free" when the spring not
in a condition to close the C.B.
The mechanism shall be fitted with local manual spring release preferably by push botton,
shrouded to prevent inadvertent operation . The mechanism shall be suitable for motor and hand
rewinding (motor should be for a system of 220 V A.C) and shall be suitable for remote control
for both closing and opening operations .
9. TRANSFORMER:
9.1 TRANSFORMER SPECIFICATION
The transformer and its associated equipment shall comply with the latest issue of IEC6076.
It should be as slim as possible to suit the requirement of the substation. The transformer shall
have the following characteristics:
(4-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
It shall not be possible for the tap changer to be left in an intermediate position. The tap
changer control circuit should be provided with protective device against short circuit when the
tap changer is in operation. (To prevent operation of tap changer during short circuit ).
The mechanism, fuses, relays and control equipment shall be housed in a suitable weather
proof metallic cabinet mounted on the transformer .
9.4 PAINTING
A primary coat shall be applied immediately after cleaning all ungalvanized metallic parts
thoroughly.
An oil and weather resistance type second coat shall then be applied and the transformer finished
in aluminum metallic paint .
(5-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
for any transformer with total losses less than 100% of the guaranteed losses, no variation to the
contract price shall be made
(6-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
11. CONNECTION
The required arrangements regarding the connection between the substation with the
network and transformer with the switchgear shall be as follows:
11.1 33KV CONNECTION
The incoming connection to the 33 kV isolator shall be by a flexible single core cable with
one end to be permanently connected to the incoming side of the isolator, or be connected after
rewound the cable so the box to be of air insulated and easily worked . The other end to be of
clamp for over head line connection operated from the ground by the telescopic insulating rod
(the rod is to be part of the S/S).
11.2 11 KV CONECTIONS :
The outgoing feeders of the 11 KV switchgear shall be connected to the line as for the 33KV
side .
11.3 TRANSFOMER CONNECTION
The connection between transformer with H.T & L.T switchgear shall be single core cables.
All the connection & live parts to be protected against direct touch so that the connection to the
transformer on 33KV and 11KV sides shall be through plug – in termination.
11.4 CABLES
The 33&11kv cables are to be of flexible type EPR single core copper conductor and
according to IEC recommendation:
The 33kv cable for incoming to be 3× 1× 150 sq mm cross section EPR type of 30 meter length
with suitable clamps.
The 11 kV cable for outgoing to be 3× 1× 150 sq mm cross section EPR type of 50 meter
length for each feeder.
For transformer connection the cables to be 3× 1× 150 sq mm XLPE TYPE ON 33KV
SIDE AND 6× 1× 400 sq mm XLPE type on 11kv side for 16 MVA mobile substation and 3×1×400
Sq. mm. XLPE type for 10 MVA substation. Each cable has to be mounted on moving drum with
arrangement for the connection on the side of the switchgear. the drum to be mounted on a stand
fixed to the trailer with easy movable action for pulling & rewinding the cable.
(7-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
14.2 The document to be furnished by the successful tendrer in English language include five copies of
the following drawing within two months from the date of the order .
• Schedule of the anticipated shipping dates.
• Installation drawings.
• Out lined drawings of the S/S , and single line diagram
• Sectional elevation of all part of S/S
• General arrangement and schematic diagram of all equipment
• One set of reproducible print (velograph ) tracing cloth etc of all approved drawings
• Two copies of final as built drawings for each s/s.
NOTE :
It must be noted that all drawings are subjected to approval before manufacturing .
15. PACKINGS
The supplier will pack or protect the goods in the most appropriate manner . He will be
responsible for any loss or damage arising from careless packing or protection unto the place of
final destination
After completion of the inspection and tests at the factory each item shall be packed for
export shipment.
All parts provided for shipping purposes only and which are to be removed at the time of
erection shall be conspicuously tagged .The method of packing shall be such as to protect all of the
items against excessive corrosion or dampness , and shall afford adequate protection against
breakage or other injury , or loss due to breakage of cases or crates from the time leaves the
factory until finally inst. allied during which time the apparatus will travel by rail , by a long sea
voyage again by rail or truck to the site of the stores . The apparatus will also undoubtedly stand
on wharves and in the open during and in between periods of transportation and will there be
exposed to heavy rains , hot sun , humid climate and sudden changes of temperature .
Owing to the numerous handling, extra –ordinary care should be given to the packing of the
equipment and especially the item having insulating material to prevent the injury due to
moisture from sources external to the packing or from excessive condensation with the packing .
16. INSPECTION
The material shall be subject to inspection and test by our inspectors at any time during
manufacturing.
