7SR105
7SR105
3kV SWGR
FEEDER TAG 450kW MOTOR FEEDER
1 CT RATIO (PHASE) 150/5
CT RATIO (EARTH) 150/5
RELAY TYPE & TAG SIEMENS 7SR105
RELAY SETTING
PROTECTION
ANSI NO. SETTINGS RANGE EXISTING SETTINGS RECOMMENDED SETTINGS REMARKS
FUNCTIONS
MOTOR CONFIGURATION
Full Load Current 0 to 10000 A 100 A 100 A
Rated output 0 to 1000000 kW 450 kW 450 kW
Rated Power Factor 0.05 to 1 0.85 0.85
Rated Efficiency 0.1 to 100 % 95.5 95.5
Service Factor 1.01 to 1.5 1.20 1.20
MOTOR Hot Stall Time 1 to 200s 7s 7s
CONF Cold Stall Time 1 to 200s 11 s 11 s
Locked Rotor Current 1 to 100 x FLC 5 x FCL 5 x FCL
Start Time 1 to 200s 4s 4s
49 Motor Stop Current 0.05 to 0.2 x Itheta 0.1 x Itheta 0.1 x Itheta
49 Motor Stop Delay 0 to 1 s 0s 0s
49 Thermal Overload Enabled, Disabled Enabled Enabled
49 49 Char IEC IEC IEC
49 Tauh Heating Constant 0.5 to 1000 min 100 min 100 min
49 Taus Starting Constant 0.005 to 1 x Tauh 0.600 x Tauh 0.600 x Tauh
49 Tauc Cooling Constant 1 to 100 x Tauh 10 x Tauh 10 x Tauh
49 Hot/Cold Ratio Enabled, Disabled Disabled Disabled
49 Hot/Cold Ratio Setting 1 to 100 % - -
49 Capacity Alarm Enabled, Disabled Disabled Disabled
49 Capacity Alarm Setting 50 to 100 % - -
49 Load Alarm Enabled, Disabled Disabled Disabled
49 Load Alarm Setting 0.5 to 1 Itheta - -
49 Overload Alarm Enabled, Disabled - -
49 Restart Inhibit Mode Off, Auto, Capacity Off Off
49 Restore After Power Down Enabled, Disabled Disabled Disabled
LOCKED ROTOR (STALL) PROTECTION
14-1 setting 0.05 to 10.00 xIn 6 xIn 6 xIn
14-1 delay 0 to 14400 s 0.30 s 0.30 s
14
14-1 Control Stopped, Running, No Accel, Stopped Stopped
None
START PROTECTION
66 Number Of Starts Enabled, Disabled Enabled Enabled
66 Max Number Of Starts 1 to 20 3 3
66 Max Start Period 1 to 60 min 15 min 15 min
66 66 Start Inhibit Delay 1 to 60 min 15 min 15 min
66 Enable Time Between Enabled, Disabled Disabled Disabled
66 Time Between Starts 1 to 60 min - -
66 Restore After Power Down Enabled, Disabled Disabled Disabled
START TIME SUPERVISION
48-1 Start Time Supervision Enabled, Disabled Enabled Enabled
48-1
48-1 Delay 0 to 14400 s 25 s 25 s
PHASE UNBALANCE PROTECTION