(8-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
The manufacture shall provide all inspection facilities for the said inspection and testing . All
testing and inspection shall be made at the place of manufacture .
The inspector shall have the right of rejecting any portion of the material at any time during
manufacture if it does not meet with the requirements of this specification in all particulars . He
shall have the right of overseeing the packing and shipping of all materials to be supplied.
A. TYPE TEST :-
These tests are in general , those detailed in the IEC standards which pertain to the
equipment being tested equipment type test approve the general design of the equipment . the
manufacturer may submit test certificates of tests which have been carried out on identical
equipments.
The inspector after referring to the COE may accept such certificate in lieu of the
specified type test or to reject them .
The type test prescribed shall be carried out in all cases where such certificates are not
available or are rejected.
The type test shall be carried out according to the IEC standards .
certified test certificates issued by KEMA or any other qualified laboratory after agreement
with the purchaser for type tests carried out on identical equipment will be accepted in lieu.
B. routine test :
The routine test shall be carried out on all equipment according to latest IEC standards :-
18. guarantee:-
The tender shall confirm that mobile substations against defects arising from faults in
design, materials and workmanship, for a period of (12) months from commissioning or (18)
months from delivery whichever period expires earlier.
(9-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
SCHEDULE "A"
SCHEDULE OF GUARANTEED PERFORMANCE AND OTHER TECHNICAL PARTICULARS
The schedule is to be fully completed by the tenderer to provide detailed characteristics of
the equipment and materials offered, which shall be guaranteed. This is an important point which
shall be taken into consideration during tender analysis.
TRANSFORMERS:
(10-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(11-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(12-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
specification offered
# Description Unit
11kV 33kV
1 make
2 Impulse voltage withstand (1.2/50 wave) KV(peak)
3 I min.power frequency withstand voltage KV.(r.m.s)
4 Rated short time current (3 sec) K.A(r.m.s)
5 Temperature rise of windings on °C
continuous operation at rated current &
output
6 For feeder circuit:
a- Type
b- Accuracy class
c- Transformation ratio
d- Current ratio error %
e- Phase displacement min
7 For transformer circuit:
a. Over current & instrument
1- Type
2- Accuracy class
3- Transformation ratio
4-Current ratio error
5-Phase displacement
b. Differential
1- Type
2- Accuracy class
3- Transformation ratio
4- Correction C.T. ratio
5-Current ratio error
6-Phase displacement
8 For metering transformer circuit
1- Type
2- Accuracy class
3- Transformation ratio
4-Current ratio error
5-Phase displacement
9 For metering Auxiliary Transformer
circuit
1- Type
2- Accuracy class
3- Transformation ratio
4-Current ratio error
5-Phase displacement
(13-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(14-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
SCHEDULE (B)
OIL CHARACTERISTICS TABLE (TO BE COMPLETED BY THE TENDERER)
(15-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(16-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(17-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(18-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
(19-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
Transformer protection indication relays (BUCHHOLZ , Oil. Temp., WINDING .Temp., GAS
RECIEVER, PRESSURE RELIEFVALVE.)
23. SCHEDULE OF COMMON MATERIAL FOR BOTH (10&16) MVA MOBILE S/S.
23.1 NEUTRAL EARTHING RESISTOR AS MENTIONED IN ITEM (12)
23.2 DC SUPPLY AS MENTIONED IN ITEM (10)
23.3 CONTROL BOARD:-
The transformer control board contain auxiliary relays, horn for trip singal, bell for alarm
signal with selector switch and lamp for each to stop the sound and to glow a lamp for permanent
signal , signaling lamps , auxiliary relays, and flag relays to indicate all tripping and alarm
signals with reset push - button as follows :-
1- Buchholz trip
2- Winding temperature trip
3- Oil temperature trip
4- Gas receiver of O.L.T.C trip
5- Pressure relief valve trip
6- Buchholz alarm
7- Winding temperature alarm
8- Oil temperature alarm
9- Low oil level alarm
10- O.L.T.C AC failure alarm
other flag relays are required:
11- O/C & E/F relays on 33kv trip
12- O/C & E/F relay on 11kv trip
13- E/F relay of N.E.R trip
14- E/F relay of open - delta trip
(20-21)
Technical Specification of 33/11 kV Mobile Sub-Station for 1×10 & 1×16 MVA
23.4 AC and DC distribution boards: contains AC and DC MCCB’s and MCB’s of sufficient number
the following flag relays are required:-
EARTHING EQUIPMENT:-
Earthing rods 6nos
Suitable connector clamp 6 nos
NOTES
• Ordinary and emergency lighting should be provided
• Single line diagrams for mobile 10MVA and 16 MVA substations are enclosed.